The SAMSON 3730-3 is the HART-communicating smart electropneumatic positioner of the 3730 family, using a hybrid platform of analog PD control plus a microprocessor, with integrated EXPERTplus valve diagnostics. It is the most common version for 4-20 mA plus HART service. Following official data sheet T 8384-3 EN and mounting instructions EB 8384-3 EN, this article sets out the technical data and gives the 16-digit ordering code bit by bit, with special attention to the Ex field, the mutually exclusive additional-equipment group and the housing material field.

I. Product Positioning

ItemDescription
BrandSAMSON (independent German brand)
Series3730 family, type 3730-3 (HART version)
Positioner typeSingle-acting or double-acting smart electropneumatic positioner
Control principleAnalog PD control plus microprocessor (hybrid platform)
Communication4-20 mA + HART (two-wire)
Self-diagnosticsEXPERT / EXPERTplus with NAMUR NE 107 status indication
Ex protectionMainly intrinsically safe Ex ia, plus Ex nA and dust protection; the 3730-3 itself is not flameproof Ex d
Key data sheetsT 8384-3 EN, EB 8384-3 EN, NA 0122

Source: SAMSON official data sheet T 8384-3 EN, mounting and operating instructions EB 8384-3 EN (firmware 1.61), master data sheet NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.1 (bit-by-bit table). Bit positions marked with an asterisk must be confirmed with the official ordering tool.

The 3730-3 belongs to the 3730-0 to 3730-5 family: 3730-0/1/2 have no fieldbus, 3730-4 is PROFIBUS PA and 3730-5 is FF. The pressure-monitoring 3730-6 (14-digit code, data sheet T 8384-6 EN) and the flameproof 3731 family (T 8387-3/5 EN) are separate designs and do not use the 16-digit bit table here.

SAMSON 3730-3 smart electropneumatic positioner
SAMSON 3730 series positioner, same-series illustration, not the actual 3730-3; parameters subject to the official catalog

II. Main Technical Data

ParameterValue / note
Input signal4-20 mA two-wire (HART type: max load 410 ohm)
Supply air1.4-7.0 bar (20-105 psi), software limit to 1.4 / 2.4 / 3.7 bar
Max output signal pressure0-7 bar (0-105 psi), not above supply
Rated linear travel3.6-300 mm (3.6-30 mm direct-mounted on 3277; 3.6-300 mm per NAMUR / VDI-VDE 3847)
Opening angle24 deg to 100 deg (rotary, VDI/VDE 3845)
CharacteristicLinear / equal percentage / reverse equal percentage / user-defined, deviation <=1%
Accuracy / hysteresis / sensitivityTypical ±0.5% / <=0.3% / <=0.1% (subject to official catalog)
Air consumptionIndependent of supply air, < 110 l/h
Ambient temperature-55 to +85 C (varies with housing and Ex option; Ex devices further limited by certificate)
Degree of protectionIP66 / NEMA 4X
Electrical connectionM20x1.5 gland (6-12 mm clamping), terminals 0.2-2.5 mm2
WeightDie-cast aluminum approx. 1.0 kg; stainless steel approx. 2.2 kg
Functional safetySupports SIL 2 / SIL 3 (per model and configuration, IEC 61508 / 61511)

Source: SAMSON official data sheet T 8384-3 EN, mounting and operating instructions EB 8384-3 EN (firmware 1.61), master data sheet NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.1 (bit-by-bit table). Bit positions marked with an asterisk must be confirmed with the official ordering tool.

III. HART Communication and Configuration

ItemDescription
Signal superpositionHART digital signal superimposed on 4-20 mA; communicator or asset management reads/writes configuration and diagnostics
Local operationSingle rotary pushbutton (turn to select, push to confirm) plus LCD, reading rotatable by 180 degrees
Software toolTROVIS-VIEW via SSP interface (RS-232 / USB) with the 3730-3 database module
AutotuneINIT starts initialization and closed-loop operation resumes immediately afterwards
DiagnosticsEXPERTplus control valve expert diagnostics with NAMUR NE 107 status indication
Feedback optionsOptional limit contact, position transmitter, external position sensor, analog/digital inputs

Source: SAMSON official data sheet T 8384-3 EN, mounting and operating instructions EB 8384-3 EN (firmware 1.61), master data sheet NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.1 (bit-by-bit table). Bit positions marked with an asterisk must be confirmed with the official ordering tool.

IV. 16-Digit Ordering Code, Bit by Bit

FieldOptionCodeMeaning
P1Explosion protection0 / 1 / 3 / 5 / 80 none; 1 ATEX Ex ia IIC Gb + Ex ia IIIC T80 Db; 3 CSA Ex ia IIC T6; 5 dust Ex tb only; 8 Ex nA / Ex tc
P2Inductive limit switch0 / 10 none; 1 SJ2-SN (normally closed contact)
P3Solenoid valve0 / 40 none; 4 with 24 V DC
P4-P7Additional equipment (mutually exclusive)1000 / 0100 / 0010 / 0001 / 0000Position transmitter (P4=1, 4-20 mA feedback) / split position sensor (P5=1 or 2, requires P2=0, P10=0) / analog input (P5=3) / leakage sensor (P6=1) / digital input (P7=2) / none (all 0)
P8Self-diagnostics0 / 40 standard EXPERT (default); 4 EXPERTplus enhanced diagnostics
P9Fixed field0Always 0
P10Housing material0 / 10 aluminum (standard); 1 stainless steel
P11Fixed field0Always 0
P12Fixed field0Always 0
P13Special application0 / 1 / 2 / 6 / 7None / free of coating-affecting substances / rear 1/4 NPT exhaust port / additional exhaust plus VDI/VDE 3847 adapter / additional exhaust
P14Fixed field0Always 0
P15-P16Special version (combined with P1)00 / 12 / 34 / 13 / 14 / 20Standard / IECEx Ex ia / Ex tb / Ex nA + Ex tc / EAC Ex ia / 2Ex ic + 2Ex nA

Source: SAMSON official data sheet T 8384-3 EN, mounting and operating instructions EB 8384-3 EN (firmware 1.61), master data sheet NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.1 (bit-by-bit table). Bit positions marked with an asterisk must be confirmed with the official ordering tool.

The full ordering number is "3730-3" plus 16 digits. Example: 3730-3 1001000400000000 means P1=1 (ATEX intrinsic safety), P2=0, P3=0, P4-P7=1000 (position transmitter / 4-20 mA feedback), P8=4 (EXPERTplus), P10=0 (aluminum), the rest standard. If "feedback" means a discrete limit switch rather than continuous 4-20 mA, use P2=1 instead, e.g. 3730-3 1100000400000000.

V. Selection Notes and Common Models

PointNote
Define communication first4-20 mA + HART -> 3730-3; no fieldbus -> 3730-0/1/2; PA -> 3730-4; FF -> 3730-5
Then define ExFill P1 and P15-P16 combination code by area certification; this family is mainly intrinsically safe, with no flameproof Ex d
When flameproof is requiredSwitch to 3731-3 (Ex d flameproof, data sheet T 8387-3 EN, 15-digit code); do not promise Ex d on a 3730-3
Pressure monitoring needUse 3730-6 (14-digit code, T 8384-6 EN); for SIS applications use 3730-6 TS or the 3731 family
Additional equipmentP4-P7 is a mutually exclusive group, fill only one at a time; distinguish 4-20 mA transmission from a discrete limit feedback
Confirm the codePositions marked with an asterisk and the final full code are subject to the SAMSON official selection/ordering tool

Source: SAMSON official data sheet T 8384-3 EN, mounting and operating instructions EB 8384-3 EN (firmware 1.61), master data sheet NA 0122, and the SAMSON smart positioner specification sections 3.2/3.4.1 (bit-by-bit table). Bit positions marked with an asterisk must be confirmed with the official ordering tool.

Red line: Ex ia intrinsic safety and Ex d flameproof enclosure are different protection types with different wiring and cover-opening rules and must not be mixed. The 3730-3 is intrinsically safe, not flameproof; flameproof applications go to the 3731 family. Where the data sheet gives no value, state "subject to the official catalog / ordering tool" and do not invent.

Selection guide: Selection sequence for 3730-3: fix 4-20 mA + HART first, fill P1/P15-P16 Ex codes by area certification, then fill limit switch, solenoid and additional equipment (mutually exclusive group) in P2/P3/P4-P7, and finally narrow by P8 diagnostics and P10 housing material, relying on the 16-digit code from the official ordering tool.

Common models: Common configurations: 3730-3 with position transmitter (4-20 mA feedback) plus EXPERTplus (1001000400000000); with discrete limit switch (1100000400000000); aluminum or stainless housing, ATEX/IECEx/CSA/NEPSI Ex combinations. Flameproof needs go to 3731-3, pressure monitoring to 3730-6.

If you are checking a 3730-3 ordering code, or are unsure whether P4-P7 should be a position transmitter or a limit switch, or whether the P1 Ex code matches the site area, please share the certification requirement and feedback method. We can check the code bit by bit against the official table.