Fisher 2625 / VBL / SS-263 Volume Boosters - Working Principle & Applications
Release time:2026-11-23 01:35:36 | Views:

Fisher 2625, VBL and SS-263 are pneumatic volume boosters used with digital valve positioners to amplify the positioner output flow and increase actuator stroke speed. All three have a fixed 1:1 pressure ratio and use dead band, soft seats and a bypass restriction for stable, fast operation, but differ markedly in flow capacity, connections and actuator suitability.

I. Product Positioning

Item2625 / 2625SST / 2625NSVBLSS-263
PositioningGeneral purpose (standard / stainless / nuclear)Small, low costHigh-flow double-acting piston type
ManualD100348X012D103393X0CND103592X012
Pressure ratioFixed 1:1Fixed 1:1Fixed 1:1
Max signal pressure10.3 bar (150 psig)5.5 / 10.3 bar (by model)10.3 bar (150 psig)
Max supply Cv3.74 / 4.982.59.5
SIL3Yes for 2625 / 2625SSTNot listed in manualYes

Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12).

Pneumatic volume booster, illustration
Pneumatic volume booster, illustration only, not a Fisher product; for illustration only, not the actual model; parameters subject to the official data sheet

II. Working Principle

ModelPrincipleBypass / dead band function
2625 seriesInput signal acts on a diaphragm and balances output pressure; fixed dead band set by supply/exhaust seat spacingBypass limit affects stability only, not dead band; small signals move the actuator, large signals open the booster
VBLFixed dead band, soft seats and an integral formed bypass restriction eliminate positioner saturation and travel oscillationBypass is set 4 turns open from fully closed at the factory and can be slowly screwed in to tune response
SS-263Dual-port design amplifies both supply and exhaust flow under precise positioner signal control; essentially a higher-capacity 2625Low-noise exhaust passages and multiple integrated diagnostic ports; one unit can replace several 2625 units

Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12).

Common caution: a booster only increases stroke speed; precise position control still requires a positioner; for on/off duty the bypass must be fully closed (clockwise to the stop). The booster and positioner must share the same air supply and must never be supplied separately.

III. Key Technical Data Comparison

Parameter2625 seriesVBLSS-263
Supply pressureDiaphragm at or below 2.8 bar; piston at or below 10.3 barShared with positioner (67D/67DR/95H)At or below 10.3 bar
Signal port1/4 NPT1/4 NPT1/4 NPT
Supply / output ports3/4 NPT1/2 NPTSupply 1 NPT; output 1 or 1-1/4 NPT
Ambient temperatureStandard -40 to 71 C; high 0 to 121 C; low -60 to 65 C (CUTR); 2625NS -40 to 93 C-40 to 93 C-40 to 71 C
WeightAluminium 2.3 kg / stainless 4.8 kgApprox. 1.0 kgAluminium 3.6 kg / stainless 10.8 kg
Ex classificationATEX II 2 GD; Ex h IIC / IIICATEX II 2 GDATEX II 2 GD; Ex h IIC / IIIC

Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12).

IV. Flow Coefficients and Version Differences

Model / combinationSupply CvExhaust CvNote
2625, 9.5 mm supply / 2.4 mm exhaust3.740.23Small exhaust, nominal dead band 2%
2625, 9.5 mm supply / 9.5 mm exhaust3.742.29Nominal dead band 3.5%
2625, 12.7 mm supply / 12.7 mm exhaust4.983.40Nominal dead band 5%
VBL-1 / VBL-22.51.1Input pressure 5.5 / 10.3 bar
VBL-3 / VBL-42.51.8Higher exhaust capacity
SS-2639.59.5C1 = 35, Xt = 0.77; high-flow double-acting

Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12).

The four VBL versions combine input pressure (5.5 / 10.3 bar) with exhaust capacity (Cv 1.1 / 1.8): VBL-1/-2 have exhaust Cv 1.1, VBL-3/-4 have 1.8. The 2625 offers 2 supply ports by 3 exhaust ports in any combination (the 3/32" exhaust is available on aluminium only). Select the smallest Cv/Cg that meets the stroke speed; oversizing can destabilize the loop.

V. Applications and Selection Guide

ConditionRecommended modelReason
Single-acting + small flow + low costVBL (VBL-3/-4 have stronger exhaust)Compact and economical
Single-acting + high flow / long travel2625 / 2625SST / 2625NSHigher Cv; 2625NS for nuclear
Double-acting piston + high flowSS-263Dual-port supply and exhaust amplification; replaces several 2625 units
SIL3 safety loop2625 / 2625SST / SS-263exida SIL3; no SIL listed in the VBL manual
Piped-away vent / flammable gas supply2625 with 1/2 NPT remote exhaustAvoid venting flammable gas locally
Low temperature -60 C2625 low-temperature construction + CUTRLow-temperature elastomer option

Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12).

Installation points: one regulator should supply both positioner and booster, with Fisher 67D / 67DR / MR95H recommended and a 262K high-flow filter upstream; air must be clean, dry and oil-free; do not use PTFE tape on pneumatic threads, use thread sealant instead; mount the booster close to the actuator. The SS-263 is ordered only as an accessory of a complete control valve, not separately.

Selection guide: Select in the order of actuator action, required stroke speed and Cv, then material, approvals and connections. A booster does not replace a positioner and has no position control capability; all three have a 1:1 pressure ratio and are distinguished by flow capacity, not by a pressure gain ratio.

Common models: 2625 / 2625SST / 2625NS (single-acting general, stainless, nuclear); VBL-1 to VBL-4 (small, low cost); SS-263 (high-flow double-acting piston).

If the valve strokes too slowly, the positioner output flow seems insufficient, or you are choosing among 2625, VBL and SS-263, please share the actuator model, stroke time and air supply conditions. We can estimate the required Cv together and help avoid oscillation from oversizing or sluggishness from undersizing.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.