| Fisher 2625 / VBL / SS-263 Volume Boosters - Working Principle & Applications | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-23 01:35:36 | Views: | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Fisher 2625, VBL and SS-263 are pneumatic volume boosters used with digital valve positioners to amplify the positioner output flow and increase actuator stroke speed. All three have a fixed 1:1 pressure ratio and use dead band, soft seats and a bypass restriction for stable, fast operation, but differ markedly in flow capacity, connections and actuator suitability. I. Product Positioning
Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12).
II. Working Principle
Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12). Common caution: a booster only increases stroke speed; precise position control still requires a positioner; for on/off duty the bypass must be fully closed (clockwise to the stop). The booster and positioner must share the same air supply and must never be supplied separately. III. Key Technical Data Comparison
Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12). IV. Flow Coefficients and Version Differences
Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12). The four VBL versions combine input pressure (5.5 / 10.3 bar) with exhaust capacity (Cv 1.1 / 1.8): VBL-1/-2 have exhaust Cv 1.1, VBL-3/-4 have 1.8. The 2625 offers 2 supply ports by 3 exhaust ports in any combination (the 3/32" exhaust is available on aluminium only). Select the smallest Cv/Cg that meets the stroke speed; oversizing can destabilize the loop. V. Applications and Selection Guide
Source: Fisher 2625 series manual D100348X012 (2020.05); VBL manual D103393X0CN (2017.09); SS-263 manual D103592X012 (2021.12). Installation points: one regulator should supply both positioner and booster, with Fisher 67D / 67DR / MR95H recommended and a 262K high-flow filter upstream; air must be clean, dry and oil-free; do not use PTFE tape on pneumatic threads, use thread sealant instead; mount the booster close to the actuator. The SS-263 is ordered only as an accessory of a complete control valve, not separately. Selection guide: Select in the order of actuator action, required stroke speed and Cv, then material, approvals and connections. A booster does not replace a positioner and has no position control capability; all three have a 1:1 pressure ratio and are distinguished by flow capacity, not by a pressure gain ratio. Common models: 2625 / 2625SST / 2625NS (single-acting general, stainless, nuclear); VBL-1 to VBL-4 (small, low cost); SS-263 (high-flow double-acting piston). If the valve strokes too slowly, the positioner output flow seems insufficient, or you are choosing among 2625, VBL and SS-263, please share the actuator model, stroke time and air supply conditions. We can estimate the required Cv together and help avoid oscillation from oversizing or sluggishness from undersizing. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |