The Fisher FIELDVUE digital valve controller evolved from DVC6000 through DVC2000 to DVC6200. The DVC2000 is the entry-level unit with a local LCD and four-button LUI; the DVC6000 was the previous mainstream platform with HART and FF; the DVC6200 is the current mid-to-high platform with multiple protocols, ValveLink diagnostics and a SIL3 variant. This article compares the three generations and covers interface and spare-part points for upgrades.

I. Product Positioning

ModelGenerationProtocolLocal interfaceAmbient rangeMax inlet pressure
DVC2000Entry level, general throttlingHART 5 (4-20 mA)LCD + 4-button LUI (multi-language)-40 to +80 C7 barg (100 psig)
DVC6000Previous mainstreamHART 5 / FFNo LCD, LED indicationPer series manualPer series manual
DVC6200H/F/PCurrent mid-to-high / projectHART 5/7, FF, PROFIBUS PANo LCD / no keys, LED status-40 to +85 C (fluorosilicone -52 C)10 barg (145 psig)
DVC6200 SISSafety instrumented systemHART 5 (HART 7 optional)No LCD / no keys, LED status-52 to +85 C10 barg (145 psig)

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Fisher DVC6200 digital valve controller
Fisher DVC6200 digital positioner, same-series illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Key Differences Across Generations

FeatureDVC2000DVC6000DVC6200
Position feedbackHall-effect non-contactFeedback arm + magnet strip (mechanical)Hall-effect non-contact magnetic array
Local interfaceLCD + 4-button LUI (12 languages)No LCDNo LCD / no keys, condition indicator
DiagnosticsBasic device diagnosticsBasic diagnosticsValveLink: online / offline / performance, NE107
Partial stroke testNoNoODV level (HART only) or SIS standard
Housing materialAluminiumAluminiumAluminium or stainless (2B)
Remote mountNoYes (DVC6015/6025/6035, etc.)Yes (RM: DVC6205 + DVC6215)
SIL capabilityNot declaredNot declaredSIL3 (exida), separate SIS variant
PositioningEntry levelPrevious generationMid-to-high / project / SIS

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

III. Upgrade and Replacement Points

Check itemKey point
Mounting interfaceAll support IEC 60534-6-1/6-2, VDI/VDE 3845 and NAMUR; check actuator mounting face and bracket
Feedback partsDVC2000 and DVC6200 use magnet strips / arrays; DVC6000 uses a feedback arm plus magnet strip; swap requires new bracket and magnet kit
Pneumatic portsDVC6200: 1/4 NPT supply/output, 3/8 NPT vent, electrical 1/2 NPT or M20
Signal and protocolHART loops can be replaced directly; FF / PA require DVC6200F / P and cannot be interchanged
DiagnosticsValveLink online/offline diagnostics and NE107 become available only after moving to DVC6200
Ex approvalRecheck CSA / FM / ATEX / IECEx / NEPSI codes against the site area classification

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

IV. Discontinuation and Spare Parts

ItemDescription
DVC6200 HW1Discontinued; official replacement is DVC7K or the current DVC6200 HW2
DVC6200 HW2Current hardware version; confirm compatibility before swapping HW1 parts
DVC6000 sparesTypical I/P converter kit 38B6041X152, cover 38B9580X012, magnet strip 49B7986X012; per official parts list
DVC6200 sparesExample order code GE40184XAT2 (HART / Housing B / aluminium / with I/O / nitrile / double-acting); verify against nameplate
Mounting bracketsGG12343X012 for 657/667 size 30-60; GG12361X012 for size 70/76/87; match with magnet strips

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

V. Selection Guide and Common Models

Replacement sequence: protocol first, then actuator and mounting interface, then diagnostics and safety needs. For HART loops consider DVC2000 (entry) or DVC6200H (diagnostics / multi-protocol); FF uses DVC6200F, PA uses DVC6200P, and SIS uses DVC6200-SIS. When retrofitting an old DVC6000, note that its feedback arm and magnet kit cannot be reused directly with DVC6200, and confirm HW1/HW2 compatibility before replacing discontinued parts.

Selection guide: The three generations are not a simple like-for-like replacement. DVC2000 keeps the local LCD and buttons for applications without complex diagnostics; DVC6200 adds ValveLink diagnostics, multiple protocols and a SIL3 variant. Cross-protocol upgrades require a different model, not just a diagnostic code change.

Common models: DVC2000 (entry HART), DVC6000 (previous generation, being replaced), DVC6200H / F / P (current mainstream), DVC6200-SIS (safety loops), DVC7K-H (new platform replacing discontinued DVC6200 HW1).

If you have a DVC6000 or DVC6200 HW1 and are weighing an upgrade to DVC6200 HW2 or DVC7K, please share the old nameplate, actuator model and site protocol. We can review brackets, feedback parts and order codes together to reduce retrofit downtime.