Home » Service & Support » Technical Documentation
Fisher DVC6200 Diagnostic Levels - Complete Comparison (HC/FD/AD/PD/ODV/PS & Pro
Release time:2026-11-23 01:35:36 | Views:

The diagnostic capability of a DVC6200 is set by segment 9 of the order code, ranging from basic communication to partial-stroke testing. HC and FD provide identical diagnostic functions but apply to different protocols; AD / PD require ValveLink software; ODV is a fourth instrument level above PD and is valid for HART only; PS applies to the FF version only. This article gives the full level comparison and a protocol applicability matrix.

I. Product Positioning

ItemDescription
BrandFisher (Emerson)
SeriesFIELDVUE DVC6200 digital valve controller
Diagnostic segmentSegment 9 (Diagnostics Level); some documents group it with segment 8/9
LevelsAC, HC, FD, AD, PD, ODV, PS (HCFD is the combined notation for HC/FD)
SoftwareValveLink: offline diagnostics, online performance diagnostics, valve signature, PST
Alarm schemeNAMUR NE107 status classification (red / yellow / green condition indicator)
Key documentsD104363X0CN, D103409X012, D103605X012

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Fisher DVC6200 digital valve controller
Fisher DVC6200 digital positioner, same-series illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Full Diagnostic Level Comparison

CodeNameCapabilitiesProtocol applicability
ACAuto calibrationBasic positioner function with remote interaction and auto calibration via HART communicatorDVC6200H only; not F / P
HCHART communication diagnosticsBasic digital communication with alarms; ValveLink compatibleDVC6200H only (HART)
FDFieldbus diagnosticsIdentical to HC but for FOUNDATION fieldbusDVC6200F only (FF)
ADAdvanced diagnosticsHC / FD plus offline diagnostics (ValveLink required)H / F; not DVC6200P
PDPerformance diagnosticsAll AD functions plus online diagnostics (ValveLink required)H / F; not DVC6200P
ODVOptimized Digital ValveAll HC/AD/PD functions plus PST and lead/lag set point filterDVC6200H only (HART); not offered on F / P
PSPartial stroke testPartial stroke action test for the FF version onlyDVC6200F only; not H / P

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

HCFD is a combined notation in the ordering table: write HC in segment 9 for HART (DVC6200H) and FD for FF (DVC6200F); the diagnostic content is identical. ODV is confirmed as the fourth Instrument Level above PD in Fisher manual D103605X012, and the partial stroke test is available only at that level.

III. Protocol Applicability Matrix

Protocol / modelACHC / FDADPDODVPS
DVC6200H (HART 5/7)YesHCYesYesYesNo
DVC6200F (FF)NoFDYesYesNoYes
DVC6200P (PROFIBUS PA)Non.a.n.a.n.a.NoNo
DVC6200 SIS (HART)Per codeHCPer codePer codePer code (PST standard)No

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Red lines: ODV is valid for HART only and is not offered on DVC6200F or DVC6200P; PS is available on the FF version only. DVC6200P does not support AD / PD, so ValveLink offline and online diagnostics cannot be promised for it. The SIS variant has PST as standard, which is a different path from obtaining PST via the ODV option on the standard HART version.

IV. Diagnostic Capabilities and Tools

Capability / testDescriptionRequired level / tool
Basic communication and alarmsDevice status and alarms, LED condition indicationFrom HC / FD
Offline diagnosticsValve signature, step response etc. with the valve out of serviceFrom AD + ValveLink
Online performance diagnosticsIn-service trends, deviation statistics and performance assessmentFrom PD + ValveLink
Partial stroke testVerify valve movability without interrupting the processODV (HART) / SIS standard
Lead / lag set point filterSet point filtering to improve control qualityODV (HART)
NAMUR NE107Status classified and indicated per NE107By model and level

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

V. Selection Guide and Common Models

First choose the base model by fieldbus protocol (H, F, P or SIS), then set the diagnostic level by maintenance strategy: HC/FD for communication and alarms only; AD for offline valve signature testing; PD for online performance diagnostics; ODV when PST is required on a HART loop; PS when PST is required on an FF loop. Do not promise AD/PD/ODV on DVC6200P. Once a level is specified, confirm that the customer has the matching software and host system, such as HART acquisition or asset management capability.

Selection guide: The diagnostic level is segment 9, not a standalone model. Select in the order protocol, maintenance need, software availability, and strictly respect that ODV is HART only, PS is FF only, and the P version has no AD/PD.

Common models: DVC6200H + HC / AD / PD / ODV (full HART range); DVC6200F + FD / AD / PD / PS (FF range); DVC6200P with basic diagnostics only; DVC6200-SIS with PST and SIS diagnostics standard.

If you are unsure whether a DVC6200 is coded HC, PD or ODV, or whether the site software can read the corresponding diagnostic data, please send us the order code and maintenance requirements. We can review it segment by segment and explain which functions are options and which are standard.