The standard Fisher DVC6200 housing is A03600 low-copper aluminium. For corrosive, food and pharmaceutical, or coastal high-humidity service, a stainless steel housing is available. Stainless is not a separate series; it is obtained by writing code 2B in segment 2 of the order code. This article explains the 2A/2B material codes, the segment 3 housing-type restriction, and the differences in weight, elastomer and temperature.

I. Product Positioning

ItemDescription
BrandFisher (Emerson)
SeriesFIELDVUE DVC6200 digital valve controller
Standard housingA03600 low-copper aluminium (segment 2 code 2A)
Stainless optionSegment 2 code 2B, stainless with fluorosilicone elastomer, Housing B only
Typical serviceCorrosive areas, food and pharma, coastal humidity, frequent washdown
EnclosureCSA / FM Type 4X, IP66; ATEX / IECEx IP66
Key documentsD104363X0CN, D103409X012, D103557X012

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Fisher DVC6200 digital valve controller
Fisher DVC6200 digital positioner, same-series illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Segment 2 Housing Material Codes

CodeMaterialKey note
2AAluminiumStandard A03600 low-copper aluminium; nitrile elastomer by default; XT option for -52 C with fluorosilicone
2BStainless steelStainless housing with fluorosilicone elastomer; Housing B only (segment 3 code 3A); default low rating -52 C

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Important: 2B is not a free-standing material upgrade. The official ordering table restricts 2B to Housing B (the general housing). Segment 3 code 3B is Housing A, the one-piece aluminium design for Fisher GX valves, and cannot be combined with 2B stainless. Also, the 2B stainless construction includes fluorosilicone elastomer as standard, so the XT extreme-temperature option is normally unnecessary.

III. Stainless vs Aluminium: Key Differences

ItemAluminium (2A)Stainless (2B)
Housing materialA03600 low-copper aluminiumStainless steel
Standard elastomerNitrile (NBR)Fluorosilicone
Low-temperature rating-40 C; XT option to -52 C-52 C by default
Ambient temperature-40 to +85 C-40 to +85 C (fluorosilicone -52 to +85 C)
WeightDVC6200 approx. 3.5 kgDVC6200 approx. 8.6 kg
RM remote mountAvailable (aluminium)Not offered
EnclosureType 4X / IP66Type 4X / IP66
Max inlet pressure10.0 bar (145 psig) or actuator rating, whichever lowerSame

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

IV. Ordering Example and Identification

ItemExample / note
Ordering exampleDVC6200H 1D_2B_3A_4A_5A_6B_7C_8A_PD
Segment meaningHART body / ATEX Ex d / stainless housing / Housing B / fieldbus module n.a. / single-acting direct / no I/O / 0-60 psig gauge / 1/2 NPT + 1/4 NPT / performance diagnostics
Obsolete prefixDVC6200S was an old prefix for stainless DVC6200 and is obsolete; use segment 2B instead
Field identificationRely on the nameplate, serial card and order acknowledgement, not appearance

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

V. Selection Guide and Common Models

Judge whether a real corrosion risk exists: 2A aluminium is sufficient for ordinary indoor or outdoor service; choose 2B stainless for coastal, chemical, acid/alkali or frequent washdown areas and accept the added weight and cost. When specifying 2B, also lock segment 3 to 3A (Housing B); do not combine it with 3B (GX one-piece aluminium) or with the RM remote-mount option. For natural gas service, verify the relevant approvals and seal materials separately.

Selection guide: The sequence is: set protocol and approvals, then housing material and type, then pneumatic action and diagnostics. The key constraints of 2B stainless are Housing B only, fluorosilicone as standard and no RM; these follow a different logic from the XT extreme-temperature option on 2A aluminium and must not be interchanged.

Common models: DVC6200H (HART) + 2B, DVC6200F (FF) + 2B, DVC6200P (PROFIBUS PA) + 2B, and DVC6200-SIS + 2B (stainless SIS version).

If you are undecided between aluminium and stainless housing, or want to check whether a nameplate 2A / 2B entry matches the order code, please contact us. We can review the housing material segment against the medium, site corrosion class and mounting arrangement.