Fisher DVC6205 / DVC6215 Remote-Mount Configuration - Selection (RM Option, 125C
Release time:2026-11-23 01:35:36 | Views:

The standard Fisher FIELDVUE DVC6200 is a one-piece digital valve controller. Where the actuator is exposed to high temperature, strong vibration or restricted space, order code option RM provides a remote-mount configuration: the DVC6205 is the main body (electrical and pneumatic conversion) and the DVC6215 is a separate remote travel sensor. The remote portion is rated up to 125 C, but only in the aluminium construction. This article covers the structure, ratings, ordering notation and application limits.

I. Product Positioning

ItemDescription
BrandFisher (Emerson)
SeriesFIELDVUE DVC6200 digital valve controller
Remote-mount assemblyDVC6205 body + DVC6215 remote travel sensor
Order optionRM (Remote Mount version)
Position feedbackHall-effect non-contact magnetic array, linkage-less and wear-free
ProtocolsHART 5 / HART 7 (DVC6200H); FF (DVC6200F); PROFIBUS PA (DVC6200P)
Remote ratingRemote feedback unit -52 to +125 C; body typically -40 to +85 C
Key documentsD104363X0CN, D103409X012, D103557X012, D103605X012

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Fisher DVC6200 digital valve controller
Fisher DVC6200 digital positioner, same-series illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Split Construction and Working Principle

ComponentModelFunctionLocation
Main bodyDVC62054-20 mA / bus input, I/P conversion, pneumatic amplification and controlBracket or instrument box away from heat
Remote travel sensorDVC6215Magnetic array reads stem position and returns it by cableMounted directly on actuator / near the stem
LinkDedicated cableSignal and power between body and sensorRouting and length per manual
Pneumatic path1/4 NPTBody output pressure directly to actuator diaphragm / cylinderSame as the one-piece version

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

The idea is to separate the heat-generating electrical/pneumatic body from the valve-mounted feedback sensing. The DVC6215 only performs non-contact position detection and tolerates a higher ambient temperature, so it can sit next to a hot valve body, while the DVC6205 is located in a cooler instrument position. A dedicated cable links the two; cable length, connectors and Ex hardware must be confirmed per the manual.

III. Ratings and Technical Data

ParameterDVC6205 / DVC6215 remoteNote
Remote portion rating-52 to +125 CDVC6215 feedback unit; 125 C in aluminium only
Body ambient-40 to +85 C (fluorosilicone -52 to +85 C)Same as standard DVC6200
Linear travel6.5 - 606 mmDepends on mounting
Rotary travel45 - 90 degDepends on mounting
Max inlet pressure10.0 bar (145 psig) or actuator rating, whichever lowerClean dry air or natural gas per ISA 7.0.01
Independent linearityTypical +/-0.50% of output spanPer manual Table 1-2
WeightDVC6205 approx. 4.1 kg; DVC6215 approx. 1.4 kgStandard DVC6200 approx. 3.5 kg
HousingA03600 low-copper aluminium (RM in aluminium only)RM not offered on stainless version
Pneumatic / electrical ports1/4 NPT supply; 1/2 NPT or M20 electricalVent 3/8 NPT
Enclosure / approvalsIP66; CSA / FM / ATEX / IECEx / NEPSI, etc.Per the approval segment of the order code

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

IV. The RM Option in the Order Code

SegmentCodeRemote-mount note
Segment 2 Housing material2A aluminiumRM only in aluminium; 2B stainless does not offer RM
Segment 9 DiagnosticsHC / AD / PD / ODV / PSBy protocol; ODV only for DVC6200H (HART)
Segment 10 Other optionsRMRemote mount: DVC6205 with separate DVC6215 remote travel sensor, rated 125 C
SIS variantDVC6205 SIS + DVC6215RM available for SIS loops; low-bleed relay and PST standard
Obsolete notationDVC6215-205, etc.Prefix+suffix notation is obsolete; use segment codes and confirm by nameplate / order acknowledgement

Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.

Example: DVC6200H 1D_2A_3A_4A_5A_6B_7C_8A_PD_RM means HART body, ATEX flameproof, aluminium, standard Housing B, single-acting direct, no I/O, 0-60 psig gauge, 1/2 NPT + 1/4 NPT, performance diagnostics, remote-mount version. Actual delivery follows the Emerson order acknowledgement, serial card and nameplate.

V. Selection Guide and Common Models

First confirm that a split solution is really needed: RM is worthwhile only when the body can be located in a cooler area; for wiring convenience alone, a one-piece unit with an extended bracket is usually enough. Then check that the remote portion temperature falls within -52 to +125 C; above 125 C this solution is not suitable. Finally confirm aluminium construction and specify diagnostics, protocol, Ex approval and cable accessories item by item.

Selection guide: The sequence is: decide whether a split unit is needed, then check remote temperature and material, then set protocol, diagnostics and Ex approval. RM is an option in segment 10, not a standalone model; it must appear in the full code of DVC6200H / F / P or the SIS variant. The 125 C remote rating and aluminium-only limit must not be relaxed.

Common models: DVC6200H + RM (HART remote mount), DVC6200F + RM (FF), DVC6200P + RM (PROFIBUS PA), DVC6200-SIS + RM (SIS remote mount); hardware: DVC6205 body plus DVC6215 remote travel sensor.

If your actuator runs hot, the mounting space is tight, or you are weighing whether a DVC6205 / DVC6215 split solution is necessary, please share the service conditions and mounting position. We can review the remote rating, housing material and order code together and help avoid a wrong RM entry.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.