The standard Fisher FIELDVUE DVC6200 is a one-piece digital valve controller. Where the actuator is exposed to high temperature, strong vibration or restricted space, order code option RM provides a remote-mount configuration: the DVC6205 is the main body (electrical and pneumatic conversion) and the DVC6215 is a separate remote travel sensor. The remote portion is rated up to 125 C, but only in the aluminium construction. This article covers the structure, ratings, ordering notation and application limits. I. Product Positioning
Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012.
II. Split Construction and Working Principle
Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012. The idea is to separate the heat-generating electrical/pneumatic body from the valve-mounted feedback sensing. The DVC6215 only performs non-contact position detection and tolerates a higher ambient temperature, so it can sit next to a hot valve body, while the DVC6205 is located in a cooler instrument position. A dedicated cable links the two; cable length, connectors and Ex hardware must be confirmed per the manual. III. Ratings and Technical Data
Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012. IV. The RM Option in the Order Code
Source: Fisher Bulletin 62.1 "Digital Valve Controller" D104363X0CN; DVC6200 instruction manual D103409X012 (Table 1-2 Specifications); DVC6200 SIS manual D103557X012; diagnostic levels D103605X012. Example: DVC6200H 1D_2A_3A_4A_5A_6B_7C_8A_PD_RM means HART body, ATEX flameproof, aluminium, standard Housing B, single-acting direct, no I/O, 0-60 psig gauge, 1/2 NPT + 1/4 NPT, performance diagnostics, remote-mount version. Actual delivery follows the Emerson order acknowledgement, serial card and nameplate. V. Selection Guide and Common ModelsFirst confirm that a split solution is really needed: RM is worthwhile only when the body can be located in a cooler area; for wiring convenience alone, a one-piece unit with an extended bracket is usually enough. Then check that the remote portion temperature falls within -52 to +125 C; above 125 C this solution is not suitable. Finally confirm aluminium construction and specify diagnostics, protocol, Ex approval and cable accessories item by item. Selection guide: The sequence is: decide whether a split unit is needed, then check remote temperature and material, then set protocol, diagnostics and Ex approval. RM is an option in segment 10, not a standalone model; it must appear in the full code of DVC6200H / F / P or the SIS variant. The 125 C remote rating and aluminium-only limit must not be relaxed. Common models: DVC6200H + RM (HART remote mount), DVC6200F + RM (FF), DVC6200P + RM (PROFIBUS PA), DVC6200-SIS + RM (SIS remote mount); hardware: DVC6205 body plus DVC6215 remote travel sensor. If your actuator runs hot, the mounting space is tight, or you are weighing whether a DVC6205 / DVC6215 split solution is necessary, please share the service conditions and mounting position. We can review the remote rating, housing material and order code together and help avoid a wrong RM entry. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |