Siemens Intelligent Positioners - Model Code Decoding & Selection
Release time:2026-11-22 09:38:23 | Views:

The Siemens SIPART PS2 is a smart electropneumatic valve positioner for linear and rotary, single-acting and double-acting pneumatic actuators. It supports 4 to 20 mA, HART, PROFIBUS PA and FOUNDATION Fieldbus with ingress protection IP66 / NEMA 4X. Its order code uses the 6DR5 prefix and splits into two independent tables for non-flameproof and flameproof housings whose options are not interchangeable. This article decodes the overall structure, housing codes, -Z options, function modules and accessories, plus selection red lines, based on the official Siemens selection manual.

I. Product Positioning and Two Selection Branches

ItemDescription
BrandSiemens (independent brand)
ProductSIPART PS2 smart electropneumatic valve positioner
Application rangeLinear travel 3 to 130 mm; rotation 30 to 160 degrees (6DR50. / 6DR51.), 30 to 100 degrees (6DR55. / 6DR56.)
Signal types4 to 20 mA, 4 to 20 mA with HART, PROFIBUS PA, FOUNDATION Fieldbus
Air supply1.4 to 7 bar; 3 to 7 bar for double-acting lock-up versions
Branch 1: non-flameproof housingHousing digits 0 / 2 / 3; non-hazardous, intrinsic safety Ex i, increased safety Ex e, dust Ex t
Branch 2: flameproof housingHousing digits 5 / 6; flameproof Ex d (Zone 1 / Class I Div 1)
Model replacement noteThe former 6DR52XX series is discontinued; current production uses the 6DR51XX series, confirmed with the manufacturer

The key red line: the two code tables have non-interchangeable options and the same letter can mean different things. For example, explosion-protection digit E means intrinsic safety Ex i in the non-flameproof table but flameproof Ex d plus dust Ex t in the flameproof table. The branch must be determined by the housing digit before digit-by-digit configuration.

Source: Siemens SIPART PS2 official selection-rules manual and technical data compilation. Current production status and codes are subject to the manufacturer's latest data / ordering tool.

Digital valve positioner appearance
Digital positioner appearance reference, not a Siemens unit and not the actual model; parameters subject to official samples

II. Overall Order-Code Structure

PositionFieldDescription
Prefix6DR5Fixed product prefix
Digit 1Signal type4 to 20 mA / HART / PA / FF (a "no mainboard" option exists for non-flameproof versions)
Digit 2ActuatorSingle acting / double acting
Digit 3HousingDetermines non-flameproof or flameproof table; the key branch digit
Fixed structure digit—Fixed 0, not selectable
Digit 4Explosion protectionOptions differ between the two tables; consult the correct branch
Digit 5ConnectionCable entry thread plus air-port thread combination
Three extension digitsExtension codesFilled only for specific options (L1A for internal NCS, R** for pressure gauge)

Before selecting, gather: actuator type and action, travel or rotation, air-chamber volume, control signal and protocol, hazardous-area classification and protection form, housing material and corrosion environment, cable and air threads, power / air-loss action, whether SIL2 is required, limit signals and position feedback, pressure-gauge material, advanced diagnostics and Bluetooth / low-temperature / natural-gas options, air medium and pressure, mounting bracket and certificate requirements.

Source: Siemens SIPART PS2 selection-rules manual (order-code structure and information checklist). Exact digits and options are subject to the official ordering manual / tool.

III. Housing Codes and Materials

Housing codeMaterial / windowWeight (approx.)Single / double actingRecommended application
6DR5..0Plastic top (polycarbonate) with window plus aluminium base0.9 kgSingle + doubleDefault choice: indoor, non-corrosive, cost-sensitive; polycarbonate top only for intrinsic safety Ex i
6DR5..3Aluminium top plus aluminium base AlSi12, window (2 J)1.6 kgSingle + doubleWhere Ex e / Ex t is needed or an all-aluminium top is required
6DR5..2Stainless steel 1.4581, no window3.9 kgSingle + doubleStrong corrosion, offshore platforms, chlorine service; standard stainless silencer
6DR5..5Flameproof aluminium AlSi125.2 kgSingle + doubleZone 1 / Class I Div 1 flameproof duties, normal corrosion
6DR5..6Flameproof 316L stainless 1.44098.4 kgSingle + doubleFlameproof plus strong corrosion; use 6DR4004-8R stainless mounting kit
6DR5..1Aluminium AlSi12 (older model)1.3 kgSingle acting onlyNot listed in the 2025 selection table; treat as a historical model

When the customer does not specify housing material, the sample's business practice defaults to code 0 (plastic top plus aluminium base); use 3 for Ex e / Ex t and 2 for strong corrosion / offshore / chlorine. Flameproof housings (5 / 6) reduce air volume by about 20%, which must be included in actuator sizing.

Source: Siemens SIPART PS2 selection-rules manual (quick guide by housing material). Weights and materials are subject to the official data sheet.

IV. -Z Option Codes

CodeOption (excerpt)Constraint
C20Functional safety SIL 2 per IEC 61508 / IEC 61511Only for 6DR5.1.* (single-acting positioner)
F50SITRANS AW050 Bluetooth adapter for communication and data transferApprovals for multiple regions
K10Control optimization for small actuatorsAir chamber volume below 200 cm3
K11 / K12Additional internal potentiometer / internal non-contacting sensor NCSSelecting AIM removes the internal potentiometer and requires restoration
K18 / K50316 stainless pneumatic module / natural gas as air supplyK50 uses FVMQ elastomers and conformal coating
M40Ambient temperature -40 to 80 CFor 6DR5.1* / 6DR5.2* / 6DR5.3*, no window
P01 / P02Pressure-sensor diagnostics: supply-pressure monitoring / P01 plus valve performance test, partial stroke test and leakage monitoringComplies with NAMUR NE107
C35 / S10 to S17EN 10204 type 2.1 certificate / marine approvals (DNV, LR, BV, ABS, KR, CCS, RINA)Per project certificate requirements
A20 / Y15 / Y16 / Y17 / Y25Stainless tag plate / measuring-point description, text and tag / preset bus addressY25 only for 6DR55.. and 6DR56..

Some combinations are mutually exclusive: mechanical limit switches MLS are not for natural-gas service (conflicts with -Z K50); the VDI/VDE 3847 interface -Z K20 is not for flameproof housings; low temperature -40 C (-Z M40) cannot be combined with double-acting lock-up (this exclusion was confirmed by a Siemens office but is not listed directly in the sample and must be finally confirmed with Siemens).

Source: Siemens SIPART PS2 selection-rules manual (-Z option table and constraints table). Exclusions and codes are subject to the official manual / manufacturer confirmation.

V. Function Modules and Accessories

Order numberModuleDescription
6DR4004-8A / -6ADigital I/O module DIO1 input and 3 outputs; non-hazardous / hazardous
6DR4004-8J / -6JAnalog output module AOM4 to 20 mA position feedback; non-hazardous / hazardous
6DR4004-8F / -6FAnalog input module AIMNon-hazardous / hazardous
6DR4004-8G / -6GInductive limit switch ILS2 proximity switches plus 1 digital output
6DR4004-8K / -6KMechanical limit switch MLS2 mechanical switches plus 1 digital output; not for natural gas
6DR4004-5L / -5LEInternal NCS moduleMounted inside the positioner; non-hazardous / hazardous
6DR4004-1ES to -4ESPosition transmittersPotentiometer / NCS / NCS+ILS / NCS+MLS
6DR4004-2BT / 7MF4997-1DCBluetooth communication kit / USB HART modemCommissioning and communication
6DR4004-1LP to -4LPSurge protection 6 kVTwo-wire / three-wire / four-wire / PA-FF bus

The separate NCS sensor uses order number 6DR4004-·N·· with cable lengths N=6 m, P=20 m, R=40 m and actuator types 2 for linear travel up to 14 mm, 3 for linear 14 to 130 mm and 4 for rotary; it is not for flameproof applications. The three extension digits are shared fields, so L1A for internal NCS and R** for a pressure gauge cannot appear together.

Source: Siemens SIPART PS2 selection-rules manual (common accessories and order-number tables). Order numbers are subject to the official ordering manual.

VI. Selection Guide and Common Configurations

Selection guide: The sequence is "branch by housing digit (0/2/3 non-flameproof table or 5/6 flameproof table), define signal type, define single / double acting, define housing material, define explosion-protection code, define cable and air threads, select -Z options, then verify accessories and extension digits". Red lines: 1. the two code tables must not be mixed because the same letter has different meanings; 2. Ex ia intrinsic safety is not Ex d flameproof enclosure and must be looked up in the correct branch; 3. SIL2 applies only to single-acting 6DR5.1.*; 4. flameproof housings have about 20% less air volume and require actuator rechecking; 5. exclusions are subject to the official manual / final manufacturer confirmation, and order codes are never invented.

Common configurations: Indoor non-hazardous service commonly uses 6DR5..0 (plastic top plus aluminium base); strong corrosion or offshore uses 6DR5..2 stainless; Zone 1 flameproof uses 6DR5..5 or 6DR5..6. Wide-range diagnostics use P01 / P02, SIL2 uses -Z C20 and Bluetooth commissioning uses -Z F50. Signal versions follow the DCS protocol: 4 to 20 mA HART, PA or FF.

If you have a 6DR5 order code but are unsure which code table it belongs to, or want to confirm a positioner's housing, explosion protection and diagnostic options, feel free to send us the complete code and site environment. We can check it digit by digit against the official manual and flag any items needing manufacturer confirmation.