The ABB TZIDC is an electronically configurable smart valve positioner with communication, based on the V18345 platform and designed for pneumatic linear and rotary actuators. Its order code consists of the base model plus eight order-code segments, with an optional suffix segment. This article decodes the code segment by segment against the official sample, lists core technical data and clarifies the boundary between standard and project-specific models. Codes are subject to ABB sample DS_TZIDC_ZH_I (REV. I).

I. Product Positioning and Selection Boundary

ItemDescription
BrandABB (independent brand)
ProductABB TZIDC smart electropneumatic valve positioner
Base modelV18345
Applicable actuatorsPneumatic linear (DIN/IEC 534, NAMUR) and rotary (VDI/VDE 3845); also integral mounting on control valves
Core functionsAuto-tuning and direct initialization, adaptive positioning, non-contact sensor, fail-safe / fail-lock, modular upgrades
Selection boundaryThese rules cover standard ABB models only; a code that cannot be fully decoded indicates a project-specific model outside standard quotation scope and must be confirmed with ABB
SourceABB official sample DS_TZIDC_ZH_I (REV. I, 48 pages)

First verify that the code can be fully decoded by the standard rules, then configure segment by segment. If a segment cannot be explained by these rules, do not invent a meaning: treat it as a project-specific model and confirm with ABB.

Source: ABB official sample DS_TZIDC_ZH_I REV. I (pages 2-3, 11-14, 41-45). Parameters are subject to the official manual.

Digital valve positioner appearance
Digital positioner appearance reference, not an ABB unit and not the actual model; parameters subject to official samples

II. Core Performance and Technical Data

CategoryData (excerpt)
Input signal4 to 20 mA, two-wire, configurable split range; above 20 mA indicates alarm level on error
Power supply24 V DC (11 to 30 V DC allowed, two-wire technology)
CommunicationHART 5.9 standard (HART 7.4 optional) plus local communication interface LCI in the non-hazardous area
Characteristic curveLinear, ratio 1:25 / 1:50 / 25:1 / 50:1, freely configurable via 20 reference points; deviation at or below 0.5%
Resolution / samplingA/D conversion above 16000 steps; sampling frequency 20 ms
Travel / rotationLinear actuator operation min 25 degrees, max 45 degrees; rotary min 25 degrees, max below 270 degrees (350 degrees with S1 sensor)
Air supply / output1.4 to 6 bar standard (marine 1.6 to 5.5 bar); output 0 to 6 bar
Air consumptionBelow 0.03 kg/h independent of supply pressure; maximum air above 5 kg/h at 1.4 bar and above 13 kg/h at 6 bar
Air qualityDIN/ISO 8573-1 class 3: particle size at or below 5 micrometres, particle density at or below 5 mg/m3, oil at or below 1 mg/m3; dew point 10 K below operating temperature
Environment / protection-40 to 85 C (remote sensor -40 to 100 C); IP66 / NEMA 4X (remote sensor IP67)
Functional safetyMeets IEC 61508; SIL 2 optional for single-acting with fail-safe pneumatic device

Expected service life is about 10 years with proper use and regular maintenance / spare-part replacement. Selection must check instrument air quality, ambient temperature and hazardous-area approval together, not communication protocol alone.

Source: ABB official sample DS_TZIDC_ZH_I REV. I (technical data tables, pages 11-14). Subject to the official manual.

III. Code Structure Overview and Example

StructureDescription
V18345Base model (ABB TZIDC smart positioner platform)
Segment 1: basic model (2 digits)Housing style and mounting, including mechanical position indicator
Segment 2: input / communication (1 digit)LCI only, or LCI + HART FSK
Segment 3: explosion protection (1 digit)ATEX / IECEx / cFMus / NEPSI and other approval codes
Segment 4: output / safe position (1 digit)Single / double acting combined with fail-safe / fail-lock
Segment 5: connection (1 digit)Cable thread plus air-port thread combination
Segment 6: feedback module (1 digit)Analog / digital / analog + digital position feedback
Segment 7: mechanical kit (2 digits)Proximity switch or microswitch kit for digital position feedback
Segment 8: design (1 digit)Standard / high rigidity and low air / IP66 / enhanced corrosion protection

In the manual example V18345-10b2c2de0f, the placeholder letters b/c/d/e/f stand for the digits to be filled in segments 2 to 8: 10 is the basic model, b is 1 or 2, 2 is cFMus approval, c is 1/2/4/5, 2 is the connection, d is 0/1/3/5, e0 is 00/10/50 and f is 1/H/P/S. There are no separators between segments, so digit positions must not shift.

Source: ABB official sample DS_TZIDC_ZH_I REV. I (ordering information and code example, pages 41-45). Subject to the official manual.

IV. Segments 1 to 4 Decoded

SegmentCodeMeaning
1: basic model10 / 20 / 30 / 40 / 7010: painted aluminium housing, NAMUR linear or VDI/VDE 3845 rotary mounting, no mechanical indicator; 20: like 10 with mechanical indicator; 30: integral mounting on a control valve; 40: integral with mechanical indicator; 70: remote-sensor control unit
2: input / communication1 / 21: 4 to 20 mA two-wire with LCI adapter connector; 2: 4 to 20 mA two-wire with LCI connector plus HART FSK module
3: explosion protection0 / 1 / 2 / 5 / 7 / B / H / J / K / U / V / P / R0 none; 1 ATEX Ex ib IIC T6/T4 Gb; 2 cFMus; 5 IECEx Ex ib; 7 ATEX Ex ia IIC T6/T4 Gb; B UKEX Ex ib; H/J EAC; K IECEx ia; U NEPSI Ex ia; V NEPSI Ex ib; P INMETRO Ex ib; R KOSHA Ex ib
4: output / safe position1 / 2 / 4 / 51 single-acting fail-safe; 2 single-acting fail-lock; 4 double-acting fail-safe (not for integral mounting); 5 double-acting fail-lock (not for integral mounting)

Within the explosion-protection segment, Ex ia and Ex ib are different approval levels: codes 7 / K / U are Ex ia while 1 / 5 / B / V / P and others are Ex ib, and they must not be interchanged. Intrinsic safety (Ex i) and flameproof enclosure (Ex d) are different protection forms; this TZIDC family mainly uses intrinsic-safety and non-incendive type approvals, with the exact approval combination subject to the code and certificate.

Source: ABB official sample DS_TZIDC_ZH_I REV. I (order code table, segments 1 to 4). Explosion-protection forms are strictly distinguished and subject to official certificates.

V. Segments 5 to 8 and Suffixes

Segment / categoryCodeMeaning
5: connection2 / 5 / 6 / 72: cable 1/2-14 NPT plus air 1/4-18 NPT; 5: M20 x 1.5 plus 1/18 NPT; 6: M20 x 1.5 plus G1/4; 7: G1/2 plus Rc1/2
6: feedback module0 / 1 / 3 / 50 none; 1 analog position feedback plug-in (4 to 20 mA two-wire); 3 digital position feedback plug-in; 5 analog plus digital feedback
7: mechanical kit00 / 10 / 5000 none; 10 proximity switch SJ2-SN (NC, only with mechanical indicator model, no IECEx approval); 50 24 V AC/DC microswitch (not for explosion-protected versions)
8: design1 / H / P / S1 standard; H high rigidity plus low air consumption (double-acting only); P IP66 / NEMA 4X; S enhanced corrosion protection
SuffixesM1/M2/M5/MB, CS2, CF2/CF3, CM1, CCC/UKCA, CBA, GHA-GHS, MK1/MK3, S1/RS/RD, RT/RV/RP/R5/R6Document language, SIL2 declaration, certificates of compliance, marine approval, CCC/UKCA, inspection certificate, certificate delivery method, device labels, position sensor type and remote-sensor options

Suffixes can be appended after the main code. Common ones include the SIL2 declaration CS2 (only for single-acting pneumatic devices with fail-safe function), CCC (3CC for Ex i and CCC for Ex d), marine approval CM1 (DNV GL) and remote-sensor options RT (-40 to 100 C), RV (2g at 300 Hz), RP (IP67) and R5 / R6 (5 m / 10 m cable).

Source: ABB official sample DS_TZIDC_ZH_I REV. I (ordering information and additional-ordering-information tables, pages 41-45). Subject to the official manual.

VI. Selection Guide and Common Models

Selection guide: The sequence is "confirm the code is decodable as a standard model, define basic model and mounting, define communication (LCI or LCI + HART), define approval, define single / double acting and fail position, define connection threads, define feedback module and mechanical kit, define design code, then append suffixes". Red lines: 1. codes that cannot be fully decoded are project-specific models and must be confirmed with ABB rather than invented; 2. Ex ia and Ex ib are strictly distinguished and intrinsic safety must not be confused with flameproof enclosure; 3. segment 7 mechanical kits have mutual exclusions with certain approvals and mechanical-indicator models; 4. double-acting fail-safe / fail-lock (codes 4 / 5) are not available for integral mounting; 5. codes are subject to ABB sample DS_TZIDC_ZH_I REV. I and the nameplate.

Common models: The V18345 platform's segment 1 gives 10 / 20 (NAMUR linear or VDI/VDE 3845 rotary mounting), 30 / 40 (integral mounting) and 70 (remote-sensor control unit). The communication segment commonly uses 2 (LCI + HART); the approval segment follows the site certification; the output / safe-position segment follows actuator action and fail action. The example V18345-10b2c2de0f only illustrates digit positions and must not be used as an order code.

If you have a V18345 nameplate code but are unsure what each segment means, or want to confirm whether a positioner has HART, a feedback module and which explosion-protection approval, feel free to send us the complete code. We can decode it segment by segment against the official sample and avoid mistaking a project-specific model for a standard one.