A control valve's flow characteristic describes the relationship between stem travel and relative flow, and it is a core selection item governing whether loop gain stays flat and control remains stable. The three common inherent characteristics are linear, equal percentage and quick opening; once installed, piping pressure-drop variation produces the installed characteristic. This article covers the definitions, schematic curves, valve-authority effects, positioner implementation and service-based selection of the three types, with classifications based on recognized standards and official manufacturer samples. I. Subject Positioning and Standards Background
One distinction must be clear: the curves in manufacturer samples are inherent characteristics, measured in the laboratory at constant differential pressure. In service, valve differential pressure changes with flow, so what the loop actually sees is the installed characteristic. Selection must treat the two separately, or the typical problem of "good sample curve but unstable field behavior" appears. Classifications and formulas reference public technical material (data obtained via web search, source: https://www.supremevalves.in/docs/technical-resources/control-valve-rangeability-chart.html; https://bluestreamfl.com/academy/control-valves). Actual curves are subject to official samples / standard originals.
II. Three Inherent Flow Characteristics
The relative Cv figures are teaching illustrations only and must not be used for sizing. Always consult the official inherent characteristic curve of the specific trim and verify rangeability (maximum controllable flow / minimum controllable flow). Equal percentage dominates because most process gain falls as load rises while an equal-percentage valve's gain rises with opening; the product tends toward constant. Definitions and indications reference public technical material (data obtained via web search, source: https://instrumentationforum.com/t/flow-characteristics-of-control-valve/5568; https://www.merobix.com/blog/what-is-a-valve-flow-characteristic). Actual curves are subject to official samples / standard originals. III. Inherent vs Installed Characteristic (Valve Authority)
Selection therefore cannot stop at the label "linear / equal percentage". The installed condition must be calculated or checked with sizing software. If most system pressure drop is consumed by the pump, heat exchanger and piping, the valve itself has little drop and even an equal-percentage trim may behave differently in the field. Authority and installed-characteristic formula reference public technical material (data obtained via web search, source: https://bluestreamfl.com/academy/control-valves; https://flowengin.com/blog/control-valve-flow-characteristics-linear-equal-percentage). Subject to official samples / standard originals. IV. Flow Characteristic Settings in Positioners
Modern smart positioners generally move the characteristic curve into software, allowing one positioner to switch between linear, equal percentage, quick opening or a custom curve. This is convenient but adds a red line: the electronic characteristic set in the positioner must be distinguished from the inherent mechanical characteristic of the trim; what matters is their combined result. Commissioning should follow the official manual and field loop testing. Source: Flowserve Logix positioner manual FCD LGENIM3404-10, SAMSON data sheet T 8387, Azbil AVP series samples, ABB TZIDC sample DS_TZIDC_ZH_I REV. I. Parameters are subject to official manuals. V. Selecting the Characteristic by Service
"Equal percentage as default, linear for constant drop, quick opening for on/off" is a general starting point, not a rigid rule. Final judgment should combine the process gain curve, valve authority, actuator deadband and positioner resolution. When in doubt, write "subject to official sizing software / sample verification" and do not invent rangeability figures. Selection principles reference public technical material (data obtained via web search, source: https://www.supremevalves.in/docs/technical-resources/control-valve-rangeability-chart.html; https://www.merobix.com/blog/what-is-a-valve-flow-characteristic). Subject to official samples / standard originals. VI. Selection Guide and Common ConfigurationsSelection guide: The sequence is "define the inherent characteristic, verify the installed characteristic, then align trim and positioner settings". First choose the default among equal percentage / linear / quick opening based on how process gain changes. Second check gain flatness at low and high load using authority and the installed-characteristic formula. Third confirm the trim's mechanical characteristic matches the positioner's electronic setting and use official sizing software for Cv, opening and rangeability. Red lines: 1. inherent is not installed characteristic; 2. quick opening is not for continuous modulation; 3. a positioner custom curve cannot replace trim selection; 4. figures and curves are subject to official samples / standard originals. Common configurations: General process control typically uses an equal-percentage trim with a smart positioner (HART / FF / PA options). Level and constant-drop blending often use linear trim. Venting and interlock shutdown use quick-opening characteristics or on/off valves. Characteristic implementation and point counts differ among positioner brands, so curves must be rechecked when changing brands. If a loop keeps oscillating at one load band after repeated tuning, the flow characteristic and installed condition may need another look. Feel free to share the medium, pressure-drop range and current valve type; we can check the characteristic and size together against official samples. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |