A solenoid valve is the directional switching element of a pneumatic circuit: a 3/2 valve is common for single-acting actuators or simple air on/off duty, while a 5/2 valve alternately fills and vents the two chambers of a double-acting actuator. Based on catalogues from ASCO (Emerson), Camozzi, Bifold and Valmet, this article explains positions and ways, single and dual solenoid, fail position and the selection basis.

I. Product Positioning

ItemDescription
Product nameSolenoid valve / solenoid directional valve, classified as 3/2, 5/2, 5/3, etc. by position and way count
3/2 typical dutySingle-acting (spring return) actuator supply/exhaust, air on/off, pilot control; the ASCO 8327 series is used in instrument air safety circuits
5/2 typical dutyAlternate fill and exhaust of the two chambers of a double-acting cylinder or actuator; Camozzi series 4, Valmet VAQ series
Brand ownershipASCO belongs to Emerson; Bifold belongs to Rotork; Valmet (former Metso flow automation) is an independent brand; Camozzi is independent
SourceASCO Series 327 catalogue (80020GB-2018/R01), ASCO solenoid selection rules; Camozzi Series 4 catalogue; Valmet S150 technical bulletins; Bifold FP series catalogue

"Positions and ways" is the first branch in selection: positions are the number of stable spool states, ways are the number of external ports. If the position or way count is wrong, no pressure rating or Cv can make the circuit work.

Source: ASCO Series 327 official catalogue (80020GB-2018/R01); Camozzi Series 4 official catalogue; Valmet technical bulletins S150-1/S150-5; Bifold FP series direct-acting solenoid catalogue (2017). Brand ownership: ASCO belongs to Emerson.

ASCO 8327 solenoid valve
ASCO 8327 solenoid valve product photo, for selection reference only

II. Working Principle of 3/2 and 5/2

TypePortsDe-energized stateTypical action
3/2 normally closed (NC)1 supply, 2 outlet, 3 exhaustSupply closed, outlet connected to exhaustEnergized gives P to A; de-energized vents A to R and the single-acting actuator resets
3/2 normally open (NO)As aboveP connected to A, R closedEnergized cuts supply and vents
5/2 single solenoid1 supply, 2/4 working ports, 3/5 exhaustSpring returns to initial positionDe-energized spring reset gives a defined fail position
5/2 dual solenoidAs aboveHolds the last position (bistable)Two coils alternately switch; de-energized holds position, and an air lock valve is needed for true lock-up

Fail position is the red line in 3/2 and 5/2 selection: a single-solenoid valve springs back to a defined initial position on power loss, while a dual-solenoid valve holds the last spool position; if the process requires fail-lock, an air lock valve or air tank must be added. The ASCO 8327 is a stainless direct-acting balanced poppet valve with a 316L body that operates at zero differential pressure; the WSNF-prefix version is Ex d flameproof, a different protection form from the intrinsically safe version.

Principles are general pneumatic descriptions; port functions and Ex forms are subject to the ASCO Series 327 catalogue (80020GB-2018/R01) and each manufacturer's data sheet. Ex ia intrinsic safety is NOT Ex d flameproof enclosure.

III. Key Technical Data

SeriesWays / operationPortFlow and pressureConstruction / Ex
ASCO 8327 (WSNFTIS8327B312)3/2 direct-acting, single solenoid316L stainless integral bodyOperates at zero differential; 24 V DCIntrinsically safe version requires a safety barrier; WSNF prefix is Ex d flameproof
ASCO 325 (SCXG325B006)3/2 direct-actingBrassPer catalogue; 3/2 NC or universalNon-hazardous, port function per original data sheet
ASCO 531 (SCG531C001MS)3/2 NAMUR, pilot spoolG (ISO G) threadPer 531 catalogue; with MS manual overrideEpoxy-moulded coil, non-hazardous IP65
Camozzi series 4 (452C-011-22)5/2 dual solenoid, bistable, spoolG1/2 in2500 Nl/min; 2-10 barDC24 V; filtered oil-free air
Valmet S150 (DAQ 3/2, VAQ 5/2)3/2 or 5/2, single/dual coil1/4, 3/8, 1/2 in G or NPTOrifice 3/6.7/10 mm; -20 to +80 CAluminum or SS316; IP versions DAQ/VAQ/VSQ/DSQ; Ex d / Ex ia optional

Compare parameters only within the same series and configuration: ASCO 8327 (316L, intrinsically safe) differs from 325 (brass, non-hazardous), and the flow test conditions of the Camozzi 5/2 and Valmet 5/2 also differ. Order code structures are completely different between brands and must not be copied across.

Source: ASCO Series 327 catalogue (80020GB-2018/R01), Camozzi Series 4 catalogue, Valmet bulletins S150-1/S150-5, Bifold FP series catalogue (2017). Unlisted values are subject to original data sheets and nameplates.

IV. Sizing Calculation and Key Points

ItemFormula / basisNote
Positions and functionSingle-acting to 3/2; double-acting to 5/2; center function to 5/3Define positions and ways first
Flow and CvCalculate Q from actuator volume and stroke time, then check the Cv-flow curveInsufficient valve Cv becomes the speed bottleneck
Pressure rangeP_min to P_max must cover actual supply pressureDirect-acting works at zero differential; pilot-operated has a minimum
Voltage and powerDC24 V, AC220 V, etc. per site supplyCoil power relates to the Ex form and must be checked together
Ex protectionEx ia needs a safety barrier; Ex d is a separate constructionNever interchange; if unavailable write "confirm by inquiry"
Fail positionSingle solenoid spring return / dual solenoid holdHold requires an air lock valve or air tank

Selection sequence: (1) choose 3/2 or 5/2 by actuator action; (2) choose NC/NO and single/dual solenoid and define the fail position; (3) set Cv and port by flow and pressure; (4) set coil voltage by site supply; (5) set Ex ia or Ex d and certificate by area classification; (6) set NAMUR or threaded mounting and manual override. Do not use PTFE tape on pneumatic threads.

The procedure is a general engineering basis; Cv, pressure, approvals and order codes are subject to each brand's official catalogues and nameplates. No values are invented.

V. Selection Guide and Common Models

Selection guide: Follow "define positions/ways and fail position, set flow and pressure, set voltage and Ex protection, set ports and manual override, verify order code". Core red lines: (1) 3/2 for single-acting or on/off, 5/2 for double-acting, not interchangeable; (2) a dual-solenoid valve does not truly lock up on power loss and needs an air lock valve; (3) Ex ia intrinsic safety is NOT Ex d flameproof enclosure, and the ASCO 8327 intrinsically safe version differs from the WSNF flameproof version, so write "confirm by inquiry" when unsure; (4) brand ownership: ASCO belongs to Emerson, Bifold to Rotork; (5) compare parameters only within the same series and configuration.

Common models: ASCO WSNFTIS8327B312 (316L intrinsically safe 3/2), WSNF8327B102/112 (Ex d flameproof), SCXG325B006 (brass 3/2), SCG531C001MS (3/2 NAMUR with override); Camozzi 452C-011-22 (5/2 dual solenoid, G1/2 in); Valmet DAQ-2-13-G-0-0-xx (3/2), VAQ-2-13-G-0-0-xx (5/2); Bifold FP06P (3/2 direct-acting NAMUR). Full order codes are subject to official catalogues.

If you are selecting a solenoid valve for an actuator, or want to decide between 3/2 and 5/2, single and dual solenoid, or intrinsic safety and flameproof enclosure, please feel free to contact us. We can check the model and order code together against the actuator action, fail position and area certification.