Commissioning of SAMSON positioners (Mounting and Start-up) follows the sequence of mechanics and pneumatics first, electrics second, parameters and initialization last. The 3730 / 3731 series are operated locally via a single rotary pushbutton and LCD; the INIT key starts autotune, and configuration can also be done with TROVIS-VIEW and a HART communicator. This article covers pre-commissioning checks, mounting and wiring, parameter setting, initialization and common error codes.
I. Scope and Tools
| Item | Description |
| Applicable series | SAMSON 3730-0/1/2/3/4/5/6 and 3731-3/3731-5 (the 3730-6 additionally includes pressure monitoring) |
| Local operation | Single rotary pushbutton (turn to select, push to confirm); LCD reading direction rotatable by 180 degrees |
| Autotune | INIT key starts initialization; closed-loop operation begins immediately afterwards |
| Software tool | TROVIS-VIEW via SSP interface (RS-232 / USB) |
| Communication tool | HART communicator / FSK modem (HART models only) |
| Reference documents | SAMSON model-specific mounting and start-up manuals, NA 0122, T 8384-x / T 8387-x |
Before commissioning, confirm that the model, data sheet and certificates are available and check the site area classification and intrinsic safety / flameproof requirements.
Source: SAMSON official data sheets NA 0122, T 8384-3/6 EN, T 8387-3 EN and the corresponding mounting and start-up manuals.

SAMSON 3730 series positioner, same-series illustration; for illustration only, not the actual model; parameters subject to the official data sheet
II. Pre-Commissioning Checks
| Check item | Requirement |
| Nameplate | Verify model, spring range and fail-safe action FA (stem extends / air-to-open) or FE (stem retracts / air-to-close) |
| Air quality | ISO 8573-1: particles class 4 / oil class 3 / humidity class 3; flush pipework, oil-free and dust-free |
| Supply pressure | 1.4-7.0 bar (3731-323: 1.4-6 bar); air-to-open supply approximately spring range upper limit plus 0.2 bar, minimum 1.4 bar |
| Mounting interface | Bracket and shaft match integrated Type 3277 / NAMUR IEC 60534-6-1 / VDI/VDE 3845 and 3847 |
| Feedback rod | Connecting pin in the correct hole for travel / angle (commonly 25 / 35 / 50 / 90 degrees) |
| Electrical conditions | Current source only; static destruction limit plus/minus 33 V; minimum current approx. 3.6-3.8 mA |
| Ex integrity | Housing, seals, glands, blanking plugs and grounding intact; certificate matches area classification |
Low air supply, loose mounting or a reversed feedback rod are common causes of initialization failure; eliminate them before starting INIT.
Source: SAMSON official mounting and start-up manuals (connections / air supply / electrical connections), data sheets T 8384-3 EN and T 8387-3 EN.
III. Mechanical and Pneumatic Mounting Steps
| Step | Action |
| 1 | Remove protective caps from pneumatic connections; verify connecting plate / gauge block ports (1/4 NPT or G 1/4) |
| 2 | Mount the positioner on the valve / actuator and connect signal pressure per FA, FE and NAMUR or VDI/VDE 3845 |
| 3 | Connect supply air; keep tubing short to avoid signal delay; fit SUPPLY / OUTPUT pressure gauges where practical |
| 4 | Set the Air-to-open / Air-to-close slide switch so that valve closed corresponds to the 0% reading |
| 5 | Rough-set supply pressure from the nameplate spring range and verify full stroke movement without sticking |
| 6 | Only then connect the electrical signal (next section) and proceed to start-up settings |
Double-acting actuators require the Type 3710 reversing amplifier; rotary actuators follow the actuator manufacturer's pneumatic specifications.
Source: SAMSON official mounting and start-up manuals (pneumatic connections and start-up sequence); data sheet T 8387-3 EN.
IV. Electrical Connections and Ex Requirements
| Item | Requirement |
| Signal source | Current source only (4-20 mA); never connect a voltage source directly; set point wires to terminals 11 and 12 |
| Cable / terminals | M20x1.5 gland clamps 6-12 mm; terminals 0.2-1.5 mm² (3731: 0.2-2.5 mm², at least 0.5 Nm) |
| IS loop | Per EN 60079-14 clause 12; clause 12.2.2.7 for multiple IS circuits in multicore cable; insulation radial thickness at least 0.2 mm and single-wire diameter at least 0.1 mm |
| Parameter matching | When interconnecting, do not exceed certificate values Ui/Ii/Pi/Ci/Li (versus barrier Uo/Io/Po/Co/Lo) |
| Ex nA / Ex tc | Zone 2 equipment: connect or disconnect under power generally only during installation, maintenance or repair; associated fuses outside the hazardous area |
| Ex d (3731) | Certified entries / conduit; certified plugs for unused entries; equipotential bonding; never open while energized |
| Signal faults | Above 22 mA shows OVERLOAD; below 3.7 mA moves to SAFE and shows LOW |
Ex ia intrinsic safety is not Ex d flameproof enclosure: wiring and cover-opening rules differ. Follow the nameplate and certificate on site; where unavailable, write "please consult for confirmation".
Source: SAMSON official mounting and start-up manuals (electrical connections), data sheets T 8384-3/6 EN and T 8387-3 EN; EN 60079-14 and EN 60079-1.
V. Parameterization, Initialization and Error Codes
| Code / step | Meaning and action |
| P2 | ATO / ATC: air-to-open (fail-close) or air-to-close (fail-open); must match the slide switch |
| P3 | Feedback rod pin position: 25 / 35 / 50 / 90 degrees |
| P4 | Rated travel range; P5 characteristic (linear / equal percentage / reverse equal percentage) |
| P6 / P7 | Input signal (4-20 mA, split range possible); w/x action direction (direct / reverse) |
| P8 | Gain Kp (set during initialization; reduce and re-initialize if oscillating) |
| P9 | Output pressure limit (approx. 2.4 bar to protect the actuator) |
| P15 | Start initialization (INIT); press * during the process to interrupt and return to fail-safe |
| P16 | Zero-point calibration (execute when E0 appears) |
| P18 / P19 | Reset to defaults / confirm configuration (auto-cancels after 3 minutes without key action) |
| Error code | Common cause and action |
| E0 | Zero drift above approx. 5%: check mounting and seat, run P16 zero calibration |
| E1 / E2 | Parameter changed after initialization / not initialized: restore parameter or run P15 |
| E3 | Oscillation from excessive Kp: check output air volume, reduce P8 and re-initialize |
| E4 / E5 | Actuation time too short / no detection: check air supply, mounting and volume settings |
| E6 / E7 | Travel not reached / actuator not moving: check supply, leakage and signal below 3.7 mA |
| E8 | Position signal out of limits: check pin position, feedback rod and NAMUR connection orientation |
| E9 / E10-E15 | Internal software / hardware fault: return to SAMSON for repair |
Source: SAMSON positioner mounting and start-up manual code tables (P0-P20, E0-E15); data sheets T 8384-3/6 EN and T 8387-3 EN.
VI. Selection Guide and Common Models
Selection guide: The commissioning path is mechanics and pneumatics, then electrics, then parameters, then INIT, then verification and records. First verify FA/FE and spring range from the nameplate, ensure air quality and supply, then connect the current source and check Ex wiring. Parameters P2 (ATO/ATC), P3 (pin position), P4 (travel) and P5 (characteristic) must match the site, followed by P15 initialization. On failure, troubleshoot via E0-E15 rather than repeating INIT blindly.
Common models: Applies to the 3730-0/1/2/3/4/5/6 and 3731-3/3731-5; the 3730-6 TS safety version additionally follows the SIL certificate (968/V 1161) and the 3.8 / 4.4 mA emergency shutdown thresholds.
If you encounter E0-E8 initialization errors during site commissioning, or are unsure whether ATO/ATC and intrinsic safety wiring comply with the certificate, please feel free to contact us. We can review the steps and fault causes against the nameplate, air supply conditions and area certification.