| SAMSON 3731-3 / 3731-5 Flameproof Positioners - Technical Data | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-22 09:38:23 | Views: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The SAMSON 3731 series is the flameproof (Ex d) version of corresponding 3730 models. It shares the same analog PD plus microprocessor hybrid platform but uses cast-aluminum or stainless-steel flameproof enclosures for local single-knob operation in hazardous areas. The 3731-3 is the HART model and the 3731-5 the FOUNDATION Fieldbus model; their order codes follow the T 8387 series and must not reuse the 3730 digit table. I. Product Positioning
Important: the 3731 order code is independent of the 3730 (T 8384), with different digit count, positions and option sets. GOST documents mention regional type numbers such as 3731-521 / 3731-524, hinting at possible regional variants such as a 3731-4 (PROFIBUS PA); final selection is subject to the official ordering tool or latest data sheet. Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN and NA 0122.
II. Core Technical Data (T 8387)
Source: SAMSON official data sheet T 8387-3 EN (general technical data 5.3); the 3731-5 shares the platform, with differences in communication and electrical data. III. 3731-3 versus 3731-5
Both are flameproof Ex d; differences lie mainly in communication protocol and electrical data. Define the protocol first, then build the order code using the Ex and option positions of T 8387-x. Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN and NA 0122. IV. Flameproof Construction and Wiring Points
Red line: Ex ia intrinsic safety is NOT Ex d flameproof enclosure. The flameproof housing of the 3731 is not equivalent to the intrinsically safe housing of the 3730; even when a 3731 carries an Ex ia option, the enclosure and wiring follow the marked type of protection separately. Source: SAMSON official data sheet T 8387-3 EN electrical connections section; EN 60079-1, EN 60079-11 and EN 60079-14. V. Order Code and Selection Boundaries
Selection path: define the protocol first (3731-3 HART or 3731-5 FF), confirm the Ex d certificate against gas group and temperature class, determine the mounting kit from travel / angle and actuator, add limit switches, solenoids or position transmitters as needed, then generate the 15-digit code with the official tool. Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN, T 8384-3 EN and T 8384-6 EN. VI. Selection Guide and Common ModelsSelection guide: Select the 3731 series when the hazardous area explicitly requires a flameproof enclosure (Ex d / Ex db): the 3731-3 for HART and the 3731-5 for FF. Only when supply / output pressure monitoring is also required should the Ex d[ja] option of the 3730-6 be considered, and its 14-digit code must not be mixed with the 15-digit 3731 code. Ex ia intrinsic safety is not Ex d flameproof enclosure; gas group and temperature class must be checked item by item. Common models: 3731-3 (HART flameproof) and 3731-5 (FF flameproof); related models include the 3730-3 / 3730-4 / 3730-5 intrinsically safe platform, the 3730-6 (pressure monitoring, 14 digits) and the 3730-6 TS (SIS safety version). If you are selecting a flameproof positioner for a Zone 1 hazardous area, or want to confirm the boundary between the 3731-3 / 3731-5 and the 3730-6 Ex d[ja], please feel free to contact us. We can check the model and order code against gas group, temperature class, communication protocol and mounting interface. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |

简体中文
ENGLISH