SAMSON 3731-3 / 3731-5 Flameproof Positioners - Technical Data
Release time:2026-11-22 09:38:23 | Views:

The SAMSON 3731 series is the flameproof (Ex d) version of corresponding 3730 models. It shares the same analog PD plus microprocessor hybrid platform but uses cast-aluminum or stainless-steel flameproof enclosures for local single-knob operation in hazardous areas. The 3731-3 is the HART model and the 3731-5 the FOUNDATION Fieldbus model; their order codes follow the T 8387 series and must not reuse the 3730 digit table.

I. Product Positioning

ItemDescription
BrandSAMSON
Series3731 flameproof intelligent electro-pneumatic positioners
Models3731-3 (HART, 4-20 mA two-wire, LCD and autotune); 3731-5 (FF bus-powered, LCD and autotune)
Explosion protectionEx d / Ex db flameproof enclosure (cast aluminum or stainless steel), may include Ex ia options
PlatformSame as the 3730: analog PD control plus microprocessor
Order code / data sheetSeparate 15-digit structure; T 8387-3 EN / T 8387-5 EN

Important: the 3731 order code is independent of the 3730 (T 8384), with different digit count, positions and option sets. GOST documents mention regional type numbers such as 3731-521 / 3731-524, hinting at possible regional variants such as a 3731-4 (PROFIBUS PA); final selection is subject to the official ordering tool or latest data sheet.

Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN and NA 0122.

SAMSON 3730 series positioner illustration
SAMSON 3730 series illustration, not the actual model; 3731 flameproof details subject to the official data sheet; parameters subject to the official data sheet

II. Core Technical Data (T 8387)

ParameterTechnical data
Rated travel (direct on Type 3277)3.6-30 mm
Rated travel (IEC 60534-6-1 bracket)3.6-300 mm
Rated rotation24-100 degrees
Set point signal (3731-3)4-20 mA two-wire, reverse-polarity protected; minimum current 3.6 mA for display; load at 20 mA less than or equal to 450 ohm
Supply pressure3731-321 / 327: 1.4-7 bar; 3731-323: 1.4-6 bar
Air qualityISO 8573-1: particles class 4 / oil class 3 / humidity class 3
Flow characteristicsLinear / equal percentage / reverse equal percentage (deviation at most 1%)
Hysteresis / sensitivityat most 0.3% / 0.1%
Steady air consumptionapprox. 110 L/h (about 0.06 scfm)
Ambient temperature-40 to +80 C (certificate limits additional); storage -60 to +80 C
Ingress / electrical interfaceIP66 / NEMA 4X; 2 x 1/2 NPT or 2 x M20x1.5; terminals 2.5 mm²
Housing / weightDie-cast aluminum EN AC-43400 or stainless steel; approx. 2.5 kg
Functional safetyIEC 61508: SIL 2 single / SIL 3 redundant

Source: SAMSON official data sheet T 8387-3 EN (general technical data 5.3); the 3731-5 shares the platform, with differences in communication and electrical data.

III. 3731-3 versus 3731-5

Dimension3731-33731-5
CommunicationHART, 4-20 mA two-wireFOUNDATION Fieldbus, bus-powered
Data sheetT 8387-3 ENT 8387-5 EN
Display / tuningLCD plus single knob plus autotuneLCD plus single knob plus autotune
Software / interfaceTROVIS-VIEW plus SSP serial interface; DD / DTM support for FDT / DTM and AMSSame platform; per FF device description
MountingSAMSON integrated / NAMUR / IEC 60534-6-1 / VDI/VDE 3845; double-acting with Type 3710 reversing amplifierSame as left

Both are flameproof Ex d; differences lie mainly in communication protocol and electrical data. Define the protocol first, then build the order code using the Ex and option positions of T 8387-x.

Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN and NA 0122.

IV. Flameproof Construction and Wiring Points

ItemRequirement
Ex d wiringPer EN 60079-1 clauses 13.1 / 13.2, use cable entries or conduit systems with separate test certificates; do not use simple-type cable glands
Unused entriesSeal with certified blanking plugs to maintain the IP rating
Equipotential bondingInclude the positioner in the site equipotential bonding system
Cover openingNever open a flameproof enclosure while energized; damaged cover or connecting threads invalidate the Ex protection
Ex i optionOnly the terminal compartment may be opened in the hazardous area to connect a certified intrinsically safe circuit; once connected to a non-IS circuit the device can no longer be used as intrinsically safe equipment
Cable / terminalsUse metal cable entries below -20 C; terminals 0.2-2.5 mm², tightening torque at least 0.5 Nm
Signal diagnosisSet point above 22 mA shows OVERLOAD; below 3.7 mA moves to fail-safe position SAFE and shows LOW

Red line: Ex ia intrinsic safety is NOT Ex d flameproof enclosure. The flameproof housing of the 3731 is not equivalent to the intrinsically safe housing of the 3730; even when a 3731 carries an Ex ia option, the enclosure and wiring follow the marked type of protection separately.

Source: SAMSON official data sheet T 8387-3 EN electrical connections section; EN 60079-1, EN 60079-11 and EN 60079-14.

V. Order Code and Selection Boundaries

ItemDescription
Code length15 digits (versus 16 for the 3730 and 14 for the 3730-6)
Governing data sheetT 8387-3 EN / T 8387-5 EN
Digit structureIndependent of T 8384; Ex, communication, additional equipment, housing and certification digits and code sets all differ
Prohibited practiceDo not apply the 3730-3 16-digit table to the 3731, or infer a 3730 code from a 3731 code
ConfirmationSubject to the SAMSON official selection / ordering tool and latest data sheets; where unavailable or uncertain, write "please consult for confirmation"

Selection path: define the protocol first (3731-3 HART or 3731-5 FF), confirm the Ex d certificate against gas group and temperature class, determine the mounting kit from travel / angle and actuator, add limit switches, solenoids or position transmitters as needed, then generate the 15-digit code with the official tool.

Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN, T 8384-3 EN and T 8384-6 EN.

VI. Selection Guide and Common Models

Selection guide: Select the 3731 series when the hazardous area explicitly requires a flameproof enclosure (Ex d / Ex db): the 3731-3 for HART and the 3731-5 for FF. Only when supply / output pressure monitoring is also required should the Ex d[ja] option of the 3730-6 be considered, and its 14-digit code must not be mixed with the 15-digit 3731 code. Ex ia intrinsic safety is not Ex d flameproof enclosure; gas group and temperature class must be checked item by item.

Common models: 3731-3 (HART flameproof) and 3731-5 (FF flameproof); related models include the 3730-3 / 3730-4 / 3730-5 intrinsically safe platform, the 3730-6 (pressure monitoring, 14 digits) and the 3730-6 TS (SIS safety version).

If you are selecting a flameproof positioner for a Zone 1 hazardous area, or want to confirm the boundary between the 3731-3 / 3731-5 and the 3730-6 Ex d[ja], please feel free to contact us. We can check the model and order code against gas group, temperature class, communication protocol and mounting interface.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.