The SAMSON 3730-0 is the non-communication basic control model of the 3730 family of electro-pneumatic positioners. It uses purely mechanical control without a microprocessor to correlate the 4-20 mA input with valve stem travel. This article covers its technical data, the digit-by-digit 16-position order code, the boundaries against 3730-1/2/3/4/5/6 and the 3731 series, plus intrinsic safety and mounting points.

I. Product Positioning

ItemDescription
BrandSAMSON (SAMSON AG, independent group)
Series / modelBasic 3730 family model: 3730-0 (no communication, no microprocessor, purely mechanical control)
Control principleForce balance / mechanical comparison, no digital microprocessor
CommunicationNone (4-20 mA two-wire set point)
Explosion protectionIntrinsic safety Ex ia, Ex nA non-sparking, dust Ex tb/tc; no Ex d flameproof enclosure in this series
Data sheetT 8384-0 EN (basic type); general document NA 0122

The 3730-0 targets applications needing only a 4-20 mA set point with cost sensitivity and no HART or fieldbus. Unlike the 3730-1 with LCD and autotune or the full-featured digital 3730-2, the 3730-0 has no digital display or self-tuning.

Source: SAMSON official data sheets T 8384-0 EN and NA 0122; family boundaries per T 8384-3/4/5 EN and T 8384-6 EN.

SAMSON 3730 series intelligent electro-pneumatic positioner
SAMSON 3730 series positioner, same-series illustration; for illustration only, not the actual model; parameters subject to the official data sheet

II. Core Technical Data

ParameterTypical value / description
Input signal4-20 mA, two-wire
Supply pressure1.4-7.0 bar
Linear travel3.6-300 mm (mounting dependent; approx. 3.6-30 mm direct-mounted on Type 3277)
Rotary angle24-100 degrees
Hysteresis / sensitivityless than or equal to 0.3% / 0.1%
Ingress protectionIP66 (with terminal box), IP67 optional
Ambient temperature-40 to +80 C (housing and Ex option dependent)
Air qualityISO 8573-1: particles class 4 / oil class 3 / humidity class 3
MountingIntegrated on Type 3277 / NAMUR (IEC 60534-6-1) / VDI/VDE 3845 and 3847

These are common 3730 platform parameters. Accuracy appears as a range of plus/minus 0.1% to 0.5% across data sheets; the actual value is subject to the official data sheet and nameplate of the specific model.

Source: SAMSON official data sheets T 8384-0 EN and NA 0122; platform parameters per T 8384-3/4/5 EN.

III. Series-by-Series Differentiation within the 3730 Family

ModelCommunicationKey featureOrder code digits
3730-0NoneNo microprocessor, purely mechanical, no LCD / autotune16
3730-1NoneBasic digital type with LCD and autotune16
3730-2NoneFull-featured digital type, parameterization plus EXPERTplus diagnostics16
3730-3HART4-20 mA plus HART, most common version16
3730-4PROFIBUS PAFieldbus, digit 4 fixed to 016
3730-5FFFF bus, Ex protection uses 4 digits, leakage sensor option16
3730-6HARTSeparate design with supply / output pressure monitoring and Ex d[ja] option14
3731-3 / 3731-5HART / FFFlameproof Ex d housing, separate order code structure15

Key boundaries: 3730-4 is PROFIBUS PA; 3730-6 is a separate 14-digit design with pressure monitoring; 3731 is flameproof Ex d. None may share the digit table of 3730-0/1/2/3/5.

Source: SAMSON official data sheets T 8384-3/4/5 EN, T 8384-6 EN and T 8387-3/5 EN.

IV. 16-Digit Order Code, Digit by Digit

PositionOptionCode and meaning (excerpt)
P1Explosion protection0 none; 1 ATEX Ex ia IIC; 3 CSA intrinsic safety; 5 dust Ex tb only; 8 Ex nA
P2Inductive limit switch0 none; 1 SJ2-SN (NC contact)
P3Solenoid valve0 none; 4 with 24 V DC
P4-P7Additional equipment (mutually exclusive group)Position transmitter 1000 (4-20 mA feedback); external position sensor; analog input; leakage sensor; binary input; 0000 none
P8Self-diagnostics4 EXPERTplus; 0 standard EXPERT (basic type normally has no diagnostic option)
P9Fixed position0
P10Housing material0 aluminum (standard); 1 stainless steel
P11-P12Fixed positions0 / 0
P13Special application0 none; 1 paint-compatible; 2 1/4 NPT exhaust port; 6 with VDI/VDE 3847 adapter; 7 additional vent hole
P14Fixed position0
P15-P16Special version (with P1) marker00 standard; 12 IECEx; 34 Ex tb; 13 Ex nA; 14 EAC; 20 2Ex ic/nA

Complete code = "3730-0" plus 16 digits. The non-communication basic type has no bus identification fixed digit (digit 4 is not forced to 0). Example: 3730-0 1000000000000000 reads as ATEX intrinsic safety, no additional equipment, standard aluminum housing; set P2=1 for discrete limit feedback. The exact digit assignment is subject to data sheet T 8384-0 EN and the official selection tool, not the 3730-3/4/5 table.

Source: SAMSON official data sheets T 8384-0 EN and NA 0122; digit structure per the published T 8384-3 EN table. Positions marked with an asterisk must be confirmed with the official ordering tool.

V. Explosion Protection, Air Supply and Mounting

ItemKey point
Ex ia is NOT Ex dThe 3730-0 offers Ex ia / Ex nA / dust protection only; where Ex d flameproof enclosure is required, select the 3731 series instead
Intrinsically safe loopWire per EN 60079-14; observe Ui/Ii/Pi/Ci/Li versus associated apparatus Uo/Io/Po/Co/Lo
Instrument airDry, oil-free and dust-free; 1.4-7.0 bar supply; flush pipework before installation
Supply pressure estimateAir-to-open (FA / ATO): required supply approximately spring range upper limit plus 0.2 bar, minimum 1.4 bar
Mounting interfacesDirect on Type 3277, NAMUR (IEC 60534-6-1), or VDI/VDE 3845 / 3847
WiringCurrent source only; M20x1.5 cable gland; 0.2-1.5 mm² terminals; follow certified terminal assignment in hazardous areas

The basic type has no pressure monitoring or fieldbus diagnostics; do not promise the pressure monitoring of the 3730-6 or the HART communication of the 3730-3.

Source: SAMSON official data sheets T 8384-0 EN and NA 0122; intrinsic safety wiring principles per EN 60079-14.

VI. Selection Guide and Common Models

Selection guide: First confirm that communication and autotune are truly unnecessary: choose the 3730-0 for plain 4-20 mA positioning, the 3730-1 for LCD and autotune, the 3730-2 for full parameterization and EXPERTplus diagnostics, and the 3730-3 / 3730-4 / 3730-5 for HART / PROFIBUS PA / FF respectively. Use the 3731 series for flameproof applications and the 3730-6 for pressure monitoring. The order code is the 16-digit result generated by the official selection tool.

Common models: 3730-0 (basic mechanical), 3730-1 (basic digital) and 3730-2 (full-featured digital); the same family also includes the 3730-3 HART, 3730-4 PROFIBUS PA, 3730-5 FF, 3730-6 (14-digit pressure monitoring) and the 3731-3 / 3731-5 flameproof models.

If you are looking for a non-communication replacement positioner for an existing valve, or want to verify the Ex position and order code of a 3730-0, please feel free to contact us. We can check the model and digit assignment against the nameplate, mounting interface and certification requirements.