| Masoneilan 4700 Digital Positioner - Technical Data & Selection | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-22 09:38:23 | Views: | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Masoneilan 4700 / 4800 series are corrosion-resistant pneumatic and electro-pneumatic valve positioners based on cam feedback and force balance, with flow characteristics rewritable by custom cams. Their mechanical architecture is entirely different from the SVI digital positioners, and the series has been withdrawn from mainland China after its CCC certificate expired. Based on the 4700-4800pe Maintenance Manual (Rev. B / PN 720014889-888-0000), this article covers the model code, technical data, approvals and replacement advice. I. Product Positioning
The 4700 and 4800 share a numbering system, differing in capacity / travel coverage and air consumption. For digital communication, diagnostics and SIL, move to the SVI series; this mechanical type must not replace a digital positioner. Source: 4700-4800pe Maintenance Manual, Rev. B / PN 720014889-888-0000. Parameters are subject to the official manual.
II. Model Code and Travel / Hole PositionsModel structure (fields left to right per manual Figure 1): 4700 / 4800 + output capacity (7/8) + signal range + mounting (0/1) + type (P/E). The numeric codes of the "signal range" field are shown graphically and cannot be extracted from the text layer, so the permitted ranges from the manual text are listed and numeric model codes are not invented.
Source: 4700-4800pe Maintenance Manual, Rev. B / PN 720014889-888-0000, Figure 1 and travel table on page 20. Complete order codes should be supplemented from the manufacturer's How to Order table. III. General Technical Data
Source: 4700-4800pe Maintenance Manual, Rev. B / PN 720014889-888-0000, specification data in Table 7 (pages 65-66). IV. Performance and Signal Interfaces
The electric input must be supplied with constant current by the loop controller, output voltage at least 5 V and input resistance 170 Ohm nominal; never drive it with a voltage source. The 24 psig signal ranges (6-30 and 3-27 psig) require a different diaphragm assembly. Source: 4700-4800pe Maintenance Manual, Rev. B / PN 720014889-888-0000, Table 7 and section 5. V. Approvals, Protection and Replacement
The 4700 / 4800 series can no longer be sold in mainland China because its CCC certificate has expired. Replacement advice: the 4700P can be replaced by other brands of pneumatic positioner (such as Fisher, YTC, etc.); the 4700E can be replaced by an SVI1000 or SVI3 depending on site explosion-protection requirements. Source: 4700-4800pe Maintenance Manual, Rev. B / PN 720014889-888-0000, section 6 approvals and section 9 market status. Ex ia intrinsic safety is NOT Ex d flameproof enclosure; strictly distinguished. VI. Selection Guide and Common ModelsSelection guide: 4700 selection follows "confirm availability ( mainland CCC expired), define P pneumatic or E electro-pneumatic, define signal range and travel hole, define rotary / reciprocal mounting, define approval and protection, verify replacement option". Core red line: this is a mechanical force-balance positioner with no HART / FF communication and no digital diagnostics, and must not replace an SVI3 / SVI-FF; if the site needs a bus or diagnostics, move to the SVI series. If data is unavailable or uncertain, write "please consult for confirmation" and rely on the official manual. Common models: 4700P standard-capacity pneumatic type (holes A-E), 4700E electro-pneumatic type, 4800P / 4800E long-travel high-capacity types, and configurations with custom cam, bypass valve module (4700P direct-acting only) and 4000-type I/P converter. If you still hold 4700 / 4800 spare parts or are planning an end-of-life replacement and want to confirm signal range, travel hole and approvals, or to decide which SVI positioner to use, please feel free to contact us. We can check the replacement model together against your action, explosion-protection and interface requirements. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |

简体中文
ENGLISH