The Masoneilan SVI-FF is a digital valve positioner based on the FOUNDATION Fieldbus (FF) protocol. It uses a non-contact Hall-effect position sensor, offers SD standard and AD advanced diagnostic firmware, and is configured via ValVue / SVI FF DTM. Based on the SVI-FF positioner manual (ES-776 Rev. K / 2015), this article covers its functions, technical data, FISCO intrinsic-safety parameters and model code, and stresses the essential difference from the HART-platform SVI3.

I. Product Positioning

ItemDescription
Brand ownershipMasoneilan, part of Baker Hughes (formerly GE Oil & Gas), not GE process automation
Model / protocolSVI-FF, FOUNDATION Fieldbus (FF) digital positioner
Physical layerFF interface compliant with IEC 60079-11, IEC 61158-2, FF-816 physical layer
Position sensingNon-contact Hall-effect sensor; magnetic travel-sensor calibration required before installation
FirmwareSD (standard diagnostics) / AD (advanced diagnostics)
Configuration toolsValVue, SVI FF DTM, handheld (DD required); AO block / TB block configuration
SourceSVI-FF positioner manual (ES-776 Rev. K / 2015)

The SVI-FF is a bus-powered FF device, not a 4-20 mA + HART positioner. Its model code is SVI-abcdefgh, a different system from the HART-platform SVI3, and the two must not be interchanged. For HART communication select the SVI3 rather than offering this model as an SVI3 communication option.

Source: SVI-FF positioner manual (ES-776 Rev. K / 2015). Brand ownership: Masoneilan belongs to Baker Hughes, not GE. Parameters are subject to official samples.

Masoneilan SVI-FF digital positioner selection reference
Masoneilan digital positioner, appearance reference only, not the actual model; parameters subject to official samples

II. Main Functions and Capabilities

FunctionDescription
Digital positioningFF digital valve positioner, bus interface per IEC 60079-11 / IEC 61158-2 / FF-816
Diagnostic firmwareSD standard / AD advanced diagnostics
Position sensingNon-contact Hall-effect sensor; travel-sensor (magnetic) calibration required before installation
Control tuningAutotune, or Custom (values must be entered)
CharacterizationCharacterization Type can be customized (Custom requires entered values)
Fail actionACT_FAIL_ACTION: Valve Closed (most common) or Valve Open
Local operationOptional local LCD + 3 buttons (*/-/+: select/decrement/increment) behind a hinged cover
Function blocksAO block / TB block configuration, integrated into asset management via DTM / DD

Source: SVI-FF positioner manual (ES-776 Rev. K / 2015), sections 1-3.

III. Technical Data and Ex / FISCO

ItemValue
Operating temperature-40 C <= Ta <= 85 C
Operating voltage9-32 V DC (bus-powered)
Operating pressure150 psig (1.03 MPa)
Maximum current18.3 mA
Ingress protectionIP66; NEMA Type 4X
ATEXIntrinsic safety II 1G Ex ia IIC T6...T4 Ga; flameproof II 2G Ex d mb IIC T6...T4 Gb; dust II 2D Ex tb IIIC T96 C Db
IECExEx ia IIC T6...T4 Ga; Ex d mb IIC T6...T4 Gb; Ex tb IIIC T96 C Db
North AmericaClass I Div.1 GR A-D T6...T4; Zone 1 AEx d mb IIC T6...T4; Zone 0 AEx ia IIC T6...T4 Ga; Zone 21 AEx tb IIIC T96 C Db
Temperature classT4 Ta=-40 to 85 C; T5 Ta=-40 to 75 C; T6 Ta=-40 to 60 C
Approval bodiesFM, FMc, ATEX, IECEx, CSA, KOSHA, NEPSI, INMETRO, GOST, JIS, CCOE

Source: SVI-FF positioner manual (ES-776 Rev. K / 2015), technical data chapter. Approvals are subject to official certificates.

IV. FISCO and Entity Intrinsic-Safety Parameters

ParameterFISCO intrinsic safetyEntity
Ui17.5 V24 V
Ii380 mA250 mA
Pi5.32 W1.2 W
Ci1 nF1 nF
Li1 uH1 uH

An intrinsically safe (Ex ia) loop must configure the safety barrier / isolator and verify bus length and spurs according to FISCO or Entity parameters. Flameproof (Ex d mb) is a different form of explosion protection and must not be confused with intrinsic safety. If data is unavailable or uncertain, write "please consult for confirmation" and rely on official certificates and loop calculations.

Source: SVI-FF positioner manual (ES-776 Rev. K / 2015), FISCO / Entity parameter table. Ex ia intrinsic safety is NOT Ex d flameproof enclosure; strictly distinguished.

V. Model Code (SVI-abcdefgh)

DigitMeaningOptions and meaning
aInternal firmware style1..X (independent of protection type; SD standard / AD advanced diagnostics)
bPneumatic system1 = single acting; 2 = double acting
cPneumatic (air flow)1 = standard flow; 2 = high flow
dDisplay / housing material1 = no display no buttons aluminum; 2 = display + buttons aluminum; 3 = no display no buttons stainless; 4 = display + buttons stainless
eCommunication protocolF = Foundation Fieldbus; P = PROFIBUS
fOptions1..X (f=1 = no options in the manual)
gAgency approval2 = UNI-LABEL (ATEX, IEC, FM, FMc)
hOther agency approval1 = North America division (FM, FMc); 2 = GOST; 3 = KOSHA; 4 = NEPSI; 5 = INMETRO; 6 = JIS; 7 = CCOE

The serial number format is SN-nnyywwnnnn. The page-8 "product number" summary and section 3 describe digits a and g from different angles; section 3 is treated as authoritative. Complete order codes should be generated with the official ordering tool.

Source: SVI-FF positioner manual (ES-776 Rev. K / 2015), model code chapter. Digit count and meanings are subject to the official manual.

VI. Selection Guide and Common Models

Selection guide: SVI-FF selection follows "confirm FF bus, define diagnostic firmware (SD / AD), define single/double acting and flow, define display and housing material, define approvals (UNI-LABEL + division certificate), calculate the intrinsic-safety loop per FISCO / Entity". Core red lines: 1. SVI-FF is an FF bus device and SVI3 a HART 7 device, with different protocols and model codes that must not be interchanged; 2. Ex ia intrinsic safety is NOT Ex d flameproof enclosure, confirmed separately by digits g/h and FISCO parameters; 3. specific order codes, approvals and loop parameters are subject to official manuals and certificates and are not invented.

Common models: SVI-FF single-acting standard-flow aluminum basic type (e=F), double-acting high-flow type with display and stainless housing, AD advanced-diagnostics UNI-LABEL type, and configurations with NEPSI / GOST / KOSHA division certificates.

If you are selecting a positioner for an FF bus project and want to confirm the SVI-FF diagnostic firmware, intrinsic-safety parameters and order code, or to clarify its difference from the HART-platform SVI3, please feel free to contact us. We can check the model and order code together against your bus protocol, hazardous-area division and loop calculation.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.