| Fisher 585C Actuator - Working Principle & Technical Data | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-22 09:38:23 | Views: | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Fisher 585C is a low-to-medium thrust piston actuator for small to medium sliding-stem control valves. Its double-acting design provides rigid, precise positioning, and sizes 25/50 can be fitted with a balanced spring to form the 585CR spring-return variant. This article covers its working principle, sizes and output data, service and materials, differences from related models and selection points. I. Product Positioning
The 585C sits below the 785C (long-stroke high-thrust) in the low-to-medium thrust range; sizes 60-130 are available only without spring. For fail-safe position either select the 585CR balanced spring on sizes 25/50 or add a 377 lock-up valve system. Source: Emerson / Fisher official product pages and Fisher 585C Series Piston Actuators manual D102087X012 (2013-10). Brand ownership: Emerson.
II. Working Principle and Construction
The 585C provides low-to-medium thrust for sliding-stem valves; its double-acting construction holds the valve rigidly throughout travel, while the nickel-plated / aluminum cylinder, hard-chromed push rod and low-friction seals give long life and low air consumption. Source: Fisher 585C Series Piston Actuators manual D102087X012. Construction description is subject to the official manual. III. Sizes, Weights and Output Data
The 585CR spring thrust figures for sizes 25/50 come from manual tables 6/7 at 10.3 bar design pressure. Actual available thrust must be checked point by point against supply pressure and travel; do not simply take the maximum table value. Source: Fisher 585C Series Piston Actuators manual D102087X012 tables 3 and 6/7; product page catalog data. Values are subject to the official manual. IV. Service Data and Materials
Air must be clean, dry and oil-free per ISA 7.0.01 / ISO 8573-1; insufficient supply pressure causes inadequate thrust and incomplete travel. For spring-return versions, net thrust must be calculated as thrust minus spring force. Source: Fisher 585C Series Piston Actuators manual D102087X012 and official product page; air standard ISA 7.0.01 / ISO 8573-1. V. Differences: 585C / 585CR vs 785C
When required thrust or stroke exceeds the 585C family range, move to the 785C rather than raising supply pressure beyond the manual limit; exceeding allowable pressure risks equipment damage and safety incidents. Source: Fisher 585C manual D102087X012 and Fisher 785C Product Bulletin 61.2:785C (D104412X012, May 2022). VI. Selection Guide and Common ModelsSelection guide: First size the actuator by required thrust and stroke (25-130); then decide between springless 585C and 585CR balanced spring (sizes 25/50 only) based on fail-safe requirements; then verify supply pressure (25-50 max 10.3 bar, min 1.4 bar; 60-130 min 2.4 bar), temperature and material options; finally determine the positioner (DVC6200 or 3600), handwheel, 377 lock-up valve and limit switches. Write subject to official manual / nameplate or please consult for confirmation for unavailable size-by-size thrust and approval data. Common models: 585C sizes 25 / 50 / 60 / 68 / 80 / 100 / 130 (double-acting, balanced spring available on 25/50); 585CR (spring-return, sizes 25/50); 785C for high thrust and long stroke. If you are selecting feedback rods and mounting kits, verifying spring range and supply pressure, or making a preliminary Cv and size calculation, please feel free to contact us. We can work through the selection and verification together against your valve service, interface standards and installation conditions. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |