Fisher DVC2000 Positioner - Model Code Decoding & Options
Release time:2026-11-22 09:38:23 | Views:

Fisher FIELDVUE DVC2000 is an entry-level single-acting digital valve controller with HART communication, linkage-less Hall-effect position feedback and a local LCD with four-key interface. Its order code is assembled from segments covering area approval, housing, connections, pressure class, I/O, diagnostics and language. This article decodes the segments and gives a typical model example with selection points.

I. Product Positioning

ItemDescription
BrandFisher (Emerson)
ModelFIELDVUE DVC2000 digital valve controller
TypeSingle-acting digital valve controller based on HART 4-20 mA input
FeedbackHall-effect non-contact linkage-less position feedback, no mechanical wear
InterfaceAluminum construction, 4-key LUI + LCD local display (12 languages)
MountingNAMUR / IEC 60534-6-1 / IEC 60534-6-2
Explosion protectionCENELEC / CSA / FM / ATEX / IECEx / NEPSI etc. by code; Ex ia intrinsic safety is not Ex d flameproof enclosure; verify certificates
Main documentFisher FIELDVUE DVC2000 product bulletin D351133X012 (2019)

The DVC2000 targets general process control and throttling applications on a single-acting platform. For double-acting or fieldbus service, move to the DVC6200 series. Gulde 3800SA is a re-badged version built on the same line but uses a different model code system; the segment table in this article does not apply to it.

Source: Fisher FIELDVUE DVC2000 product bulletin D351133X012 (2019). Brand ownership: Emerson. Ex ia intrinsic safety is not Ex d flameproof enclosure; official certificates govern.

Fisher DVC2000 digital positioner
Fisher DVC2000 digital positioner, same model, for selection reference only

II. Core Technical Specifications

ItemDescription
ParameterSpecification / Description
CommunicationHART 5 (4-20 mA input)
Input signal4-20 mA DC; minimum loop voltage 8.5 V DC, 9.0 V DC for HART
Maximum inlet pressure100 psi (7 bar)
OutputSingle-acting direct acting, up to 95% of supply pressure
Travel rangeLinear 6.35-606 mm; rotary 45-90 degrees
Position feedback option4-20 mA position transmitter + independent switch (option 5B)
Limit switchesTwo independent switches, 5-30 V DC
Position transmitter4-20 mA, 8-30 V DC, approx. 1% travel accuracy
Ingress protectionNEMA 4X / CSA Type 4X / IEC 60529 IP66
Ambient temperature-40 to +80 C (another bulletin states -40 to +85 C; LCD may be unreadable below -20 C)
Construction / weightA03600 low-copper aluminum; approx. 1.5 kg; approx. 90 x 106 x 165.6 mm
Electrical / air connections1/2 NPT female (standard) / M20 (optional); supply/output 1/4 NPT (standard) / G1/4 (optional)

Temperature and weight figures differ slightly between bulletin revisions; use the actual nameplate and order confirmation rather than inventing an intermediate value.

Source: Fisher FIELDVUE DVC2000 product bulletin D351133X012 (2019) specification summary and product family overview. Parameters subject to the latest official bulletin.

III. Order Code Segment Structure

SegmentMeaningCommon codes (excerpt)Description
1Hazardous area approval1C / 1D / 1G etc.1C is ATEX intrinsic safety; the code determines Ex ia or Ex d, never guess from housing
2Housing material / design2A etc.2A is type B standard design; aluminum or per option
3Conduit and air connections3A / 3B etc.3A is 1/2 NPT conduit plus 1/4 NPT air
4Operating / supply pressure4A / 4B etc.4B is 3.4-7.0 barg
5Position feedback I/O5A / 5B etc.5A no feedback; 5B transmitter plus independent switch
6Diagnostics levelHC / AD / PD / ODV etc.HC is HART communication diagnostics; ODV is not available on DVC2000
7Local interface languageEN / othersEN is English; 12 languages available
8Other optionsSF / HF / XX etc.SF 10 micron integral supply filter; HF HART filter

Example: DVC2000 1C_2A_3A_4B_5A_HC_EN_SF HF means DVC2000 body, ATEX intrinsic safety (1C), type B standard housing (2A), 1/2 NPT conduit plus 1/4 NPT air (3A), 3.4-7.0 barg (4B), no position feedback (5A), HART communication diagnostics (HC), English interface (EN), 10 micron integral filter (SF) and HART filter (HF).

Source: Fisher FIELDVUE DVC2000 product bulletin D351133X012 (2019) ordering information and example. Complete codes are subject to the official selection tool / order confirmation.

IV. I/O and Diagnostic Options

ItemDescription
OptionFunctionConstraint / Note
5ANo position feedbackValve position read vialocal HART only
5BPosition transmitter + independent switch4-20 mA feedback plus limit switch
Limit switchesTwo independent switches, 5-30 V DCOpen / closed position feedback
Position transmitter4-20 mA, 8-30 V DCReference accuracy approx. 1% of travel
HCHART communication / basic diagnosticsAlarms and communication supported
AD / PDAdvanced / performance diagnosticsRequire ValveLink; available levels on DVC2000 subject to bulletin
ODVOptimized Digital Valve diagnosticsValid only on DVC6200H (HART); not offered on DVC2000
SF10 micron integral supply filterImproves particle protection
XTExtreme low temperature (fluorosilicone)Availability on DVC2000 subject to official bulletin; XT on DVC6200 is aluminum only

Diagnostic data are usable only if a HART acquisition path exists: if the DCS has no AMS / asset management station or HART multiplexer, diagnostics will not be routinely read. Confirm the availability of HART acquisition at the selection stage.

Source: Fisher FIELDVUE DVC2000 product bulletin D351133X012; diagnostic level definitions per Fisher DVC6200 manual D103605X012. Option availability subject to official bulletin.

V. Explosion Protection and Safety Boundaries

DimensionIntrinsically safe Ex iaFlameproof Ex d
PrincipleLimits loop energy so sparks cannot ignite the mixtureRobust enclosure withstands internal explosion and prevents flame propagation
DVC2000 codeDetermined by segment 1 approval code (e.g. 1C ATEX intrinsic safety)Requires the corresponding flameproof approval code; e.g. 1D denotes ATEX fireproof in a DVC6200 SIS example
Loop requirementUsually requires a safety barrier / isolator per certified parametersFlameproof wiring and sealing practices apply
VerificationCheck official certificate and nameplate; if uncertain write please consult for confirmationSame

Red line: Ex ia intrinsic safety is not Ex d flameproof enclosure. They are not interchangeable and must not be merged into one code merely because both are hazardous-area approvals. The exact DVC2000 approval combination is subject to nameplate and certificate.

Source: Fisher FIELDVUE DVC2000 product bulletin D351133X012; Ex forms strictly distinguished and subject to official certificates.

VI. Selection Guide and Common Models

Selection guide: Follow the sequence define action (DVC2000 is single-acting only), define area approval (segment 1, distinguish Ex ia from Ex d), define housing and connections (segments 2 and 3), define pressure class (segment 4), define I/O feedback (segment 5), define diagnostics (segment 6), define language and other options (segments 7 and 8). For double-acting, fieldbus, PST or SIL service choose the DVC6200 series. For intrinsic safety loops verify barrier parameters. Order codes are subject to the official selection tool and order confirmation; codes are not invented.

Common models: DVC2000 (HART, single-acting, LCD and 4 keys), a typical configuration being 1C_2A_3A_4B_5A_HC_EN_SF HF. The re-badged Gulde 3800SA uses an independent coding system and must be selected per its own bulletin.

If you are verifying a positioner model, spare part or diagnostics level, or want to confirm air purification and area approval requirements, please feel free to contact us. We can check the model and configuration together against your protocol, actuator interface and site approval conditions.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.