The ABB TZIDC series (order code V18345) is a smart electro-pneumatic positioner with an LCD and local operator panel, supporting 4-20 mA two-wire, HART communication and multiple Ex options, with mounting compatible with NAMUR / IEC 534 and VDI/VDE 3845. This article organizes its technical data, digit-by-digit order code, Ex protection and selection points based on ABB official operating instructions, ordering data and the Chinese data sheet. No in-house ABB positioner material is available; all online-sourced data is annotated with sources in the text, and parameters are subject to the official ABB catalog. I. Product Positioning
The TZIDC compares the setpoint with position feedback in a microprocessor and outputs pneumatic pressure to drive the actuator. Its local LCD and pushbuttons handle commissioning and configuration, and the ABB local communication interface (LCI) can connect a programming device outside hazardous areas. The TZIDC-110 / TZIDC-120 are versions oriented to intrinsic safety and specific approvals; verify them digit by digit against the order code. Source: ABB official documents 3KXE341007R4201-42/18-84-EN, 10_18-022-EN-A-07_2007 and DS_TZIDC_ZH_I. Parameters are subject to the latest official ABB catalog.
II. Series Versions and Communication OptionsThe following data was obtained via online search. Sources: ABB official TZIDC ordering data 10_18-022-EN (https://library.e.abb.com/public/1b4989c6fa0a198fc1257b0c005493dd/10_18-022-EN-A-07_2007.pdf); ABB official TZIDC operating instructions 3KXE341007R4201 (https://library.e.abb.com/public/60ef1a03711a8025c1257a1e0032fa7a/3KXE341007R4201-42_18_84_EN_C_06_2012.pdf).
Communication capability is determined by the "input / communication port" group of the order code: the basic type has only 4-20 mA two-wire, an LKS adapter adds the local interface, and only an added FSK module enables HART. Do not assume a unit has HART merely from the V18345 prefix; check the complete order code. The above data was obtained via online search. Sources: https://library.e.abb.com/public/1b4989c6fa0a198fc1257b0c005493dd/10_18-022-EN-A-07_2007.pdf, https://library.e.abb.com/public/60ef1a03711a8025c1257a1e0032fa7a/3KXE341007R4201-42_18_84_EN_C_06_2012.pdf. Ex markings are subject to official certificates. III. Core Technical DataThe following data was obtained via online search. Sources: ABB official TZIDC operating instructions 3KXE341007R4201 and Chinese data sheet DS_TZIDC_ZH_I.
For intrinsically safe input circuits, note the entity parameters: for example terminals 11/12 have Vmax = 30 V, Imax = 104 mA, Ci = 6.6 nF and Li = 0 uH, which must match the associated apparatus. The LCI may only be used outside hazardous areas; never connect the local communication port directly inside a hazardous area during commissioning. The above data was obtained via online search. Sources: https://library.e.abb.com/public/60ef1a03711a8025c1257a1e0032fa7a/3KXE341007R4201-42_18_84_EN_C_06_2012.pdf, https://cn.library.e.abb.com/public/e4b0677698b443bd94cac80500b9cc4a/DS_TZIDC_ZH_I.pdf. Entity parameters and temperature codes are subject to official certificates. IV. Order Code Structure (V18345)The following data was obtained via online search. Source: ABB official TZIDC ordering data 10_18-022-EN (https://library.e.abb.com/public/1b4989c6fa0a198fc1257b0c005493dd/10_18-022-EN-A-07_2007.pdf).
Digits are concatenated, and some combinations are mutually exclusive (for example the SIL 2 declaration CS2 is available only with certain Ex forms and single-acting Fail Safe pneumatic conditions; the mechanical digital feedback kit is only for versions with a mechanical position indicator). Generate the complete order code with the ABB official selection tool; do not invent codes. The above data was obtained via online search. Source: https://library.e.abb.com/public/1b4989c6fa0a198fc1257b0c005493dd/10_18-022-EN-A-07_2007.pdf. Digits and meanings are subject to the official ordering manual. V. Ex Protection and Mounting (Ex ia is not Ex d)The following data was obtained via online search. Sources: ABB official TZIDC operating instructions 3KXE341007R4201 and Chinese data sheet DS_TZIDC_ZH_I.
Ex ia intrinsic safety and Ex d flameproof enclosure are two different forms. The TZIDC order code mainly offers Ex ia / Ex ib / Ex ic and Ex nA options, and the exact approval must be checked against official certificates; if unavailable or uncertain, write "please consult for confirmation". For mounting, use DIN/IEC 534 / NAMUR for linear actuators and VDI/VDE 3845 for rotary actuators; standard attachment requires separately purchased mounting material. The above data was obtained via online search. Sources: https://library.e.abb.com/public/60ef1a03711a8025c1257a1e0032fa7a/3KXE341007R4201-42_18_84_EN_C_06_2012.pdf, https://cn.library.e.abb.com/public/e4b0677698b443bd94cac80500b9cc4a/DS_TZIDC_ZH_I.pdf. Ex ia intrinsic safety is not Ex d flameproof enclosure; official certificates govern. VI. Selection Guide and Common Models
Selection guide: ABB TZIDC selection follows "define mounting, define communication, define Ex protection, define acting and safe position, define connections and feedback". Core red lines: 1. HART capability depends on digit 2, not the V18345 prefix; 2. Ex ia intrinsic safety and Ex d flameproof enclosure are strictly distinguished, writing "please consult for confirmation" when unavailable; 3. LCI / LKS local interfaces are only for use outside hazardous areas; 4. Fail Safe and Fail Freeze are different codes and must follow the process safety logic; 5. where digit combinations are mutually exclusive, use the ABB official selection tool and do not invent order codes. Common models: TZIDC basic type V18345-0...; common progression includes V18345-1 (aluminum NAMUR linear mounting), V18345-2 (with LKS / HART communication port) and V18345-3 (with LKS adapter and HART FSK module); the same series includes TZIDC-110 and TZIDC-120 intrinsically safe versions. Generate the exact complete order code with the ABB official selection tool. If you are selecting a positioner for a control valve, or want to confirm the ABB TZIDC communication port, Ex code or fail-safe option, please feel free to contact us. We can check the order code together against your actuator interface, protocol and area certification requirements. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |