The Siemens SIPART PS2 (6DR5...) is a smart electro-pneumatic positioner using piezoelectric valve technology, available in 4-20 mA/HART, PROFIBUS PA and FOUNDATION Fieldbus versions, with automatic initialization, low air consumption and extensive diagnostics. This article organizes its working principle, technical data, DIP switch and initialization commissioning steps based on the Siemens official concise operating instructions. No in-house PS2 article material is available; all online-sourced data is annotated with sources in the text, and parameters and procedures are subject to the official manual.

I. Product Positioning

ItemDescription
BrandSiemens (independent brand)
SeriesSIPART PS2 (6DR5...) smart electro-pneumatic positioner
Product typeSmart electro-pneumatic positioner (single / double acting, linear / rotary actuators)
Control principleMicroprocessor control plus piezoelectric valve technology; consumes air only while moving
Communication4-20 mA / HART; PROFIBUS PA; FOUNDATION Fieldbus (FF)
CommissioningLocal pushbuttons for automatic / manual initialization; DIP switch (transmission selector S1) or rotary switch; configuration via SIMATIC PDM or a handheld communicator
MountingNAMUR mounting on linear and rotary actuators (IEC 60534-6-1 / VDI/VDE 3845)
Source documentSiemens official SIPART PS2 (6DR5...) concise operating instructions A5E03436620-AF

The SIPART PS2 compares the controller output with the valve position feedback inside its microprocessor and drives the actuator air path through a piezoelectric valve. During initialization the microprocessor automatically determines the actuator zero point, maximum travel, direction of action and positioning speed, and from these derives the minimum pulse time and dead band to optimize control. Its air consumption is far lower than a conventional nozzle-flapper positioner.

Source: Siemens official SIPART PS2 (6DR5...) concise operating instructions A5E03436620-AF (https://cache.industry.siemens.com/dl/files/718/109781718/att_1031200/v1/A5E03436620-AFzh_PS2_COI_zh-CHS.pdf). Parameters and procedures are subject to the official manual.

Siemens instrument appearance reference
Siemens instrument appearance reference only, not an actual SIPART PS2 unit; refer to the official catalog

II. Versions and Communication Options

The following data was obtained via online search. Source: Siemens official SIPART PS2 (6DR5...) concise operating instructions A5E03436620-AF (https://cache.industry.siemens.com/dl/files/718/109781718/att_1031200/v1/A5E03436620-AFzh_PS2_COI_zh-CHS.pdf).

VersionCommunicationDescriptionVerification point
4-20 mA / HART4-20 mA with HART overlayBasic type, two-wire loop; supports SIMATIC PDM, AMS Device Manager and field communicatorsManual lists EDD 24.00.00 or higher (September 2020 edition, device version 7 or higher)
PROFIBUS PAPROFIBUS PA fieldbusBus powered, cyclic exchange of setpoint and valve positionPA firmware 6.01.00 or higher (September 2020 edition); check GSD mapping
FOUNDATION FieldbusFF busFunction-block integration into an FF segmentConfirm compatible versions per official manual
Single / double actingPneumatic outputs Y1 / Y2Double-acting versions (e.g. 6DR5xx2 / 6DR5xx3 suffix) provide a second pneumatic output Y2For double acting, swap Y1 / Y2 tubing before re-initializing
Option modulesDIO 6DR4004-6A/-8A, AOM 6DR4004-6J/-8J, ILS 6DR4004-6G/-8G, MLS 6DR4004-6K/-8K, internal NCSDigital I/O, analog output, inductive / mechanical limit switches, non-contacting position sensingVerify option model and -Z order suffix against the official catalog

The communication version is fixed by the ordered model; a basic HART unit cannot be converted on site to PROFIBUS PA or FF. The HART basic type corresponds to suffixes such as 6DR5x1x, while bus types use the 6DR5x2x series; confirm the exact suffix against the Siemens official selection table.

The above data was obtained via online search. Source: https://cache.industry.siemens.com/dl/files/718/109781718/att_1031200/v1/A5E03436620-AFzh_PS2_COI_zh-CHS.pdf. Model suffixes and firmware versions are subject to official selection data.

III. Working Principle

The following data was obtained via online search. Sources: SIPART PS2 smart electro-pneumatic positioner technical data (http://www.ahhenghui.cn/upload/files/201901/15484015549124.pdf); Siemens official concise operating instructions A5E03436620-AF.

StageProcessPurpose
Signal comparisonThe microprocessor compares the setpoint (4-20 mA / bus setpoint) with the position feedback to derive an errorForms a closed position-control loop
Piezoelectric valve driveAccording to the error polarity, the piezo valve charges or vents the actuator chamber; it closes at steady stateAir is consumed only while moving, greatly reducing consumption
Position sensingLinear or rotary displacement is converted into an electrical signal returned to the microprocessorProvides continuous valve position feedback
Automatic initializationAutomatically determines zero point, maximum travel, direction of action and positioning speed, then derives minimum pulse time and dead bandOptimizes control without manual tuning
Diagnostics and alarmsRecords travel accumulation, direction reversals, alarm count, dead-band self-adjustment, end positions, hours at high / low temperature, piezo valve cycles, positioning time and actuator leakageSupports condition monitoring and predictive maintenance

Piezoelectric valve technology is the key to the low air consumption of the PS2: a conventional positioner vents continuously through a restriction to hold balance, whereas the PS2 does not vent at steady state and only acts briefly when position changes. Initialization is completed by internal algorithms; after completion, verify zero and span before returning the valve to service.

The above data was obtained via online search. Sources: http://www.ahhenghui.cn/upload/files/201901/15484015549124.pdf, https://cache.industry.siemens.com/dl/files/718/109781718/att_1031200/v1/A5E03436620-AFzh_PS2_COI_zh-CHS.pdf. Subject to the Siemens official manual.

IV. Core Technical Data

The following data was obtained via online search. Source: Siemens official SIPART PS2 (6DR5...) concise operating instructions A5E03436620-AF (chapter 7, technical data).

ParameterDescription
Input signal4-20 mA (HART type); PROFIBUS PA / FF powered and communicated over the bus
Supply air1.4-6 bar (set according to actuator requirements during installation and commissioning)
Travel / angleBoth linear and rotary actuators supported; travel detected during initialization; rotary transmission ratio 33 or 90 degrees
Acting typeSingle and double acting (double acting provides Y1 / Y2 pneumatic outputs)
CommissioningLocal pushbutton automatic / manual initialization; remote configuration via SIMATIC PDM or handheld communicator
Display and operationLocal LCD and pushbuttons, switching between automatic / manual / configuration modes; manual mode drives the valve over full travel
Option modulesDIO digital I/O, AOM analog output, AIM analog input, ILS inductive limit switches, MLS mechanical limit switches, internal / external NCS non-contacting position sensing
Ex protection and approvalsEx marking determined by the basic-unit type key (model suffix), including intrinsically safe and flameproof versions; verify against nameplate and certificates
Firmware / engineering compatibilitySeptember 2020 manual edition: HART firmware 5.02.00 or higher (device version 7 or higher), EDD 24.00.00 or higher; PA firmware 6.01.00 or higher

The Ex marking is determined by the basic-unit type key; if unavailable or uncertain, write "please consult for confirmation". Ex ia intrinsic safety and Ex d flameproof enclosure are two different forms and must never be inferred merely from the presence of a bus interface.

The above data was obtained via online search. Source: https://cache.industry.siemens.com/dl/files/718/109781718/att_1031200/v1/A5E03436620-AFzh_PS2_COI_zh-CHS.pdf. See chapter 7 of the official manual for rated conditions, pneumatic data and Ex markings.

V. Commissioning: DIP Switch and Initialization Steps

The following data was obtained via online search. Sources: Siemens official concise operating instructions A5E03436620-AF (chapter 5, commissioning); SIPART PS2 direction setting and initialization note (https://industrialmonitordirect.com/zh-hant/blogs/knowledgebase/configuring-sipart-ps2-ydir-and-sdir-to-invert-feedback; DIP and parameter-name details come from this online source and are subject to the official manual).

StepActionKey point
1. Mechanical preparationMount on the actuator per NAMUR, connect the feedback lever and air lines, apply 1.4-6 bar supply airVerify vent direction and leak-free tubing
2. DIP / transmission switchSet the transmission selector (S1 or rotary switch) to 33 or 90 degrees, consistent with parameter 2.YAGLA mismatch can corrupt position sensor calibration
3. Direction parametersCheck YFCT (flow characteristic / direction), SDIR (setpoint direction) and YDIR (position display direction)YDIR affects only HART variable 244, the PA / FF slot and the local LCD, not variables 246 / 247
4. Enter initializationUse local pushbuttons to enter FINI (Init in newer menus), select Auto and confirmDisplay cycles Pr1, Pr2, Pr3, Pr4 and counts down from 5
5. Automatic tuningThe positioner drives the valve through full travel and learns the upper / lower range values X.TU / X.TL, hysteresis, temperature compensation and (optionally) self-tightening frictionA rotary valve takes about 2-4 minutes
6. Double-acting correctionIf the actuator extends the wrong way as the setpoint rises, first swap the Y1 / Y2 tubing and re-initializeDo not change YFCT / SDIR / YDIR first; swapping is faster and reversible
7. Verification and cancellationVerify zero and span; if needed, cancel initialization per official manual section 5.8Confirm displayed position matches actual travel before return to service

Switching between 33 and 90 degrees changes the internal transmission ratio and reverses the direction of action: changing from 33 to 90 gives a 0-90 degree working range, and from 90 to 33 gives 0-33 degrees. The logical parameter 2.YAGL must be set to the same range as the physical transmission switch on the electronics module. PROFIBUS PA versions must also check the GSD mapping: the setpoint may be sent as a 0-100% floating point or as a 0-27648 integer (100% = 27648).

The above data was obtained via online search. Sources: https://cache.industry.siemens.com/dl/files/718/109781718/att_1031200/v1/A5E03436620-AFzh_PS2_COI_zh-CHS.pdf, https://industrialmonitordirect.com/zh-hant/blogs/knowledgebase/configuring-sipart-ps2-ydir-and-sdir-to-invert-feedback. DIP and parameter details are subject to the Siemens official manual.

VI. Diagnostics and Status Indication

The following data was obtained via online search. Source: SIPART PS2 smart electro-pneumatic positioner technical data (http://www.ahhenghui.cn/upload/files/201901/15484015549124.pdf).

Diagnostic itemMeaningOutput
Travel accumulation / direction reversals / alarm countReflects how often the valve moves and the number of anomaliesLocal display, HART, bus interface
Dead-band self-adjustment / positioning timeReflects control quality and responseLocal display, HART, bus interface
Valve end position (e.g. seat wear) / actuator leakageEarly detection of mechanical wear and air-path faultsStatus alarm output, HART / bus
Hours at highest / lowest temperature, piezo valve cyclesAccumulated severe-service hours and key component lifeRead via asset management system
Three-level alarm (green / yellow / red wrench)Maintenance required / urgently required / imminent or actual faultShown in PDM software, also available via wired output

The three-level alarm follows a "traffic light" scheme and can warn before a major failure of the valve or actuator, avoiding a plant shutdown. Examples include diaphragm damage, delayed motion, packing friction, seat wear and buildup or fouling.

The above data was obtained via online search. Source: http://www.ahhenghui.cn/upload/files/201901/15484015549124.pdf. Diagnostic items are subject to the Siemens official manual and firmware version.

VII. Selection Guide and Common Models

Selection guide: SIPART PS2 selection follows "define communication protocol (HART / PROFIBUS PA / FF), define single or double acting, define linear or rotary and mounting interface, define the Ex type key, define option modules (DIO / AOM / ILS / MLS / NCS)". Core red lines: 1. the communication version is fixed by the ordered model and a basic HART unit cannot be converted to a bus type on site; 2. the 33 / 90 degree transmission switch must match parameter 2.YAGL or initialization results are invalid; 3. for double-acting units with wrong direction, swap the Y1 / Y2 tubing before re-initializing; 4. Ex ia intrinsic safety is NOT Ex d flameproof enclosure and must be confirmed against the nameplate and certificates; 5. firmware and EDD versions must match the PDM / asset management system. All parameters are subject to the Siemens official manual; this article does not replace original documentation.

Common models: SIPART PS2 basic 6DR5... (4-20 mA / HART), PROFIBUS PA type 6DR5x2x, FF type and double-acting suffixes 6DR5xx2 / 6DR5xx3; common options are 6DR4004-6A/-8A (DIO), 6DR4004-6J/-8J (AOM), 6DR4004-6G/-8G (ILS), 6DR4004-6K/-8K (MLS) and the internal NCS module.

If you are selecting a positioner for a control valve, or want to confirm the communication version, single or double acting configuration and initialization procedure of the SIPART PS2, please feel free to contact us. We can check the model and commissioning steps together against your actuator, protocol and certification requirements.