The Neles NE724 (now under Valmet Flow Control, formerly Metso) belongs to the NE700 series and is an analog (proportional) electro-pneumatic valve positioner based on the force-balance principle: 4-20 mA input, a 4 mm pilot valve and a 1/4 NPT connection, suited to actuators with a swept volume of 1.0-8.0 dm3. This article explains its force-balance working principle, model options and applications, and clearly distinguishes it from the ND9000 series digital valve controllers.
I. Product Positioning
| Item | Description |
| Brand ownership | NELES (formerly the Metso positioner product line, now under Valmet Flow Control) |
| Series | NE700 series analog electro-pneumatic positioner |
| Model covered | NE724/RS1 (NE = electro-pneumatic positioner, 7 = NE700, 2 = 4-20 mA, 4 = 4 mm pilot valve 1/4 NPT; RS1 = IP65 housing + VDI/VDE 3845 mounting face with H clamp) |
| Control principle | Analog (proportional) positioner based on force balance, not a microprocessor-based smart positioner |
| Communication / diagnostics | No communication protocol, no diagnostics, no valve signature or event log |
| Applicable actuators | Diaphragm or piston, linear and rotary valves; swept volume 1.0-8.0 dm3 |
| Source | Neles official manual "NE700/NP700 Positioners" 7NENP20EN (-10/2020) |
Source: Neles official manual 7NENP20EN (-10/2020, also a 2/2026 bulletin) sections FEATURES, PRINCIPLE OF OPERATION, TECHNICAL DATA and How to Order. Parameters are subject to the official manual and nameplate / order; unlisted items are not invented.

Neles NE724/RS1 electro-pneumatic valve positioner (same model), for selection reference only
II. Working Principle: Force Balance
| Stage | Process |
| Input torque | The force coil in a permanent magnetic field generates a torque proportional to input current, acting on the balance beam |
| Feedback torque | The feedback spring, via feedback shaft / cam / lever, generates an opposing torque balanced against the input torque |
| Imbalance detection | The nozzle senses the displacement imbalance of the balance beam |
| First-stage amplification | Nozzle + diaphragm piston amplify the signal |
| Second-stage amplification | Pilot valve + actuator deliver airflow, driving the stem until valve position corresponds to the signal |
The NE724 is therefore a purely pneumatic-amplified analog positioner: there is no microprocessor inside and no self-diagnostics, online diagnostics, valve signature or event log. For on-site status judgement, a mechanical position indicator, external limit switch / transmitter and pressure gauge can be used as auxiliary means.
Source: Neles official manual 7NENP20EN, "PRINCIPLE OF OPERATION" section.
III. Core Technical Data
| Parameter | Description |
| Input signal | Standard 4-20 mA DC (also 0-20 mA); split range 4-12 mA, 12-20 mA; max input resistance 190 ohm |
| Feedback shaft | Max rotation 95 deg; angle-to-signal relationship is linear |
| Air supply | 0.14-0.8 MPa (1.4-8 barg / 20-115 psig); effect of a 10 kPa supply change on output subject to official data |
| Pilot valve / connection | The NE724 corresponds to a 4 mm pilot valve, 1/4 NPT |
| Actuator matching | Swept volume 1.0-8.0 dm3 (e.g. BICU13-BICU20, BIJU10-BIJU16, QP3/QP4 Quadra-Powr, DA/RA to DB/RB diaphragm linear actuators) |
| Air consumption / output | Consumption about 0.9 m3n/h (0.5 scfm), output capacity about 12.0 m3n/h (7.0 scfm), reference supply 0.4 MPa / 4 barg / 60 psig |
| Operating temperature | Standard -25 to +85 deg C; high-temperature construction (H option, Viton diaphragm and seals) -10 to +120 deg C, not included in this order code |
| Ingress / housing | Standard IP54 housing, PG11 conduit; R option IP65 / NEMA 4 and 4X; epoxy-coated anodized aluminum housing, stainless + aluminum internals, NBR diaphragm and seals (standard) |
| Weight | NE700 net weight about 2.3 kg (4.8 lbs); overall dimensions per official dimension drawing |
Source: Neles official manual 7NENP20EN "TECHNICAL DATA" and pilot valve selection table. Individual character differences in printed examples are noted as-is without inference; unlisted items are subject to nameplate / order or official manual.
IV. Option Decoding and Ex Note
| Code | Meaning | Notes / constraints |
| NE724 (base) | NE = electro-pneumatic positioner, 7 = NE700, 2 = 4-20 mA input, 4 = 4 mm pilot valve 1/4 NPT; action position blank = single / double acting universal | Analog proportional, no communication, no diagnostics |
| R | IP65 / NEMA 4 and 4X waterproof / dustproof housing | On the housing protection row; standard is IP54 |
| S1 | VDI/VDE 3845 mounting face with H clamp, supplied with VDI/VDE trunnion when ordered separately | On the mounting row; not for linear actuators (action position A) |
| RS1 (as ordered) | Two-option combination: R + S1 | Per manual "multiple options are entered top-down, S1 must be specified"; RS1 means both waterproof housing and VDI/VDE 3845 mounting |
| A | Linear (globe valve) option, standard stroke 19-57 mm (3/4-2-1/4 in) | Mutually exclusive with S1 (S1 is for rotary mounting face) |
| K / CE01-CE03 | K = supply filter regulator + gauge (5 micron, not for use with HC pilot valve); CE = conduit adapters (PG11 to 1/2 NPT / M20x1.5 / R1/2) | No accessory position in this order code |
Explosion protection must be strictly distinguished: the manual lists ATEX II 2G c construction safety (NP only), ATEX EEx d IIC T4/T5/T6 or FM/CSA Class I, II Div.1 Gr. B-G flameproof (NP only), and IP65 housing options; the NE700 itself is mainly intended for general industry with EEA CE marking, and hazardous-area use must be confirmed item by item against nameplate / certificates. Intrinsic safety Ex ia and flameproof Ex d are not interchanged.
Source: Neles official manual 7NENP20EN "How to Order" and option tables; the RS1 option-combination reading is cross-checked with internal compilations, and the final authority is the nameplate and order confirmation.
V. Applications and Same-Series Comparison
| Model | Type / range | Application |
| NE724 (this article) | 4 mm pilot valve, 1.0-8.0 dm3 | General modulating loops, single control valves, spare-part replacement; small to medium-volume diaphragm / piston actuators |
| NE726 / NE727 | NE726 4-6 mm (8.0-30.0 dm3, consumption 1.2 m3n/h); NE727 6 mm HC (above 30 dm3, consumption 2.1 m3n/h) | Larger swept-volume actuators, not interchangeable with the NE724 4 mm / 1.0-8.0 dm3 |
| NP724 / NP723 | Pure pneumatic, responds to 20-100 kPa (3-15 psig) air signal, NP724 also in the 1.0-8.0 dm3 range | Pneumatic modulating loops without electrical signal, different from the NE724 4-20 mA input |
| NT3000 / external position transmitter | External 4-20 mA position feedback / limit switch | The NE700 body has no position feedback; add externally when a position signal is needed, ordered separately per the actual loop |
Source: Neles official manual 7NENP20EN pilot valve selection table and same-series model comparison; also compiled in the internal document "Neles_NE700_NP700 Technical Data and Model Coding Rules".
VI. Distinction from ND9000 and Selection Guide
| Dimension | NE724 (NE700 series) | ND9206 / ND9300 (ND9000 series) |
| Generation / principle | Analog generation, force-balance proportional | Digital generation, 32-bit microcontroller + non-contact position sensing |
| Input / communication | 4-20 mA, no communication protocol | HART / FF / PA three networks |
| Diagnostics | No diagnostics, valve signature or event log | Device / online / performance / communication / advanced diagnostics and data logging |
| Weight | about 2.3 kg | ND9300 about 8.6 kg (stainless flameproof) |
| Interchangeability | Not interchangeable on the same technical basis; appearance and mounting face may look similar but generation and configuration differ entirely. If diagnostics are needed, consider the NDX retrofit kit (per official manual it can replace NE700 and ND9000), with interface, signal and configuration rechecked |
Selection guide: First confirm this is an analog-generation electro-pneumatic positioner: 4-20 mA input, force-balance principle, no communication and no diagnostics, suited to general modulating loops and spare-part replacement; if the host system needs HART/FF/PA or valve diagnostics, move to ND9000/ND7000 or NDX rather than adding modules to the NE724. Then check the pilot valve: the 4 mm corresponds to a swept volume of 1.0-8.0 dm3; above 8 dm3 use the NE726 (8-30 dm3) or NE727 (above 30 dm3); air supply 0.14-0.8 MPa, ambient -25 to +85 deg C, and confirm action position and mounting (S1 rotary / A linear) against the actuator. Ingress protection (standard IP54 or R option IP65) and hazardous-area approvals must be confirmed item by item against nameplate / certificates.
Common models: This arrival: Neles NE724/RS1 electro-pneumatic valve positioner (NE700 series, RS1 = IP65 housing + VDI/VDE 3845 mounting), an analog-generation unit of a different generation from digital valve controllers such as the ND9206, whose technical data must not be mixed. Parameters come from Neles official manual 7NENP20EN, for selection and spare-part cross-check only, not a guarantee; specific configuration is subject to nameplate / order or official manual, and unlisted items are not invented.
If you are selecting a positioner for a control valve, or want to confirm the NE724 pilot valve size, mounting face and spare-part replacement options, please feel free to contact us. We can check the model and applications together against your actuator volume and signal requirements.
Orders & Inquiries
Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.