Home » Service & Support » Technical Documentation
Neles/Valmet ND9000 Digital Valve Positioners - Technical Data & Selection
Release time:2026-11-21 13:41:01 | Views:

The Neles ND9000 series (formerly Metso, now Valmet Flow Control) is a 32-bit intelligent valve positioner / valve controller for every control valve, using non-contact valve position sensing and supporting three networks - HART, FOUNDATION Fieldbus and Profibus PA - with device-level SIL 2. Based on the official technical bulletin 7ND9021EN, this article covers its core technical data, digit-by-digit model decoding, communication versions and selection points.

I. Product Positioning

ItemDescription
Brand ownershipNeles(TM), under Valmet Flow Control; Metso valve business was spun off as Neles in 2020 and merged into Valmet in 2022, now sold under the Neles brand
SeriesND9000 series intelligent valve positioner / Intelligent Valve Controller
Model coveredND9303HX (4-20 mA + HART, stainless flameproof enclosure, medium-capacity spool, ATEX + IECEx)
Control principle32-bit microcontroller + non-contact valve position sensing, single / double acting, for both linear and rotary valves
CommunicationHART, FOUNDATION Fieldbus (FF), Profibus PA (physical layer all per IEC 61158-2)
Ex / approvalsDevice-level SIL 2; ATEX, IECEx, INMETRO, cCSAus, NEPSI, CCC, etc.; this unit's housing digit 3 is stainless Ex d flameproof
SourceValmet / Neles official technical bulletin 7ND9021EN - 4/2025 (online research)

Data obtained via online search. Source: Valmet official technical bulletin 7ND9021EN - 4/2025 (ND9000 Intelligent Valve Controller), Neles ND9000 official product page (valmet.com). Brand is described by the Metso to Neles / Valmet lineage to avoid confusion with the divested Metso brand.

Neles ND9303HX intelligent valve positioner
Metso ND9303HX intelligent valve positioner (same ND series), for selection reference only

II. Core Technical Data

ParameterDescription
Product nature32-bit microcontroller intelligent valve controller powered by 4-20 mA or fieldbus; non-contact position feedback
Stroke rangeLinear 10-120 mm; rotary 45 deg to 95 deg; feedback shaft free rotation measuring range 110 deg
Air supply1.4-8 bar (20-115 psi); effect of a 10 % inlet pressure change on position subject to official data
Operating temperatureStandard -40 to +85 deg C; Arctic option -53 to +85 deg C; temperature effect on position 0.5 %/10 K
PerformanceDead band at most 0.1 %; hysteresis and vibration resistance per official data sheet
Ingress / housingIP66 / NEMA 4X; ND9300 stainless housing (ND9100 epoxy-coated anodized aluminum + polymer, ND9200 epoxy-coated aluminum + tempered glass, ND9400 stainless + polymer composite)
Mounting interfaceVDI/VDE 3845 mounting face (80x30-20 / 80x30-30 / 130x30-30 / 130x30-50); conduit thread M20x1.5, ND9000E2/U is 1/2 NPT
Net weightND9100 1.8 kg, ND9200 3.4 kg, ND9300 8.6 kg, ND9400 5.6 kg; digit-by-digit outline dimensions not listed
Diagnostics / local interfaceDevice self-diagnostics, online diagnostics, performance diagnostics, communication diagnostics, advanced diagnostics and data logging; LUI supports guided startup, auto / manual linearization calibration, one-point calibration and hot swap

Data obtained via online search. Source: Valmet / Neles official technical bulletin 7ND9021EN - 4/2025 "Detailed Technical Data". Unpublished outline dimensions are subject to nameplate / order or official manual and are not invented.

III. Communication Versions and Electrical Data

Communication versionInput / powerElectrical data (excerpt)
HART (H type here)Loop powered 4-20 mA, minimum signal 3.6 mA, HART 6 or 7 selectableMax current 120 mA; load voltage at most 9.7 VDC at 20 mA (about 485 ohm); max voltage 30 VDC; reverse polarity protection -30 VDC; overcurrent protection above 35 mA
FOUNDATION Fieldbus (FF)Fieldbus powered, 9-32 VDC (reverse polarity protection)Max baseline current 17.2 mA; quiescent current 16 mA; fault current (FDE) 3.9 mA
Profibus PAFieldbus powered, 9-32 VDC (reverse polarity protection)Max baseline current 17.2 mA; quiescent current 16 mA; fault current (FDE) 3.9 mA

All three physical layers comply with IEC 61158-2. When selecting, first fix the communication version by the host system protocol: choose the H type for two-wire 4-20 mA + HART, or the corresponding variant for an FF / PA bus site. The ND9000 natively supports all three protocols, unlike the Emerson FIELDVUE DVC6200 (standard body is HART only, with FF / PA as separate variants).

Data obtained via online search. Source: Valmet / Neles official technical bulletin 7ND9021EN - 4/2025 "Electrical Data" and the Neles ND9000 official product page.

IV. Model Digit-by-Digit Decoding (ND9303HX)

FieldCodeMeaning
SeriesNDIntelligent valve positioner (valve controller)
Digit 19Series 9000, VDI/VDE 3845 mounting face
Digit 23Stainless flameproof Ex d, IP66 / NEMA 4X housing
Digits 3-403Medium-capacity spool (actuator stroke volume 1-3 dm3)
Digit 5H4-20 mA + HART communication
Digit 6XATEX + IECEx hazardous-area approval
Suffix fieldsNot listedTemperature / junction box / special construction / limit switch are generated by the official selection software, subject to nameplate / order or official manual

Data obtained via online search. Source: Valmet official technical bulletin 7ND9021EN - 4/2025 pages 11-12 "How to Order" official coding table. Unpublished fields are not invented.

V. Capacity / Air Consumption and Family Distinctions

ItemDescription
Capacity (4 bar supply)Spool 2 is 5.5 Nm3/h, spool 3 is 12 Nm3/h, spool 6 is 38 Nm3/h
Steady-state air consumptionValues for spools 2&3 at 4 bar are subject to the official bulletin data table
ND9100 / ND9200 / ND9400Same series with different housing / capacity: standard aluminum 1.8 kg, flameproof aluminum 3.4 kg, stainless polymer cover 5.6 kg, forming a housing ladder with the ND9300 (8.6 kg stainless flameproof)
Neles NDXNew-generation modular intelligent valve controller, non-contact magnetic sensing, stem stroke up to 220 mm, graphical LUI, SIL 2 capable (bulletin 7NDX23EN - 2/2026)
Neles NE700 / NP700NE700 electric (electro-pneumatic) positioner (4-20 mA, max input impedance 190 ohm), NP700 pure pneumatic positioner (20-100 kPa)
Neles SG9000 / VG9000SG9000 is an intelligent on/off controller; VG9000 is a SIL 3 safety solenoid valve with partial stroke testing (PST)

Data obtained via online search. Source: Valmet / Neles official technical bulletin 7ND9021EN - 4/2025 and Neles NDX bulletin 7NDX23EN - 2/2026. Unlisted values are subject to official data sheets and are not invented.

VI. Selection Guide and Common Models

Selection guide: First confirm from the order code the housing (ND9303HX digit 3 = stainless Ex d flameproof), spool capacity (03 medium 1-3 dm3), communication (H 4-20 mA + HART) and hazardous-area approval (X ATEX + IECEx); then check air supply 1.4-8 bar, stroke range, operating temperature and ISO 8573-1 air quality. For SIL loops, evaluate against device-level SIL 2 and the complete assembly safety manual, and if limit switches require SIL2/3 use a qualified safety interface. Unpublished suffix fields for temperature / junction box / special construction are subject to nameplate / order or the official selection software. Note that this series is a digital valve controller, a different generation from analog positioners such as the NE700, and the technical data must not be mixed.

Common models: ND9303HX (4-20 mA + HART, stainless flameproof, medium capacity, ATEX + IECEx, this arrival); the same series includes ND9100 / ND9200 / ND9400 housing variants and FF / PA communication variants. The above data comes from online research of the Valmet / Neles official bulletin 7ND9021EN - 4/2025, for selection and spare-part cross-check only, not a guarantee; specific configuration and approval codes are subject to nameplate / order or official manual, and unlisted items are not invented.

If you are selecting an intelligent positioner for a control valve, or want to confirm the ND9000 protocol, flameproof housing and spool capacity configuration, please feel free to contact us. We can check the model and order code together against your actuator volume, protocol requirements and hazardous-area approvals.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.