Home » Service & Support » Technical Documentation
Bifold VBP Series Pneumatic Volume Booster - Technical Data & Selection
Release time:2026-11-21 13:41:01 | Views:

The Bifold VBP series (Bifold Fluidpower, UK, now part of Rotork) is a piston-type pneumatic volume booster that converts a small-flow pilot pressure signal into a 1:1 high-flow output. Its standard body is 316L stainless steel, used to speed up the stroke of large-volume actuators and for fast ESD shutdown. This article covers its technical data, order-code digit structure, selection tables and stainless-steel features, and clarifies the difference between the arrival marking VBP-11-12-V and the official field order.

I. Product Positioning

ItemDescription
BrandBifold (Bifold Fluidpower Ltd, UK; now part of Rotork)
SeriesVBP series piston-type volume booster / booster (Volume Booster)
Arrival markingVBP-11-12-V; purchase record also lists VBP-12-11-V
Product typePure pneumatic volume booster (not an electric positioner, not a filter regulator; the filter booster is a separate version)
Control principleConverts a 2-10 bar g small-flow pilot signal into a 1:1 high-flow output; outlet pressure follows pilot pressure
Standard material316L stainless steel body, 302S26 stainless spring, 18/10 stainless fasteners, Viton main-valve seal
Typical useSpeed up large-volume actuator stroke and fast ESD shutdown (both modulating and on/off pilot signals)
SourceBifold official datasheet "Volume Booster & Filter Booster Range" BFD03/8, Rotork VBP product page (online)

Data obtained via online search. Source: Bifold official datasheet "Bifold Volume Booster & Filter Booster Range" BFD03/8 (bifold.co.uk), Rotork VBP product page (rotork.com). No VBP technical entry is held internally; parameters are subject to the latest official datasheet and nameplate / order.

Bifold VBP-11-12-V pneumatic volume booster
Bifold VBP-11-12-V pneumatic volume booster, for selection reference only

II. Core Technical Data

ParameterDescription
Pressure ratio1:1 (valve pressure to pilot pressure)
AccuracyWithin +/-5 % of pilot pressure
Pilot / output pressure range2-10 bar g
Maximum valve inlet pressure15 bar g (a distributor page lists 20 bar MWP; subject to nameplate / official data sheet)
Pilot port1/4" NPT standard, BSPP / BSPT optional
Gauge portsTwo 1/8" NPT, one plugged as standard (optional 1/4" NPT or BSPP / BSPT)
Operating temperatureViton standard seal -20 to +180 deg C; low-temperature NBR / silicone seal -50 to +40 deg C; sensor head PTFE-encapsulated silicone seal
Applicable mediaAir, natural gas, inert gas, and sour / sweet gas
Approval noteThe datasheet lists SIL 3 third-party certification (IEC 61508 Parts 1 and 2) for the VBP filter booster; the volume booster is a purely pneumatic accessory, not an electrical explosion-proof body; hazardous-area use must be confirmed per system design and product certificate; Ex ia and Ex d are not interchanged

Data obtained via online search. Source: Bifold official datasheet BFD03/8, Rotork VBP product page, cross-checked by a distributor digit-decoding page (radward.co.uk). Unlisted approvals and inlet pressure values are subject to the nameplate / official manual.

III. Working Principle and Flow Capacity

Pilot pressure is applied to sensing port P; the main valve opens so high flow passes from inlet 1 to outlet 2. When outlet pressure equals pilot pressure, the valve enters a fully closed static position; if outlet pressure is high the valve exhausts at high flow, and if low the main valve supplies make-up air, maintaining a 1:1 pressure ratio.

Port size (standard volume booster)Output CvExhaust Cv
1/2"3.23.2
1"11.011.0
2"50.050.0
Port size (filter booster, separate)Output CvExhaust Cv
1/2"9.33.2
1"29.011.0

ESD fast-closing example: the official selection table takes a 50 L actuator set at 5 bar with upstream above 10 bar; a 1" volume booster opens in about 1.2 s and closes in about 2.5 s at 5 bar, with no extra pilot valve or quick-exhaust valve required.

Data obtained via online search. Source: Bifold official datasheet BFD03/8 (Cv tables and ESD selection table); 1-1/2" and 2" sizes are not offered as filter boosters.

IV. Order-Code Structure and Arrival Marking

The official field order is VBP - [port] - [ratio] - [seal] - [option] - [revision]. The arrival marking VBP-11-12-V swaps ratio code 11 with port code 12; the official order form is VBP-12-11-V.

FieldCodeMeaning
SeriesVBPPiston volume booster, standard 316L stainless body
Field 1: port04 / 06 / 08 / 12 / 16 / 24 / 321/4" / 3/8" / 1/2" / 3/4" / 1" / 1-1/2" / 2" NPT
Field 2: ratio11Pilot pressure to valve pressure 1:1
Field 3: sealV / ALV = Viton (standard, -20 to +180 deg C); AL = fluorosilicone (extreme cold)
Fields 4-5: option / revisione.g. -MD-X4MD = manual drain, X4 = 40-50 micron filter element (filter booster); not listed in the arrival marking, subject to nameplate / order
FormatMeaning per official codeConclusion
VBP-12-11-V (purchase record)12 = 3/4" NPT port, 11 = 1:1 ratio, V = Viton sealMatches the official field order; indicates 3/4" NPT, 1:1, Viton, 316L stainless body
VBP-11-12-V (arrival marking)Ratio 11 written before port 12Yields the same configuration by code meaning, but does not follow the official order; confirm with Bifold / Rotork or by nameplate / order

Data obtained via online search. Source: Bifold official datasheet BFD03/8, Rotork VBP product page, distributor digit-decoding page radward.co.uk. The arrival marking versus official order discrepancy must be confirmed by nameplate / order; no other fields are invented.

V. Related Models and Selection Table

ModelDescriptionSource
VBP-12-11-VOfficial field order: 3/4" NPT, 1:1, Viton, 316L stainless; confirm against nameplateBFD03/8 + purchase record
VBP-08-11-V-MD-X41/2" NPT, 1:1, Viton, filter booster with manual drain and 40-50 micron element (Cv 3.6)BFD03/8 + radward.co.uk
VBP-16-11-V / VBP-04 / VBP-32Other sizes in the series: 1" (Cv 11.0), 1/4", 2" (Cv 50.0)BFD03/8
Bifold HIPEX seriesHigh-flow 2/2 exhaust valve, can pair with the VBP for fast ESD dump; 1/2", 1", 2" availableBFD03/8 p.11
ControlAir 600 / 6000 / 6500-6600Other-brand volume booster alternatives; size, Cv and material must be checked item by item, parameters are not interchangeable with the VBPPlease consult for confirmation

Data obtained via online search. Source: Bifold official datasheet BFD03/8, radward.co.uk and bifold.su order-code entries. Different port sizes require rechecking flow and ESD times.

VI. Selection Guide and Common Models

Selection guide: First confirm the function: the VBP is a pure pneumatic volume booster that drives a high-flow output from a small pilot signal, speeding up large-volume actuator stroke and ESD closure, without built-in regulating / filtering (the filter booster is a separate form). Then check the code: port 12 = 3/4" NPT, ratio 11 = 1:1, seal V = Viton (-20 to +180 deg C); for extreme cold choose AL fluorosilicone, and for sour gas confirm the Inconel X-750 spring and material compatibility. Match Cv and open / close times to actuator volume and required stroke time (the 3/4" version has a distributor-listed Cv of about 8.50, to be confirmed with the manufacturer); pilot 2-10 bar g, maximum inlet 15 bar g, accuracy +/-5 %, two 1/8" NPT gauge ports. For hazardous areas confirm SIL 3 and other applicable certificates per system design and product certificate; intrinsic safety and flameproof enclosure must not be mixed. Most importantly, the arrival marking VBP-11-12-V does not match the official field order, so confirm port size and ratio by nameplate / order before ordering or purchasing spares.

Common models: This arrival: BIFOLD VBP series pneumatic volume booster (316L stainless, arrival marking VBP-11-12-V, indicating per official code 3/4" NPT, 1:1, Viton); the purchase record also lists VBP-12-11-V. The above data comes from online-sourced Bifold official datasheet BFD03/8 and Rotork product page, for selection and spare-part cross-check only, not a guarantee; the discrepancy between arrival marking and official field order is subject to nameplate / order, and unlisted items are not invented.

If you are selecting a volume booster for a large-volume actuator, or want to confirm the port size, ratio and seal configuration of the VBP, please feel free to contact us. We can check the model and order code together against your actuator volume, pilot pressure and ESD closing time requirements.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.