The ControlAir 6100-EA belongs to the Type 6100/6200 high-flow pneumatic volume booster series and is the aluminum-bodied model. It is a 1:1 signal / output relay used to increase the stroke speed of large control valves (diaphragm or piston actuators), typically on anti-surge valves. This article organizes its working principle, technical data and model digit decoding per the original ControlAir spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069), and emphasizes that it is a volume booster, not a regulator; items not listed in the spec sheet or not fully transcribed are marked "please consult for confirmation".

I. Product Positioning

ItemDescription
BrandControlAir (US brand)
Series / modelType 6100/6200 high-flow pneumatic volume booster series; model covered: 6100-EA (aluminum body, 3/4" NPT)
Product type1:1 signal / output pneumatic volume booster, NOT a pressure regulator / filter regulator
Core functionAmplifies the low-flow signal from a positioner or I/P converter into a high-flow output, increasing the response speed of large-volume actuators
Typical applicationsAnti-surge valves, high-flow / high-temperature / radiation environments (e.g. nuclear industry); EXIDA certified to IEC 61508 SIL 3 for use in safety instrumented systems (SIS)
ConstructionFixed deadband plus integral adjustable bypass valve; small signal changes do not open the main valve; soft seat design gives tight shutoff at steady state and eliminates leakage
SourceControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069, 6/3/26 version)

The "1:1" of the 6100-EA means output pressure follows signal pressure, but its flow capacity is far greater than the signal source, so it can significantly speed up the charging and exhausting of a large-volume actuator. The essential difference from a regulator is that a regulator targets a set outlet pressure, while a volume booster only follows the signal proportionally and provides high flow; the 6100-EA and Masoneilan BR200 volume boosters must not be selected as regulators.

Source: ControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069); SIL 3 / EAC background is subject to original certificates and order documents, and certificate numbers are not invented here.

ControlAir 6100-EA high-flow pneumatic volume booster
ControlAir 6100-EA product photo, for selection reference only

II. Working Principle: 1:1 High-Flow Volume Booster

StageProcessNotes
Signal inputThe pneumatic signal from a valve positioner or I/P converter enters the signal chamber and acts on one side of the diaphragmSignal port 1/4" NPT; signal pressure 150 psig (10.0 bar) maximum
ComparisonThe diaphragm compares signal pressure with output feedback pressure to develop an error forceFixed deadband prevents the main valve from opening on tiny signal changes, avoiding frequent movement
Amplified outputThe error opens the pilot stage and main valve, sending supply air at high flow to the output port; output pressure follows signal pressure 1:1Supply / output port 3/4" NPT for this model; maximum supply 250 psig (17.0 bar)
Fast exhaustWhen output pressure exceeds signal pressure, the main valve opens the exhaust passage and vents actuator air rapidlyExhaust capacity at 3/4" is 80 scfm (about 2,264 Nl/min)
Bypass and stabilityThe integral adjustable bypass valve tunes dynamic response for stable operation across a wide range of actuator sizesBypass setting should be adjusted on site against actuator volume
Steady shutoffThe soft seat design gives tight shutoff once the system settles, eliminating steady-state leakageLow steady air consumption, suitable for long-term holding applications

Installed between the positioner and the actuator, the 6100-EA "copies" the low-flow positioner output into a high-flow air stream, speeding up stroking and reducing the load on the positioner. For higher flow choose the 6500 / 6600, and for proportional amplification choose Type 600; never use a volume booster as a pressure-regulating element.

Source: construction and principle of Type 6100 / 6200 in ControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069); adjustment methods are subject to the original installation and maintenance manual.

III. Main Technical Data

ParameterValue (6100-EA, 3/4" port)
Signal / output ratio1:1
Supply pressure250 psig (17.0 bar) maximum
Signal pressure150 psig (10.0 bar) maximum
Maximum flow coefficient CvForward 5.0 / exhaust 3.5 (6100 is the 3/4" NPT port column; 1/4" port is forward 2.0 / exhaust 2.5, and 1/2" is forward 4.5 / exhaust 3.5; Cv changes with port size and must not be interchanged)
Exhaust capacity80 scfm (about 2,264 Nl/min)
Temperature rangeStandard -40 to 200 °F (-40 to 93 °C); low-temperature option L: -62 to 194 °F (-52 to 90 °C); extended-temperature option P: -55 to 284 °F (-48 to 140 °C)
PortsSignal port 1/4" NPT; supply / output ports 1/4", 1/2" or 3/4" NPT (3/4" for this model); exhaust port on 6100 is 7/16" or optional 1/4" NPT (option E); two gauge ports 1/4" NPT
MaterialsBody 6100=aluminum (6200=316 stainless); fasteners 6100=zinc-plated steel; other external and internal parts 6100=aluminum; standard elastomer nitrile, low-temperature option=silicone, extended-temperature option=EPDM; optional stainless internal parts (option S, 6100 only)
Output accuracy and deadbandOutput accuracy: 1.0% of a 100 psi output span; deadband figure is not fully transcribed in the collected material, please consult for confirmation
Weight and bias6100 about 2.5 lbs (1.13 kg); 6200 about 5.7 lbs (2.60 kg). Optional negative bias 4 psi (0.3 bar); option Z is -4 +/-1 psi for I/P converter zero reset
Safety approvalIEC 61508 SIL 3 (EXIDA third-party certification, usable in SIS); EAC (GOST) approval system available; option X is ATEX 2014/34/EU explosion protection certification, subject to order confirmation. Specific certificate numbers are subject to original certificates and order documents

Source: Type 6100 / 6200 specification table in ControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069, 6/3/26 version); parameters are not guaranteed values and are subject to the latest original spec sheet, nameplate and order documents, with unlisted items not invented.

IV. Model Digit Decoding and Options

The 6100-EA consists of "series + port code + material code", and this model carries no option suffix (options such as E threaded exhaust, L low temperature and X ATEX must be added separately).

Field6100-EA valueMeaning
Series number6100High-flow pneumatic volume booster series, aluminum body (6200 is 316 stainless)
Port codeESupply / output port 3/4" NPT (B=1/4", D=1/2", E=3/4")
Material codeAAluminum material designation, matched to 6100 (S=316 stainless, matched to 6200)
Option suffixNoneBase model as delivered; E / L / P / S / X / Z must be added at ordering

Option meanings: E=(2) 1/4" NPT threaded exhaust port (6100 only), L=low temperature, P=extended temperature, S=stainless internal parts (6100 only), X=ATEX, Z=negative bias. Mounting brackets and other accessories are ordered under separate part numbers (e.g. P/N 449-542-045) and are not included in the model suffix; the complete order code is subject to nameplate, order or original spec sheet.

Source: model coding and option table in ControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069); part numbers and options are subject to the latest original documents.

V. Related Model Comparison

ModelKey differenceSelection note
6100-BA / 6100-DASame Type 6100 aluminum series with 1/4" NPT (BA) and 1/2" NPT (DA) ports; Cv changes with port (1/4" forward 2.0, 1/2" forward 4.5)Not interchangeable with 6100-EA at 3/4" (forward 5.0)
6200-ES316 stainless model of the Type 6100/6200 series, 3/4" NPT; Cv forward 4.0 / exhaust 4.0, weight 5.7 lbs (2.60 kg)Both material and Cv differ from the aluminum 6100-EA
6100-EA-E6100-EA with option E ((2)1/4" NPT threaded exhaust port)The delivered batch is base 6100-EA without this option; distinguish when ordering
ControlAir 6500 / 6600Large-flow volume boosters, 3/4" or 1" NPT, Cv 8.0 / 9.0, exhaust 150 scfm, also IEC 61508 SIL 3Higher flow tier than the 6100 series, select by duty
ControlAir 6000 / Type 6006000 is a pneumatic volume booster (Cv 6.6 / 6.8, 300 scfm, no SIL); Type 600 is a proportional relay booster (1:1 and 1:2 / 1:3 / 1:6 ratios, Cv 1.0, no SIL)Different positioning from the 6100's 1:1 high flow plus SIL 3
Fisher 2625 / Masoneilan BR200 / BR400Volume boosters from other brands as alternativesNote that BR200 / 6100 are volume boosters, NOT regulators; check Cv, ports and approvals item by item and do not interchange parameters

Source: ControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069); parameters of other brands are subject to their own official data sheets and are not interchangeable.

VI. Selection Guide and Common Models

Selection guide: First set the series by flow and actuator volume: the 6100-EA is a 1:1 high-flow volume booster with 3/4" NPT, Cv forward 5.0 / exhaust 3.5 and exhaust 80 scfm, suited to high-flow diaphragm / piston actuators and anti-surge valves; for higher flow (Cv 8.0 / 9.0, 150 scfm) choose the 6500 / 6600, and for proportional amplification choose Type 600. Then check pressure (supply 250 psig maximum, signal 150 psig maximum), ports (3/4" NPT supply / output and 1/4" NPT signal for this model), materials (6100 aluminum body / nitrile elastomer; for corrosive service choose the 6200 316 stainless or option S stainless internal parts), temperature (standard -40 to 93 °C, option L low temperature, option P extended temperature) and options (E threaded exhaust, Z negative bias, X ATEX). For SIS applications verify IEC 61508 SIL 3 (EXIDA) certification and EAC / ATEX order options. Cv varies with port size, so check against the actual port; the complete order code is subject to nameplate, order or original spec sheet. Red line: a volume booster is not a regulator, and BR200 / 6100 volume boosters must not be selected as regulators.

Common models: ControlAir 6100-EA high-flow pneumatic volume booster (aluminum body, 3/4" NPT, 1:1, Cv forward 5.0 / exhaust 3.5, IEC 61508 SIL 3), strictly distinguished from the 6200 stainless series, the 6500 / 6600 high-flow series and the 6000 / Type 600 non-SIL models. Data comes from ControlAir original spec sheet 6100-6200_SpecSheet.pdf (P/N 441-625-069) and is for selection and spare-part reference only, not guaranteed values; specific configuration and approvals are subject to nameplate, order or original certificates, with unlisted items not invented.

If you are selecting a volume booster for an anti-surge valve or a large-volume actuator, want to verify the Cv, ports and SIL certification of the 6100-EA, or want to clarify its difference from a regulator or the 6200 stainless model, please feel free to contact us. We can check the model and order code together against your actuator volume, signal source and operating conditions.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.