When installing SAMSON 3725 / 3730 series positioners in the field, the appropriate mounting parts, connection blocks, pressure gauge kits and cable glands must be selected according to the actuator type (3277-5 / 3277 / NAMUR / rotary). Based on the official SAMSON installation manual, this article organizes part-number cross-reference tables by mounting scenario, along with feedback lever and pin positions, air connections and precautions, to support spare parts procurement and field assembly.

I. Product Positioning

ItemDescription
BrandSAMSON
Applicable positioners3725 / 3730 series digital electropneumatic positioners (incl. intrinsically safe Ex ia types)
Mounting scenariosDirect on 3277-5 / 3277 actuators, IEC 60534-6 (NAMUR), VDI/VDE 3845 rotary
Accessory categoriesMounting parts, connection / gauge connection blocks, pressure gauge kits, air switching plate, cable glands, feedback lever and pins
Main sourceSAMSON 3725 installation manual EB 8394 ZH (section 4.5, tables 1-5, pp.26-27); data sheet T 8394 EN

The positioner ships standard with feedback lever M (connecting pin at position 35); pressure gauges and connection blocks are selected by mounting method. Note that the threaded ports on the housing are not designed for direct pneumatic connection: the fittings must be installed on the connection plate, gauge connection block or connection block supplied as accessories. All part numbers come from the official manual; procurement and assembly are subject to the latest version.

Source: SAMSON official installation manual EB 8394 ZH (Feb 2012 edition, section 4.5 tables 1-5), data sheet T 8394 EN. Part numbers are subject to the official manual.

SAMSON positioner and mounting accessories
Official product image, for selection reference only

II. Mounting Parts for Direct Integration on 3277-5

For direct integration on 3277-5 actuators of 120 cm2 and below (manual table 1).

Part numberNameApplicationDescription
1402-0239Mounting part3277-5, 120 cm2 and belowBase part for direct positioner mounting
1400-6822Switching plate3277-5xxxxxx.01 actuatorAir switching for fail-safe action (FA / FE)
1400-6820Connection plateFor adding a solenoid valve (e.g. G 1/4)Exports output signal when a solenoid valve is added
1402-0235Connection plate (6)G 1/4 portAir connection block on the positioner, with 2 seals
1402-0236Connection plate (6)1/4 NPT portSame, NPT version
1402-0237Gauge connection plate (7)G 1/4 portBlock with pressure gauge port
1402-0238Gauge connection plate (7)1/4 NPT portSame, NPT version
1400-6950Pressure gauge kit (8)Stainless steel / copperMonitors supply and output pressure
1400-6951Pressure gauge kit (8)All stainless steel, max 6 barOutput / supply gauge for corrosive environments

Installation notes: for a 120 cm2 actuator, first fit the air switching plate (9) according to the fail-safe action (stem extends / retracts), then mount connection plate (6) or gauge block (7) on the positioner, ensuring both seals (6.1) are in place. If a solenoid valve is to be added, plug the internal air passage at the back and use a connection plate to export the output signal.

Source: SAMSON official installation manual EB 8394 ZH, table 1 (direct mounting on 3277-5 actuator).

III. Mounting Parts for Direct Integration on 3277

For direct integration on 3277 actuators of 240 / 350 / 355 / 700 cm2 (manual table 2).

Part numberNameApplicationDescription
1402-0240Mounting part240 / 350 / 355 / 700 cm2 actuatorsBase part for direct positioner mounting
1402-0241Connection plateG 1/4, with seal and screwsAir connection block on the positioner
1402-0242Connection plate1/4 NPT, with seal and screwsSame, NPT version
1400-6950Pressure gauge kitStainless steel / copperMonitors supply and output pressure
1400-6951Pressure gauge kitAll stainless steel, max 6 barOutput / supply gauge

Installation notes: for 240-700 cm2 actuators, signal pressure reaches the diaphragm chamber via connection block (12); the "stem extends" type connects via internal passages in the bracket, while the "stem retracts" type requires an external tube (remove plug 12.2 and fit an external signal line). Pin positions by travel: 240 / 350 cm2 (15 mm travel) keep pin at 35; 355 / 700 cm2 move the pin to position 50.

Source: SAMSON official installation manual EB 8394 ZH, table 2 (direct mounting on 3277 actuator).

IV. NAMUR and Rotary Mounting Parts

NAMUR (IEC 60534-6) mounting corresponds to manual table 3, rotary (VDI/VDE 3845) to table 4.

Part numberNameApplicationDescription
1402-0330NAMUR mounting part (feedback lever pre-installed)Other manufacturers' actuators and 120-700 cm2 Type 3271, travel 3.75-50 mmNAMUR bracket assembly
1402-0243Rotary mounting partVDI/VDE 3845, level 2, 20 mm shaft heightRotary mounting bracket
1402-0244Rotary mounting partVDI/VDE 3845, level 2, 30 mm shaft heightRotary mounting bracket
1402-0294Rotary mounting partVETEC S160 and SAMSON 3278 (160 cm2), level 2Adapter (13) must be fitted first with four screws
1402-0235 / 1402-0236Connection plateG 1/4 / 1/4 NPTCommon air connection plate for rotary / NAMUR
1402-0237 / 1402-0238Gauge connection plateG 1/4 / 1/4 NPTBlock with pressure gauge port
1400-6950 / 1400-6951Pressure gauge kitSS/copper / all SS (max 6 bar)Output / supply pressure monitoring

Installation notes: for NAMUR mounting use bracket (10) and follower plate (3); at mid-travel the transverse slot of the follower plate should be centered in the bracket. For rotary mounting, first confirm the rotation direction, fix feedback lever M with a 5 mm metal pin at the 90-degree position, keep the lever parallel to the long side of the positioner at mid-angle, and finally stick the scale dial with its arrow pointing to the closed position.

Source: SAMSON official installation manual EB 8394 ZH, table 3 (NAMUR mounting), table 4 (rotary mounting).

V. General Accessories and Lever / Pin Positions

Part numberNameSpecification / description
8808-1012Plastic cable glandM20x1.5, blue, cable OD 6-12 mm
8808-1011Plastic cable glandM20x1.5, black (general accessory)
0190-6173 / 0190-6174Brief instructions inside coverGerman (DE) / English (EN), as delivered
Feedback lever MStandard feedback leverShipped with positioner, pin at position 35 as delivered
Feedback lever SShort-travel leverFor NAMUR 120 cm2, 7.5 mm travel (pin at position 17)
MountingActuator / travelFeedback leverPin position
Direct on 3277120 cm2 / 7.5 mmM25
Direct on 3277120 / 240 / 350 cm2 / 15 mmM35
Direct on 3277355 / 700 cm2 / 30 mmM50
NAMUR120 cm2 / 7.5 mm (3.75-10.6 mm)S17
NAMUR120 / 240 / 350 / 700 cm2 / 15 mmM35 / 50
Rotary VDI/VDE 384524 to 100 degreesM90 degrees

Source: SAMSON official installation manual EB 8394 ZH, table 5 (general accessories), travel table. Values are subject to the official manual and are not invented here.

VI. Installation and Selection Precautions

Precautions: 1. Use only the mounting parts / accessories listed in the manual and observe the specified assembly type, paying attention to the combination of feedback lever and pin position. 2. When removing the feedback lever (e.g. with a screwdriver), do not rotate the sensor shaft; move the lever to the mechanical stop, otherwise the internal limit may be damaged. 3. Pneumatic connections must use a connection plate / block; the air supply must be dry, oil-free and dust-free, lines kept as short as possible to reduce signal delay, and all lines blown clean before supply. 4. Electrical connections must comply with EN 60079-14 (electrical installations in hazardous areas); connect according to the assigned terminals, since changing terminal assignments may invalidate explosion protection; intrinsically safe circuits must observe the maximum Ui / Ii / Pi / Li / Ci values in the EC certificate. 5. Static destruction limit is +/-33 V and minimum input current 3.8 mA.

Selection guide: Accessories follow the sequence "define mounting scenario (3277-5 / 3277 / NAMUR / rotary), select mounting part, choose connection / gauge connection plate by port type (G 1/4 or 1/4 NPT), select feedback lever and pin by travel, choose gauge kit material by environment". This table focuses on SAMSON 3725 / 3730 positioners and 3277 actuators; part numbers are from the official manual, and unavailable accessories and the latest order numbers are subject to the official manual / ordering tool and are not invented.

Common combinations: direct on 3277-5 commonly uses 1402-0239 mounting part + 1402-0235 (G 1/4) connection plate + 1400-6950 gauge kit; 3277 (240-700 cm2) uses 1402-0240 + 1402-0241 (G 1/4); NAMUR uses 1402-0330; rotary uses 1402-0243 / 1402-0244; cable gland commonly 8808-1012 (blue).

If you are specifying mounting accessories for a field positioner, or want to check which actuator size a part number fits, please feel free to contact us. We can check the mounting parts list and order numbers together against your actuator model, travel and port type.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.