The SAMSON 3725 is the basic digital electropneumatic positioner in the 3730 family. It uses a two-wire 4-20 mA setpoint, LCD and autotuning, and achieves high positioning accuracy with a non-contact AMR (anisotropic magneto-resistive) position sensor and microprocessor PD control. Mainly intrinsically safe Ex ia with a 10-digit order code, it is simple and cost-effective for applications requiring only 4-20 mA control and intrinsic safety. This article covers its working principle, construction and typical applications.

I. Product Positioning

ItemDescription
BrandSAMSON
Series3725 digital electropneumatic positioner (basic type)
Control principleNon-contact AMR position sensor + analog i/p converter + pneumatic amplifier + microprocessor PD control
Input signal4-20 mA two-wire (reverse polarity protected; HART handheld setup available, no fieldbus)
Hazardous areaIntrinsically safe Ex ia (up to II 2G Ex ia IIC T4), incl. CCC Ex / CSA / EAC approvals; no Ex d
Order code10 digits (explosion protection occupies the first 3, ship approval is digit 8)
Main data sheetsT 8394 EN; installation manual EB 8394 ZH

In the SAMSON positioner family, the 3725 is the "basic digital type": choose the 3725 for 4-20 mA only, intrinsically safe and cost-sensitive applications; the 3730 series for HART / FF / PROFIBUS-PA communication and full diagnostics; the 3730-6 for local pressure monitoring; and the 3731 series for flameproof Ex d. Their order codes have different digit counts and digit tables, which are not interchangeable.

Source: SAMSON official data sheets T 8394 EN, EB 8394 ZH (3725 installation manual), T 8384-x / T 8387-x EN. Parameters are subject to the latest official data.

SAMSON 3725 digital electropneumatic positioner
Official product image, for selection reference only

II. Construction

The 3725 consists of four parts: position sensing, electrical conversion, pneumatic amplification and control electronics, working together to form a closed-loop position control circuit.

ComponentFunction
AMR position sensorNon-contact detection of the stem / feedback lever angle, no mechanical wear, unaffected by ambient conditions and water hammer
Analog i/p converterConverts the control current from the electronics into a pneumatic pressure signal
Pneumatic amplifierAmplifies signal flow and pressure to drive rapid charging / venting of the actuator diaphragm chamber
Microprocessor electronicsRuns the PD control algorithm, compares position with setpoint and outputs the control value; parameters stored in non-volatile EEPROM
LCD and capacitive keysLocal display of position, setpoint, alarms and configuration codes, single-knob / touch-key operation
Feedback lever and pinCouples actuator stem travel to the sensor shaft; standard feedback lever M (pin at position 35)

The 3725 offers self-calibration, automatic adaptation to the valve and actuator (autotune), tight shutoff and continuous zero-point monitoring, with parameters retained in non-volatile EEPROM. It has no fieldbus but supports HART handheld devices for commissioning and parameterization.

Source: SAMSON official data sheets T 8394 EN, EB 8394 ZH. Construction described from official data.

III. Working Principle

The 3725 forms a typical closed-loop position control system. Its working process can be divided into the following steps:

StepProcess
1. Input setpointThe control system outputs a 4-20 mA two-wire signal to terminals 11 (+) / 12 (-) as the position setpoint
2. Position sensingThe AMR sensor non-contact detects the feedback lever angle, obtaining the actual position for the microprocessor
3. Deviation calculationThe microprocessor runs the PD algorithm, comparing actual position with setpoint to compute the control deviation
4. Electrical conversionThe analog i/p converter turns the control current into a pneumatic pressure signal
5. Pneumatic amplificationThe pneumatic amplifier boosts flow and outputs pressure to the actuator diaphragm chamber
6. Position executionThe actuator stem moves the valve stem and feedback lever, producing a new position fed back to the sensor; the loop converges

Before initialization (autotune), the fail-safe action and output air volume must be set, so the positioner can learn the actuator travel and direction. If the input is below 4 mA before initialization, LOW appears on the display; before initialization the fault symbol and S (fail-safe position) are shown, and after initialization code 0 appears and the positioner returns to the last active operating mode.

Source: SAMSON official data sheets T 8394 EN, EB 8394 ZH (circuit diagram Fig.1, startup-setup chapter).

IV. Core Technical Data

ParameterDescription
Input signal4-20 mA two-wire, reverse polarity protected
Split range4 to 11.9 mA and 12.1 to 20 mA
Static destruction limit+/-33 V; minimum current 3.8 mA
Load impedanceup to 6 V (approx. 300 ohms at 20 mA; English data sheet: 6.3 V / 315 ohms)
Travel (direct on 3277)3.75 to 30 mm (English data sheet 5-30 mm)
Travel (IEC 60534-6 / NAMUR)3.75 to 50 mm (English data sheet 5-50 mm)
Travel (Type 3372 / rotary)15 / 30 mm; rotary 24 to 100 degrees
Supply pressure1.4 to 7 bar (20 to 105 psi)
Air qualityISO 8573-1: particles Class 4 / oil Class 3 / pressure dew point Class 3 (or 10 K below minimum ambient)
Output signal pressure0 bar up to maximum supply pressure; software limit approx. 2.4 bar (English: approx. 2.3 bar)
Flow characteristic3 types for globe valves; 9 for rotary valves
Hysteresis / sensitivityat most 0.3 % / at most 0.1 %
Steady air consumptionup to 100 ln/h (supply at most 6 bar, output 0.6 bar)
Ambient temperature-25 to +80 C (Ex versions per EC certificate limits)
Ingress / electrical connectionIP66; 1x M20x1.5 cable gland (6-12 mm cable), terminals 0.2-1.5 mm2
Hazardous areaIntrinsically safe type up to II 2G Ex ia IIC T4

Source: SAMSON official data sheets T 8394 EN, EB 8394 ZH. Values are subject to the official data sheets and are not invented here.

V. Ordering Code and Explosion Protection

A complete 3725 order code is 3725- followed by 10 digits: digits 1-3 are explosion protection (Ex), the only core position normally selected by the customer; digits 4-7 are fixed at 0; digit 8 is ship approval; digits 9-10 are fixed at 0. Hence it is often abbreviated as 3725-XXX. Note that this series is intrinsically safe Ex ia with no flameproof Ex d; Ex ia intrinsic safety is NOT the same as Ex d flameproof enclosure and they must not be confused.

Digits 1-3Approval systemEx markingShort model
000None—3725-000
110ATEX / STCC intrinsic safetyII 2G Ex ia IIC T4 Gb3725-110
112CCC Ex (China)Ex ia II T4 Gb3725-112 (common in projects)
113EAC / GOST (EAEU)I Ex ia IIC T4 Gb X3725-113
116TR CMU 1055 (Turkey)II 2G Ex ia IIC T4 Gb3725-116
130CSA c/us (North America)Ex ia IIC T4; Class I, Zone 0; Div.1 A-D3725-130

Digit 8 ship approval: 0 = none, 1 = Bureau Veritas (BV) type approval (certificate 46564/BO BV, 2022-01-11 to 2027-01-11). Example: 3725-1100000100 indicates ATEX intrinsic safety plus BV ship approval. The older Chinese manual EB 8394 ZH (2012) uses a 13-digit template, different from the current 10-digit / 3-digit Ex code of T 8394 EN; quotation and ordering follow T 8394 EN, and the complete code should be confirmed with the official ordering tool.

Source: SAMSON official data sheet T 8394 EN (Article code matrix), EB 8394 ZH. Explosion protection codes are subject to the official data sheets and certificates.

VI. Applications and Selection Guide

DimensionApplication
Typical media / dutyModulating control of linear globe / single-seat valves and rotary butterfly / ball valves
MountingDirect on SAMSON 3277 / 2780-2 actuators; IEC 60534-6 (NAMUR); Type 3372; VDI/VDE 3845 rotary
Control systemDCS / PLC loops providing a 4-20 mA setpoint, HART handheld setup, no fieldbus
Hazardous areaIntrinsically safe Ex ia applications with ATEX / CCC Ex / CSA / EAC approvals; not for Ex d
Selection boundaryFor HART / FF / PA communication and full features use the 3730 series; for pressure monitoring the 3730-6; for Ex d the 3731 series

Selection guide: The 3725 follows the sequence "define explosion protection approval (digits 1-3), confirm communication (4-20 mA only), select feedback lever / mounting parts by mounting method, verify digit 8 ship approval". The key points: the 3725 is a basic intrinsically safe type with no Ex d and no fieldbus; choose the 3731 series for flameproof and the 3730 series for fieldbus, never interchange digit tables between series. Unavailable certification status and order identifiers are subject to the official manual, nameplate and ordering tool and are not invented.

Common models: 3725-000 (no explosion protection), 3725-110 (ATEX intrinsic safety, widely used), 3725-112 (CCC Ex China, common in projects), 3725-113 (EAC / GOST), 3725-130 (CSA c/us), and 3725-1100000100 with BV ship approval.

If you are selecting an economical intrinsically safe positioner, or want to confirm the 3725 order code digit count and approval options, please feel free to contact us. We can check the model and order code together against your control signal, mounting and area certification requirements.