| SAMSON 3730 / 3731 Positioners - Comparison & Selection | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-21 02:05:02 | Views: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The SAMSON 3730 and 3731 are two positioner families on the same hybrid technology platform (analog PD control plus a microprocessor). The core difference lies in explosion protection: the 3730 series (3730-0 to 3730-5) is mainly intrinsically safe Ex ia with no Ex d, while the 3731 series is the flameproof (Ex d) version of the corresponding 3730 models. Their ordering code structures are independent with different digit counts, so one digit table cannot be applied to both. This article compares them point by point across communication, explosion protection, digit count, data sheets and selection guidance. I. Product Positioning
The 3731 series is built on the same hybrid technology platform as the 3730; the main difference is the flameproof (Ex d) cast aluminum or stainless steel housing, operable locally in hazardous areas via a single-knob menu, for industrial applications requiring flameproof devices. It can be mounted on linear and rotary pneumatic actuators. It must be made clear that the 3731 is the flameproof Ex d series, not the intrinsically safe Ex ia type of the 3730; there is no Ex d anywhere in the 3730-0-5. Source: SAMSON official data sheets T 8384-3/4/5 EN, T 8387-3 EN, T 8387-5 EN and NA 0122; series comparison organized from the official data sheets.
II. Family Members and Communication Comparison
The 3730-4 is the PROFIBUS-PA type (not HART; HART is the 3730-3), a point easily confused during selection. Although the 3730-6 keeps the 3730 prefix, it is a special design with pressure monitoring (14-digit code, T 8384-6 EN) whose data sheet lists a dedicated flameproof Ex d[ja] / Ex db[ja] option (order codes 210 / 211); when flameproof enclosure is explicitly required, prefer the 3731 series designed for Ex d. Source: SAMSON official data sheets T 8384-3/4/5 EN, T 8384-6 EN, T 8387-3/5 EN and T 8394 EN. III. Series 3731 Technical Data
The above data is based on the 3731-3 data sheet T 8387; the 3731-5 is identical on the same platform, differing only in communication and electrical data. Common platform parameters (travel, rotary angle, supply air, accuracy, ingress protection, diagnostics, mounting and functional safety) match the 3730. Specific values are subject to the data sheet of the corresponding model. Source: SAMSON official data sheets T 8387-3 EN, T 8387-5 EN and NA 0122. Values are subject to the official data sheets and are not invented here. IV. 3731-3 vs 3731-5 Comparison
The main differences between the 3731-3 and 3731-5 lie in the communication protocol and power supply: the former is HART (4-20 mA two-wire), the latter is bus-powered FF. Both have a flameproof Ex d housing that may include an Ex ia intrinsically safe option. Note that flameproof Ex d and intrinsically safe Ex ia are two different forms of explosion protection and must not be confused; the specific certification codes are subject to data sheet T 8387 and the nameplate. Source: SAMSON official data sheets T 8387-3 EN and T 8387-5 EN. Explosion protection forms are strictly distinguished and certification codes are subject to the official data sheets. V. Selection Points and Precautions1. Define the explosion protection form first: for a hazardous area requiring a flameproof enclosure, choose the 3731 series; for intrinsically safe Ex ia applications, choose the 3730 series; the two are not interchangeable. 2. Then define the communication protocol: no communication 3730-0/1/2, HART 3730-3 (or flameproof 3731-3), PROFIBUS-PA 3730-4 (not HART), FF 3730-5 (or flameproof 3731-5). 3. Confirm the digit count: 3730 has 16 digits, 3731 has 15, 3730-6 has 14 and 3725 has 10; the digit tables differ and are not interchangeable. 4. Add special functions as needed: for local pressure monitoring see the 3730-6, for SIS applications see the 3730-6 TS / 3731, and add feedback, switches and solenoid valves in the corresponding positions. 5. Write "please consult for confirmation" when unavailable: for area certifications or special options, rely on the official data sheets and ordering tool; do not invent an order code. Although the 3730 and 3731 share the control platform and mounting methods (SAMSON integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845), their ordering code structures are independent. In particular, there is no Ex d in the 3730-0-5 and the 3731 is the flameproof Ex d series; filling in the explosion protection code for a 3731 as if it were the intrinsically safe 3730 is a typical selection error. Source: SAMSON official data sheets T 8384-x, T 8387-x, T 8394 EN and NA 0122; selection boundaries are subject to the official selection manual. VI. Selection Guide & Common ModelsSelection guide: Selection of the 3730 / 3731 follows the sequence "define explosion protection form (intrinsically safe Ex ia or flameproof Ex d), define communication protocol, confirm digit count, add functions as needed, verify the order code". The key points are: the 3731 is the flameproof Ex d series (3731-3 HART / 3731-5 FF), the 3730 series is mainly intrinsically safe Ex ia with no Ex d, and the 3730-4 is the PROFIBUS-PA type rather than HART. For specific digit positions, certification options and suffixes, refer to the SAMSON official selection / ordering tool and data sheets T 8384-x / T 8387-x; when unavailable, write "subject to the official manual" and do not invent an order code. Common models: 3730-3 (HART, widely used), 3730-4 (PROFIBUS-PA), 3730-5 (FF), 3730-0/1/2 (non-communication basic versions), 3730-6 (pressure monitoring, 14 digits); flameproof series 3731-3 (HART), 3731-5 (FF), and the basic 3725. The models have different digit counts and explosion protection coding methods, so their digit tables are not interchangeable. If you are selecting a positioner for a site and want to confirm whether to use the intrinsically safe 3730 or the flameproof 3731, HART or PROFIBUS-PA, or to verify the ordering code digit count, please feel free to contact us. We can check the model and order code together against your area certification, communication protocol and fail-safe requirement. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |

简体中文
ENGLISH
