The Fisher 133H and 1098-EGR are both pressure reducing regulators, but they are based on two different principles. The 133H is a self-operated (direct-acting) gas regulator that uses its own balancing system to hold outlet pressure as inlet pressure changes. The 1098-EGR is a pilot-operated regulator, combining an EGR main valve with a pilot and filter to deliver high accuracy, large body sizes and monitoring configurations. This article compares their construction, pressure ranges, sizes and typical duties point by point and gives practical selection rules.
I. Product Positioning
| Item | 133 series (including 133H) | 1098- / 1098H-EGR |
| Brand | Fisher (Emerson) | Fisher (Emerson) |
| Operating principle | Self-operated / direct-acting | Pilot-operated |
| Construction | Single-port body plus balancing system plus diaphragm, with an external downstream control line; an optional restriction collar reduces capacity | EGR main valve plus P590 series filter plus 6350 series regulator / 61 series pilot / Type Y600AM pilot (61 series with Type 1806 check valve); 1098H uses a high-pressure actuator |
| Typical media | Natural gas and fuel gas for industrial and commercial burners and appliances | Natural gas, fuel gas, plant air and liquids requiring slow main valve travel (about 30 to 90 seconds) |
| Body sizes | 2 in (DN 50) | NPS 1, 2 (DN 25, 50); NPS 3, 4, 6 (DN 80, 100, 150); 8x6, 12x6 (DN 200x150, 300x150) |
| Main manuals | D100270X012 (Form 5007) | D100339X012 (Form 5084, 2016-02) |
The fundamental difference is the operating principle. The 133H needs no external pilot supply, is compact and responds directly, suiting small to medium flows and individual combustion equipment. The 1098-EGR uses a pilot to amplify the control action, enabling higher accuracy, larger body sizes and working monitor or wide-open monitor configurations for distribution stations and large industrial users.
Source: Fisher official manuals D100270X012 and D100339X012.

Official product image, for selection reference only
II. Difference in Working Principle
| Item | 133H (self-operated) | 1098-EGR (pilot-operated) |
| Pressure control chain | Outlet pressure acts directly on the diaphragm against spring force, driving the plug to throttle | Downstream pressure first acts on the pilot, which regulates the loading pressure on the main valve actuator diaphragm; the main valve then throttles |
| External sensing | Requires an external downstream control line | External sensing from a downstream control line, per manual |
| Shutoff characteristic | Single-port construction provides bubble-tight shutoff | Main valve flow characteristic: linear (standard), Whisper Trim or quick opening; capacity depends on the seat and cage combination |
| Response to inlet changes | The balancing system maintains fairly accurate outlet pressure despite inlet pressure variation | Pilot amplification suits large differentials, large bodies and higher accuracy requirements |
| Monitoring | No monitoring configuration listed for this series | Available as working monitor and wide-open monitor configurations |
Source: Fisher official manuals D100270X012 and D100339X012; exact construction and sensing arrangements are subject to manual drawings and order configuration.
III. 133 Series Models and Data
| Model | Outlet pressure range | Maximum inlet pressure | Positioning |
| 133H | 1.5-10 psig | 60 psig (125 psig emergency) | High-pressure type for industrial and commercial burner supply |
| 133HP | 2-60 psig | 150 psig (150 psig emergency) | Extra-high-pressure type with balanced construction and steel body |
| 133L | 2 in w.c. to 2 psig | 60 psig (125 psig emergency) | Low-pressure type |
| 133Z | -1 to 4 in w.c. | 20 psig (125 psig emergency) | Zero / very low pressure regulator |
| Parameter | Specification |
| Body size | 2 in (DN 50) |
| Body material | Cast iron or WCC steel (133HP is steel) |
| End connections | NPT or CL125 FF flange (cast iron) / CL150 RF flange (steel) |
| Orifice material | Aluminum (133H / L / Z) or stainless steel (133HP balanced construction) |
| Diaphragm / seals | Diaphragm of elastomer or stainless steel; O-ring of nitrile (NBR) or fluorocarbon (FKM) |
| Temperature range | -20 to 150 degrees F (-29 to 66 degrees C) |
| Capacity | No separate Cv table published; capacity varies with size and restriction collar, per Fisher Catalog 12 |
Source: Fisher official manual D100270X012 (Form 5007); Cv and capacity per Fisher Catalog 12.
IV. 1098- / 1098H-EGR Models and Data
| Parameter | Specification |
| Main valve body sizes | NPS 1, 2 (DN 25, 50); NPS 3, 4, 6 (DN 80, 100, 150); 8x6, 12x6 (DN 200x150, 300x150) |
| Maximum inlet pressure | 400 psig (27.6 bar) or body rating, whichever is lower |
| Maximum pilot supply pressure | 600 psig (41.4 bar) |
| Outlet pressure ranges | Multiple spring ranges: 4-8 in w.c., 7 in w.c. to 2 psig, 3-20 psig, 5-35 psig, 35-100 psig, 85-200 psig, 200-300 psig, among others |
| Actuator | Type 1098 sizes 30 / 40 / 70 (max control pressure 100 / 75 / 115 psig); Type 1098H size 30 (max control pressure 350 psig / 24.1 bar, emergency case 400 psig) |
| End connections | NPT, CL125 FF, CL250 RF, CL150 / 300 / 600 RF, BWE, SWE, PN 16 / 25 / 40 |
| Flow characteristic | Linear (standard), Whisper Trim, quick opening |
| Elastomer temperature | NBR -20 to 180 degrees F; FKM 0 to 300 degrees F; EPR -20 to 275 degrees F (FFKM option available) |
| Sensing | External sensing from a downstream control line |
| Monitoring | Working monitor and wide-open monitor configurations |
Elastomer trim kits for the 1098-EGR are ordered by NPS (for example the NBR series R63EGX00112 through R63EGX00162), and actuator kits by size 30 / 40 / 70. Orders must include the full 11-digit part number and be confirmed against the nameplate FS number with the Emerson sales office; exact part numbers are subject to the original manual.
Source: Fisher official manual D100339X012 (Form 5084); part numbers and capacity per the original official manual and Fisher Catalog 12.
V. Selection Rules and Applications
| Condition | Preferred choice | Basis |
| Outlet 1.5-10 psig, DN 50, single burner | 133H | Self-operated, bubble-tight shutoff, simple construction for direct burner supply |
| Outlet 2-60 psig with higher inlet pressure | 133HP | Extra-high-pressure type with steel balanced construction |
| Very low or near-zero pressure (in w.c. range) | 133L / 133Z | Dedicated low-pressure and zero-pressure ranges |
| Natural gas distribution, large commercial / industrial users, monitoring required | 1098-EGR | Pilot-operated, large bodies, high accuracy, working / wide-open monitor options |
| High inlet pressure or large differential | 1098H-EGR | High-pressure actuator version, max control pressure 350 psig |
| Plant air or liquids requiring slow valve travel | 1098-EGR | Main valve travel of about 30-90 seconds suits slow-stroke liquid duties |
| High noise or noise reduction requirement | 1098-EGR with Whisper Trim | Whisper Trim cage available on the main valve |
Data obtained via online search. Sources: Fisher official manuals D100270X012 and D100339X012, and Emerson official Fisher regulator product material. Application limits are subject to the official manual.
VI. Selection Guide and Common Models
Selection guide: First divide by operating principle: for a single burner, small to medium flow, DN 50 and outlet 1.5-10 psig, favour the self-operated 133H; for larger bodies, higher accuracy, higher inlet pressure or monitoring, move to the pilot-operated 1098-EGR, and choose the 1098H-EGR for high inlet pressure. Next select the spring range by outlet pressure, the elastomer (NBR / FKM / EPR / FFKM) by medium and temperature, and the end connection by installation (NPT / CL125 FF / CL150 RF / CL250 RF / CL600 RF / BWE / SWE / PN). Then confirm Whisper Trim, external control line, monitoring and slow-travel requirements. Finally check body pressure rating, inlet pressure and differential limits; Cv and part numbers are subject to Fisher Catalog 12 and the official manual. The 133H and 1098-EGR cannot be substituted for each other: the former is a self-operated single-port regulator, the latter a pilot-operated main valve system.
Common models: 133H (self-operated high-pressure type, 1.5-10 psig), 133HP (2-60 psig), 133L (low-pressure type), 133Z (zero-pressure type); 1098-EGR (pilot-operated, multiple body sizes and spring ranges), 1098H-EGR (high-pressure actuator version); matching pilots include the 6350 series, 61 series and Type Y600AM, with P590 series filters.
If you are specifying a regulator for burner fuel supply or a distribution station, or want to compare the 133H and 1098-EGR by outlet pressure, body size and monitoring function, please feel free to contact us. We can check the model, spring range and end connections together against your medium, inlet and outlet pressures and installation conditions.
Orders & Inquiries
Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.