The Fisher FIELDVUE 4400 and the Fisher 4200 series are valve position (positioning signal) transmitters that convert the position of valves, vents, dampers and similar devices into a 4-20 mA feedback signal for indicators, process control systems or PLCs. The 4400 is a digital valve position transmitter with HART communication and linkage-less non-contact feedback, while the 4200 is a potentiometer-based electronic position transmitter discontinued in 2025 and replaced by the 4400. This article summarizes the technical data, model configurations and applications of both generations.

I. Product Positioning

ItemDescription
BrandFisher (Emerson)
SeriesFIELDVUE 4400 digital valve position transmitter; Fisher 4200 series electronic position transmitter
FunctionSenses linear / rotary position and outputs a 4-20 mA feedback signal plus switch position indication
Feedback structure4400: Hall effect and magnet array, linkage-less non-contact; 4200: mechanical potentiometer
Communication4400: HART 7 (superimposed on a two-wire 4-20 mA loop); 4200: 4-20 mA, no digital communication
Main data sheets4400: brochure D104739X0CN (2024-04); 4200: instruction manual D200354X012 (2018-08)

The 4400 uses linkage-less (linkless) non-contact feedback to avoid direct contact between the stem and transmitter, eliminating part wear. A magnet strip must be ordered separately from the transmitter body, and the 4400-specific mounting kit must be used; the 4200 brackets and procedures cannot be reused. The 4200 senses motion through a potentiometer shaft mechanically coupled to the device; all types use a single potentiometer except the 4215, which uses a coaxial dual potentiometer.

Source: Fisher 4400 brochure D104739X0CN (2024-04) and Fisher 4200 instruction manual D200354X012 (2018-08).

Fisher 4400/4200 valve position transmitter
Official product image, for selection reference only

II. FIELDVUE 4400 Technical Data

ParameterSpecification
Input sourceHall-effect sensor and magnet array
Transmitter outputAnalog 4-20 mA DC
Reference accuracy+/-1% (combined effects of hysteresis, linearity and dead band)
Repeatability+/-0.25% of span
Limit switchesTwo solid-state limit switches, 2% of travel range
Sensor refresh rate100 ms / 10 Hz
High/low saturation and alarmsHigh >21.0 mA; low <3.6 mA (per NAMUR NE43)
Digital communicationHART 1200 baud FSK, HART 7
HART impedanceTotal shunt impedance (excluding host/transmitter) 230-600 ohms; Rx 28.06 kohms, Cx 5.84 nF
Recommended power24-30 V DC, 25 mA; reverse polarity protection; minimum compliance voltage 17.75 V DC
Output current limitNot more than 30 mA DC
Environmental conditionsIndoor/outdoor; altitude <= 2000 m; temperature -40 to +80 degrees C; relative humidity 9.2%-90%
Electromagnetic compatibilityEN 61326-1:2013 and EN 61326-3-2:2008
Actuator compatibilityLinear stem travel 6.35 mm (0.25 in) to 606 mm (23.375 in); rotary shaft 45-180 degrees (180 degrees requires a special mounting kit)
Approximate weightTransmitter without mounting bracket approx. 1.8 kg (4 lb)

The 4400 provides Valve Performance Metrics, tracking valve response in both directions and recording cycle count, open/close times, accumulated travel, dwell time, current valve position and travel actuation time with time stamps for troubleshooting. An optional diagnostics monitor reports device status to the host as alarms. With the cover removed, local buttons allow field calibration without tools, cams or potentiometers.

Source: Fisher 4400 brochure D104739X0CN (2024-04); parameters are subject to the official manual.

III. Fisher 4200 Series Technical Data and Configurations

The 4200 series was officially discontinued in 2025 and replaced by the FIELDVUE 4400. Repair kits for installed 4200 units remain orderable; new projects should specify the 4400 directly.

ParameterSpecification
Input signalSingle potentiometer (standard); dual potentiometer (4215 only)
Output signal4-20 mA DC (4210 / 4211 / 4215 / 4220 / 4221)
Reference accuracy+/-1% of output span (combined hysteresis, linearity and dead band)
Repeatability+/-0.25% of span
Output current limit30 mA DC (maximum)
Power requirementTransmitter only 11-30 V DC / 20 mA max; with position switch 20-30 V / 80 mA max; without transmitter position switch 20-30 V / 50 mA max; 24 V DC nominal recommended
Position switch relaysTwo SPDT; contacts rated 5 A at 30 V DC or 120 V AC (resistive); 100,000 operations
Ambient temperatureOperation -40 to 71 degrees C (-40 to 160 degrees F); transport/storage -50 to 80 degrees C
Relative humidity10%-95% (operation and transport/storage)
Enclosure protectionNEMA 4X; CSA Enclosure 4X; IP66
Approximate weightTransmitter without mounting bracket approx. 1.8 kg (4 lb); body approx. 102 x 159 x 51 mm

The 4200 series distinguishes configurations by Type Number: standard travel up to 105 mm (4.125 in) and long travel up to 610 mm (24 in). Types 4210 (transmitter plus electrical position switch), 4211 (transmitter only), 4212 (position switch only) and 4215 (transmitter plus position switch, dual potentiometer) are standard travel; 4220 / 4221 / 4222 are the corresponding long-travel versions. Zero and span limits are subject to Table 3 of the official manual.

Source: Fisher 4200 instruction manual D200354X012 (2018-08); configurations and zero/span limits are subject to Tables 2 and 3 of the original manual.

IV. Approvals and Safety

Item44004200
Functional safetyexida certified per IEC 61508:2010, meeting SIL 2 system integrity requirements—
Hazardous area approvalscCSAus, ATEX, IECEx flameproof etc.; intrinsically safe, Type n and dust options per the product selection tableCSA / FM / ATEX / IECEx: intrinsically safe, flameproof, Type n, dust ignition protection, etc.
Supplementary approval documentsSee product selection tableCSA D104308X012; FM D104309X012; ATEX D104310X012; IECEx D104311X012
OtherEMC/CE, RCM (Australia/New Zealand)CUTR (EAC), KGS (Korea), PESO (India)
Enclosure protectionCSA Type 4X; ATEX IP66; IECEx IP66NEMA 4X; CSA 4X; IP66

Intrinsic safety (Ex ia) and flameproof enclosure (Ex d) are different protection concepts; the specific certification of the 4400/4200 must be confirmed against the nameplate and certificate. When it cannot be found, state "confirm with the manufacturer" and do not infer one protection type from another. The SIL 2 of the 4400 is a device-level capability; SIS use still requires system integrity confirmation.

Source: Fisher 4400 brochure D104739X0CN, Fisher 4200 instruction manual D200354X012 and related hazardous area approval documents; certifications are subject to the official certificates.

V. Applications and Typical Packages

ApplicationDescription
Position feedback to control systemsSends valve position as 4-20 mA to indicators, process control systems or PLCs for position display and interlock decisions
Side-by-side with positionersProvides an independent valve position signal on valves already fitted with DVC positioners, independent of the positioner's internal feedback
Safety instrumented systemsThe 4400 has SIL 2 device capability and switch indication for valve position monitoring in SIS/ESD applications (subject to system requirements)
Non-valve devicesCan sense position of vents, dampers, silencers and similar devices
Linear and rotary serviceThe 4400 handles 6.35-606 mm linear travel and 45-180 degree rotation; the 4200 covers standard/long travel by type

Selection boundary: a valve position transmitter only measures and reports position; it does not drive the actuator. For closed-loop position control, use a positioner or digital valve controller. The 4400 requires a separately ordered magnet strip and a dedicated mounting kit; 4200 brackets cannot be reused. The 4200 is discontinued, so new projects should select the 4400.

Source: Fisher 4400 brochure D104739X0CN and Fisher 4200 instruction manual D200354X012.

VI. Selection Guide & Common Models

Selection guide: First decide the generation by project stage — new projects go directly to the FIELDVUE 4400, while installed 4200 units are maintained by ordering repair kits to the original type. Next select the mounting kit and magnet strip by actuator stroke/rotation (the 4400 requires a separately ordered magnet strip). Then determine output and switch configuration (transmitter only / with switch / switch only), HART communication requirement and site hazardous area certification. Finally verify power, load and HART impedance requirements. The 4400 and 4200 differ in feedback structure, mounting method and ordering model and must not be mixed.

Common models: 4400 digital valve position transmitter (with HART and two solid-state limit switches, select by certification code A/B/C/D/ATEX); 4200 series 4210, 4211, 4212, 4215 (standard travel) and 4220, 4221, 4222 (long travel), with 4215 being the dual-potentiometer type. Common repair parts include control board kits R4210CBX012 (4210/4220), R4211CBX012 (4211/4221), R4212CBX012 (4212/4222), R4215CBX012 (4215), and potentiometer/bushing kits R4210PSX012 and R4220PSX012.

If you need valve position feedback, or want to know how to replace a discontinued 4200 with a 4400, please feel free to contact us. We can check the model, magnet strip and mounting kit together against your stroke/rotation, communication and hazardous area requirements.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.