| Fisher 3570 / 3582i Positioners - Technical Data & Selection | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-21 02:05:02 | Views: | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Fisher 3570 and 3582/3582i belong to the mechanical (electro-pneumatic / pneumatic) positioner family: the 3570 is an electro-pneumatic positioner accepting 4-20 mA, the 3582 is a pneumatic positioner, and the 3582i adds a type 582i electro-pneumatic converter to the 3582 body. They feature linkage feedback and field-adjustable zero and span, and are widely used with Fisher 470/480/490 actuators. This article summarizes their technical data, variants and selection points, with parameters cited to the official manuals. I. Product Positioning
The 3570 accepts a 4-20 mA control signal and drives a pneumatic actuator so valve position is proportional to the signal. The 3582 is a pneumatic positioner, and the 3582i accepts 4-20 mA after adding a type 582i converter to its body. Both match different actuators through field adjustment of zero and span, with a pneumatic output up to the supply pressure. Source: Fisher 3570 electro-pneumatic valve positioner instruction manual D200137X0CN; Fisher 3582/3582i valve positioner instruction manual D200138X012.
II. Fisher 3570 Technical Data
Source: Fisher 3570 electro-pneumatic valve positioner instruction manual D200137X0CN (2022-09 Chinese manual). III. Fisher 3582 / 3582i Technical Data
Source: Fisher 3582/3582i valve positioner instruction manual D200138X012 (2019-09, including English 124114 / Chinese 3582i manual). IV. Model Variants and CodingBoth series distinguish variants by base model plus construction suffixes; selection must match the actuator and functional requirements item by item.
The suffix meanings of the 3570 and 3582 series differ and must not be interchanged; give the complete model when ordering and confirm against the official selection table. If the site uses natural gas, note that the 3582i is not approved for natural gas. Source: Fisher D200137X0CN and D200138X012 manuals, "model coding" sections; complete ordering codes are subject to the official brochure. V. Approvals and Certifications
Intrinsic safety (Ex ia) and flameproof enclosure (Ex d) are different protection concepts; certification must be confirmed against the nameplate and certificate. When it cannot be found, state "confirm with the manufacturer" and do not mix or infer one from the other. Source: Fisher D200137X0CN and D200138X012 manuals, approvals sections; specific certifications are subject to the original certificates. VI. Selection Guide & Common ModelsSelection guide: Choose the series by signal type — 3570 or 3582i for 4-20 mA electro-pneumatic service, 3582 for pure pneumatic signals. Next select the variant by actuator (e.g. 3570/3570C for 470/480, 3570P for 490, 3576/3577 for rotary). Then verify the supply pressure limit, medium (note the 3582i natural gas restriction), temperature range and hazardous area certification. Finally confirm gauge, bypass and tire valve options. Mechanical positioners provide no digital communication or safety certification; for HART/FF/PROFIBUS or SIL applications, move to the FIELDVUE DVC series. Common models: 3570 (for 470/480, widely used), 3570C (high supply pressure), 3570P (for 490), 3576/3577 (rotary); 3582 (with gauge plus bypass), 3582A (no bypass, no gauge), 3582i (electro-pneumatic), 3582NS (nuclear). Related products include the 3610J/3620J rotary positioners and the type 3622 electro-pneumatic converter for rotary actuator packages. If you are specifying a mechanical positioner for an actuator, or want to confirm the 3570 versus 3582i variants, supply pressure and hazardous area options, please feel free to contact us. We can check the model together against your signal type, actuator model and site certification requirements. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||