Home » Service & Support » Technical Documentation
Fisher 3570 / 3582i Positioners - Technical Data & Selection
Release time:2026-11-21 02:05:02 | Views:

The Fisher 3570 and 3582/3582i belong to the mechanical (electro-pneumatic / pneumatic) positioner family: the 3570 is an electro-pneumatic positioner accepting 4-20 mA, the 3582 is a pneumatic positioner, and the 3582i adds a type 582i electro-pneumatic converter to the 3582 body. They feature linkage feedback and field-adjustable zero and span, and are widely used with Fisher 470/480/490 actuators. This article summarizes their technical data, variants and selection points, with parameters cited to the official manuals.

I. Product Positioning

ItemDescription
BrandFisher (Emerson)
SeriesFisher 3570 electro-pneumatic valve positioner; Fisher 3582/3582i valve positioner
ConstructionMechanical positioner with linkage feedback and field-adjustable zero and span
Input signal3570 / 3582i: 4-20 mA DC; 3582: 0.2-1.0 bar / 0.4-2.0 bar pneumatic signal
Supply mediumAir or natural gas (3582i is not approved for natural gas)
Main data sheets3570: D200137X0CN (2022-09 Chinese); 3582/3582i: D200138X012 (2019-09)

The 3570 accepts a 4-20 mA control signal and drives a pneumatic actuator so valve position is proportional to the signal. The 3582 is a pneumatic positioner, and the 3582i accepts 4-20 mA after adding a type 582i converter to its body. Both match different actuators through field adjustment of zero and span, with a pneumatic output up to the supply pressure.

Source: Fisher 3570 electro-pneumatic valve positioner instruction manual D200137X0CN; Fisher 3582/3582i valve positioner instruction manual D200138X012.

Fisher 3570/3582i valve positioner
Official product image, for selection reference only

II. Fisher 3570 Technical Data

ParameterSpecification
Input signal4-20 mA DC (electro-pneumatic type)
Output signal0.2-1.0 bar (3-15 psig) or 0.4-2.0 bar (6-30 psig)
Supply pressureStandard 3.4 bar (50 psig); 3570C / 3570CP max 6.2 bar (90 psig)
Linearity0.2% (of output span)
Hysteresis0.3% (of output span)
Steady-state air consumptionApprox. 0.54 Nm3/h (20 scfh at 6.9 bar)
Process temperature (standard)-34 to 71 degrees C (-30 to 160 degrees F)
Process temperature (high-temperature option)0 to 104 degrees C (32 to 220 degrees F)
Supply mediumAir or natural gas per ISA 7.0.01 / ISO 8573-1 (max 40 micron particles, 5 micron recommended; oil <= 1 ppm)
ConnectionsSupply 3/8 NPT; output 1/4 NPT
WeightApprox. 2.7 kg (6 lb)

Source: Fisher 3570 electro-pneumatic valve positioner instruction manual D200137X0CN (2022-09 Chinese manual).

III. Fisher 3582 / 3582i Technical Data

Parameter3582 (pneumatic)3582i (electro-pneumatic)
Input signal0.2-1.0 bar / 0.4-2.0 bar, or split range4-20 mA DC (max 30 V DC)
Output signalPneumatic pressure to actuator, up to the supply pressure
Supply pressureMax 3.4 bar (50 psig); medium air or natural gas, 3582i is not approved for natural gas
Steady-state air consumption0.38-0.54 Nm3/h0.46-0.64 Nm3/h
Linearity+/-1%+/-2%
Hysteresis0.5%0.6%
Ambient temperature-40 to +71 degrees C; 3582NS -40 to +82 degrees C
Rotation angleDepends on actuator (standard rotary range)
WeightApprox. 2.5 kgApprox. 3.6 kg
ConnectionsSupply/output 1/4-18 NPT; exhaust 3/8-18 NPT; conduit 1/2-14 NPT

Source: Fisher 3582/3582i valve positioner instruction manual D200138X012 (2019-09, including English 124114 / Chinese 3582i manual).

IV. Model Variants and Coding

Both series distinguish variants by base model plus construction suffixes; selection must match the actuator and functional requirements item by item.

SeriesModelDescription
35703570 / 3570CFor Fisher 470 / 480 actuators; C type has a higher supply pressure limit
35703570P / 3570PCFor 490 actuators
35703571For spring-return rotary actuators
35703572 / 3573For 472 / 473 (PDTC) actuators
35703576 / 3577Rotary applications
35823582With gauge plus bypass
35823582ANo bypass, no gauge
35823582C / 3582DTire valve / bypass plus tire valve
35823582GWith gauge, no bypass
35823582NSNuclear service, wider temperature range
35823582iElectro-pneumatic type (3582 body plus type 582i converter)

The suffix meanings of the 3570 and 3582 series differ and must not be interchanged; give the complete model when ordering and confirm against the official selection table. If the site uses natural gas, note that the 3582i is not approved for natural gas.

Source: Fisher D200137X0CN and D200138X012 manuals, "model coding" sections; complete ordering codes are subject to the official brochure.

V. Approvals and Certifications

Item35703582 / 3582i
Hazardous area (positioner body)ATEX II 2 G/D (gas and dust), Ex h IIC Tx Gb / Ex h IIC Tx Db, T4/T5/T6ATEX Zone 2 Group II gas and dust, Ex h IIC Tx Gb / Ex h IIC Tx Db, T4/T5/T6
Electro-pneumatic converter—582i: CSA / FM / ATEX / IECEx intrinsically safe, flameproof and Type n
Enclosure protection—CSA Type 3; FM NEMA 3 / IP54; ATEX IP64; IECEx IP54
Pressure equipmentPED 2014/68/EU Article 4(3) (SEP), CE marked—
Other approvalsANSI/ISA S51.1CUTR (EAC), INMETRO (Brazil), KGS (Korea), NEPSI (China)

Intrinsic safety (Ex ia) and flameproof enclosure (Ex d) are different protection concepts; certification must be confirmed against the nameplate and certificate. When it cannot be found, state "confirm with the manufacturer" and do not mix or infer one from the other.

Source: Fisher D200137X0CN and D200138X012 manuals, approvals sections; specific certifications are subject to the original certificates.

VI. Selection Guide & Common Models

Selection guide: Choose the series by signal type — 3570 or 3582i for 4-20 mA electro-pneumatic service, 3582 for pure pneumatic signals. Next select the variant by actuator (e.g. 3570/3570C for 470/480, 3570P for 490, 3576/3577 for rotary). Then verify the supply pressure limit, medium (note the 3582i natural gas restriction), temperature range and hazardous area certification. Finally confirm gauge, bypass and tire valve options. Mechanical positioners provide no digital communication or safety certification; for HART/FF/PROFIBUS or SIL applications, move to the FIELDVUE DVC series.

Common models: 3570 (for 470/480, widely used), 3570C (high supply pressure), 3570P (for 490), 3576/3577 (rotary); 3582 (with gauge plus bypass), 3582A (no bypass, no gauge), 3582i (electro-pneumatic), 3582NS (nuclear). Related products include the 3610J/3620J rotary positioners and the type 3622 electro-pneumatic converter for rotary actuator packages.

If you are specifying a mechanical positioner for an actuator, or want to confirm the 3570 versus 3582i variants, supply pressure and hazardous area options, please feel free to contact us. We can check the model together against your signal type, actuator model and site certification requirements.

Orders & Inquiries

Baoman Industrial Technology (Chengdu) Co., Ltd
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.