| Fisher DVC6200 Model Code Decoding & Variants (SIS9/H10/FF/PROFIBUS) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Release time:2026-11-21 02:05:02 | Views: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Fisher (Emerson) FIELDVUE DVC6200 digital valve controller is available in three communication variants: DVC6200H (HART), DVC6200F (FOUNDATION Fieldbus) and DVC6200P (PROFIBUS PA), plus the DVC6200 SIS for safety instrumented systems. Its ordering code is grouped into positions, and the diagnostic level at position 9 is not interchangeable across variants. This article decodes the ordering structure position by position and compares the SIS, HART and fieldbus variants, including the boundaries of ODV diagnostics. I. Product Positioning
The DVC6200 is a two-wire smart electropneumatic positioner powered by a 4-20 mA loop with superimposed digital communication. The FF and PROFIBUS PA versions are separate model variants, not a communication option added to the standard body. Its ordering code consists of grouped positions; the complete code should always be confirmed with the Emerson ordering tool. Source: Fisher FIELDVUE DVC6200 instruction manual D103409X012 (Table 1-2 Specifications) and D103605X012. Parameters are subject to the latest official data.
II. Technical Data Overview
Source: Fisher FIELDVUE DVC6200 instruction manual D103409X012, Table 1-2 Specifications. III. Ordering Code Position by PositionThe DVC6200 ordering code is filled in by grouped positions. The general framework is listed below; the available values in each position should be confirmed with the ordering tool and official brochure.
Note also that an older "prefix + suffix" shorthand existed (for example DVC6200-101, DVC6215-205) and is now obsolete. Suffixes 100/101/102 indicate no position feedback (GX housing single-acting, standard housing single-acting, standard housing double-acting respectively), while 203/204/205 indicate the corresponding with-feedback combinations. Prefix DVC6200 denotes standard aluminum, DVC6200S stainless steel and DVC6215 the split remote-mount version. This shorthand should not be used for new orders. Source: Fisher FIELDVUE DVC6200 instruction manual D103409X012 and ordering information; inferred positions should be confirmed with the official ordering tool. IV. Diagnostic Levels and Protocol VariantsPosition 9 (position 6 in some versions) is the diagnostic level and is the most frequently confused area across variants. Core rule: ODV applies only to DVC6200H (HART protocol); DVC6200F and DVC6200P do not offer the ODV diagnostic level. PS applies only to DVC6200F; AD/PD do not apply to DVC6200P.
ODV is the fourth instrument level confirmed by Fisher manual D103605X012, above PD performance diagnostics. Its PST verifies valve movability online during operation, a key function for SIS/ESD applications. When PST is required, specify the ODV diagnostic level on DVC6200H for the HART route, or DVC6200 SIS; on the FF route only the PS diagnostic of DVC6200F is available and ODV must not be assumed. Source: Fisher DVC6200 instruction manual D103409X012 and diagnostic level description D103605X012. V. Variant-by-Variant Comparison
Important: the original bulletin for the standard DVC6200 body (H/F/P) does not declare SIL. When claiming a SIL safety level, refer to the DVC6200 SIS variant rather than treating diagnostic options on the standard body as safety certification. The SIS position differs from the standard H10 position in low-air-consumption relay, temperature range and PST configuration, so the two must be selected against their respective brochures rather than a shared code table. Source: Fisher DVC6200 instruction manual D103409X012, D103605X012 and the DVC6200 SIS brochure. Parameters are subject to the latest official data. VI. Selection Guide & Common ModelsSelection guide: Follow the sequence "protocol and variant first, explosion protection second, housing and supply third, diagnostics and options last". First lock the variant by protocol: DVC6200H/F/P or DVC6200 SIS. Second, fill in the hazardous area code at position 1; intrinsically safe Ex ia and flameproof Ex d are different certifications and are not interchangeable, so confirm with the manufacturer when unclear. Third, determine housing material and supply/actuator. Fourth, select diagnostics by variant: AC/HC/AD/PD/ODV for HART, HCFD(FD)/AD/PD/PS for FF, and the available levels for PROFIBUS PA. Finally add options such as XT, RM and LB, and confirm the complete code with the official ordering tool. Common models: DVC6200H (HART, widely used), DVC6200F (FF), DVC6200P (PROFIBUS PA), DVC6200 SIS (SIL 3 safety version); common diagnostic combinations include HC/AD/PD/ODV (HART) and PS (FF); common options include LB low-air-consumption relay, XT extreme temperature, RM remote mount (DVC6205 + DVC6215) and H7 HART 7 upgrade. If you have a DVC6200 ordering code you would like decoded, or need to decide between HART, FF, PROFIBUS PA and SIS versions for a valve, please send it to us. We can check the variant and each position together against your protocol, certification and diagnostic requirements. Orders & InquiriesBaoman Industrial Technology (Chengdu) Co., LtdTel: +86 028-60220547 | Email: info@bit-cd.com Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry. |