Fisher 4211NS Position Transmitter - Arrival & Data
Baoman Industrial Technology (Chengdu) Co., Ltd. has recently received the Emerson Fisher 4211NS position transmitter. The 4211 belongs to the Fisher (the brand now belongs to Emerson) 4200 series of electronic position transmitters; a potentiometer shaft is mechanically coupled to linear or rotary actuators, dampers or other devices to sense position, and a standard 4-20 mA signal is sent to indicators, process control systems or PLCs. Reference accuracy is ±1% of output span, it can be mounted on linear or rotary valve actuators, and the enclosure is rated NEMA 4X / IP66. The 4200 series was discontinued in 2025 and replaced by the FIELDVUE 4400 digital position transmitter, but repair kits for installed units remain orderable. The 4211 differs from the 4210 / 4215 / 4220 / 4221 in stroke and configuration, and is also distinct from the integral position-transmitter option of FIELDVUE DVC positioners; specifications must not be interchanged. The specifications below are taken from the Fisher official instruction manual and product catalogue recorded in the knowledge base, for selection and spare-part verification.
I. Arrival Photos

Arrival photo (taken by Baoman Industrial, watermarked, serial information redacted)

Arrival and unboxing detail (taken by Baoman Industrial)

Arrival and unboxing detail (taken by Baoman Industrial)

Arrival and unboxing detail (taken by Baoman Industrial)
II. Brand & Model
| Item | Specification |
|---|---|
| Brand | FISHER (now part of Emerson) |
| Model | 4211NS (4200 series electronic position transmitter) |
| Positioning | Standalone valve-position feedback instrument: converts the mechanical position of linear / rotary actuators or devices into a standard 4-20 mA signal for indicators, process control systems or PLCs; available in three configurations (transmitter only / transmitter with high-low position switches / high-low position switches only) |
| Coordination with positioners | The positioner receives the control signal and drives valve position, while the 4211 converts the actual valve position into an independent 4-20 mA feedback; together they form a valve-position control plus feedback loop. This is a different implementation from the integral 4-20 mA position-transmitter option inside FIELDVUE DVC smart positioners and must not be equated with it |
| Arrival designation | The arrival note states 4211NS; the NS suffix is not explicitly defined in the available official documents, so the ordering configuration (stroke / switches / certifications) is subject to the nameplate / purchase order and no value is assumed |
| Source status | The knowledge-base document 'Fisher 4400 / 4200 Technical Data' is compiled from two original PDFs - the 4400 product catalogue and the 4200 instruction manual; specifications and certifications follow the originals, and the 4200 does not provide a complete ordering-code tree |
III. Technical Data
The specifications below are taken from the knowledge-base document 'Fisher 4400 / 4200 Technical Data' (entry_id c43303a12a6b4206a7509bf95f45fbfa), compiled from two original Fisher PDFs - the 4400 digital position transmitter product catalogue and the 4200 series position transmitter instruction manual; output signal, accuracy, power supply, temperature, certifications and ordering codes are transcribed from the originals. Items not listed in the manual (such as the definition of the NS suffix and item-by-item dimensions) are flagged honestly and are subject to the nameplate / purchase order or the official manual, with no values assumed.
| Item | Specification |
|---|---|
| Working principle | The potentiometer shaft is mechanically coupled to the sensed device; standard versions use a single potentiometer as position input (the 4215 uses a concentric dual potentiometer for additional electrical isolation between the transmitter and switch circuits); long-stroke versions use a multi-turn potentiometer with a travel sensor assembly to sense actuator pushrod linear motion |
| Output signal | 4-20 mA DC (4210 / 4211 / 4215 / 4220 / 4221); output current limit 30 mA DC (maximum) |
| Reference accuracy / repeatability | Reference accuracy ±1% of output span (combined effects of hysteresis, linearity and dead band); repeatability ±0.25% of span |
| Available configurations | Transmitter only; transmitter with integrated high / low position switches; or high / low position switches only. Refer to the nameplate and model table for the specific type |
| Power requirements | Transmitter only 11-30 V DC / 20 mA max; transmitter with position switch 20-30 V / 80 mA max; position switch only 20-30 V / 50 mA max; 24 V DC nominal recommended |
| Position switches | Two SPDT high / low position switch relays, ON/OFF status; contacts rated 5 A at 30 V DC or 120 V AC (resistive); rated life 100,000 operations, and 50,000 operations at 10 A surge lamp / motor loads |
| Stroke range (4211) | Potentiometer rotation: zero 0 to 90°, span 15 to 90°; linear stroke: zero position 1-1/4 in or below, travel 0 to 51 mm (min 8, max 51 mm), i.e. 0 to 2 in (min 0.315, max 2 in); see manual Table 3 |
| Installation | Can be mounted on linear or rotary valve actuators, or other devices; after installation the potentiometer shaft is mechanically coupled to the device to sense motion |
| Ambient temperature / humidity / effects | Operating -40 to 71 °C (-40 to 160 °F); transport / storage -50 to 80 °C (-60 to 180 °F); relative humidity 10% to 95%; per 38 °C (100 °F) ambient change zero drift max ±0.5% and span drift max ±0.75%; supply variation causes output change < ±0.1% |
| Enclosure rating | NEMA 4X; CSA Enclosure 4X; IP66 |
| EMC (4211 / 4221) | Complies with EN 61326-1:2013; immunity per industrial location Table 2, emissions Class A; ISM equipment Group 1, Class A |
| Electrical classification / certifications | CSA: intrinsically safe, explosionproof, dust ignitionproof; FM: intrinsically safe, explosionproof, dust ignitionproof, nonincendive; ATEX: intrinsically safe, n-type, flameproof; IECEx: intrinsically safe, n-type, flameproof. Also CUTR, KGS and PESO. Supplementary hazardous-area documents: CSA D104308X012, FM D104309X012, ATEX D104310X012, IECEx D104311X012 |
| Approximate weight and spares | Transmitter without mounting bracket approx. 1.8 kg (4 lb); control board repair kit R4211CBX012 (4211 / 4221), potentiometer / bushing repair kit R4210PSX012 (4210 / 4211); the transmitter serial number must be provided when ordering |
| Product status | The 4200 series was formally discontinued in 2025 and replaced by the FIELDVUE 4400 digital position transmitter; new projects should select the 4400 directly, while repair kits for installed 4200 units remain orderable |
Sources: the knowledge-base document 'Fisher 4400 / 4200 Technical Data' (entry_id c43303a12a6b4206a7509bf95f45fbfa, Product Materials space), based on two original Fisher PDFs - the 4400 product catalogue and the 4200 series instruction manual; corroborated by the 'FISHER Price Sheet' (entry_id a78472b6753c40c880dc74736808fae0), which lists 'position transmitter 4211', and the 'Actual Procurement Cost Record up to 2026-05-31' (entry_id 666b58c007d14314b19751831e12a61e), which records a 2026-05-21 'Fisher 4211 position transmitter' purchase entry, confirming the product category. The definition of the NS suffix in the arrival note was not found in the available documents and is not assumed.
IV. Related Models
| Item | Specification |
|---|---|
| Fisher 4210 / 4212 / 4215 / 4220 / 4221 / 4222 | Sibling models in the 4200 series, all with 4-20 mA output; 4210/4211 cover 0 to 2 in linear stroke, 4212/4215 cover 0 to 4.125 in, and 4220/4221 cover 0 to 12 / 0 to 24 in via converters; the 4215 uses a concentric dual potentiometer and repair kits are model-specific, so specifications must not be interchanged |
| FIELDVUE 4400 | Fisher digital position transmitter that replaces the discontinued 4200 series; hazardous-area certification codes A (EMC/CE), B (cCSAus), C (IECEx), D (RCM) and ATEX, mounts on linear or rotary actuators, and is recommended directly for new projects |
| Integral position transmitter of FIELDVUE DVC7K / DVC series | An optional integral 4-20 mA position transmitter inside the positioner (isolated output, 11-30 V DC, reference accuracy 1% of stroke span, compliant with NAMUR NE43); a different implementation from the standalone 4200/4211 and must not be equated with it |
| Fisher 4200 discontinuation / replacement | The knowledge-base 'FISHER Discontinued Products Replacement Table' records that the 4200 series position transmitter was discontinued in 2025 and replaced by the 4400; repair kits for installed 4200 units remain orderable (entry_id 455429c44759455c90cbe2ff7034557c) |
| YTC / SAMSON position transmitters | Alternative position transmitters from other brands (e.g. YTC SPTM-5V/6V/65V and the SAMSON positioner 4-20 mA feedback option), compiled in the knowledge-base document 'YTC Position Transmitter Selection Rules and Technical Data'; select by output signal, accuracy and mounting method item by item |
V. Selection Guide & Common Models
Selection guide:Selection starts with the function: the 4211 is a standalone position transmitter that converts the actual valve position of a linear / rotary actuator into 4-20 mA feedback, paired with a positioner to form a control plus feedback loop; if integrated feedback inside the positioner is required, choose the integral position-transmitter option of a FIELDVUE DVC or the 4400 instead. Then check the stroke (4211: 0 to 51 mm / 0 to 2 in, zero position 1-1/4 in or below, span 15 to 90°), 4-20 mA output, load impedance, power supply (transmitter only 11-30 V DC), ±1% accuracy, ±0.25% repeatability, whether high / low SPDT switches are needed, ambient -40 to 71 °C, NEMA 4X / IP66 enclosure, and the required certifications (CSA / FM / ATEX / IECEx - intrinsically safe is not the same as flameproof, to be confirmed by zone classification). The NS suffix in the arrival note and the discontinued status of the 4200 series should be confirmed with Emerson; the serial number is required when ordering and repair kits are model-specific. Please feel free to inquire for an item-by-item check against your stroke and feedback requirements.
Common models:This arrival: the Emerson Fisher 4211NS electronic valve position transmitter (4200 series, 4-20 mA output). Parameters come from the Fisher official 4400 product catalogue and 4200 instruction manual recorded in the knowledge base, for selection and spare-part verification only, not guaranteed values; the NS suffix in the arrival note and the ordering configuration are subject to the nameplate / purchase order or the official manual, the 4200 series has been discontinued and replaced by the 4400, and items not listed in the available materials are not assumed.
These are some of the configurations we supply regularly. If you are working through a selection, or would like to know about availability of these models, feel free to get in touch — we can look at the right combination together based on your operating conditions.
Disclaimer: The information above is not guaranteed to remain valid and may be modified without separate notice. Please confirm the latest information at the time of inquiry.
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文