Fisher DLC3020f Digital Displacer Level Controller - Arrival & Data
Baoman Industrial Technology (Chengdu) Co., Ltd. has recently received the Fisher FIELDVUE DLC3020f digital displacer level controller (the arrival note marks DLC3020F). The DLC3020f belongs to the Fisher FIELDVUE line (the brand now belongs to Emerson) and is based on displacer/torque-tube technology; it measures level and liquid-liquid interface and can derive fluid density through temperature compensation. The same hardware can be configured as a transmitter, a controller or a switch, and mounts directly on 249 series displacer sensors. Its output is FOUNDATION Fieldbus digital communication with no separate 4-20 mA analog output, which differs from the DLC3010 (discontinued in 2022, replaced by the DLC3100) and the current DLC3100 (4-20 mA + HART); these must not be interchanged. The original arrival text also mentioned the DLC3010, which this page distinguishes. The specifications below are taken from the original Fisher document "DLC3020f Digital Level Controller Instruction Manual" D103434X012 recorded in the knowledge base, for selection and spare-part verification only.
I. Arrival Photos

Arrival photo (taken by Baoman Industrial, watermarked, serial information redacted)

Arrival and unboxing detail (taken by Baoman Industrial)

Arrival and unboxing detail (taken by Baoman Industrial)
II. Brand & Model
| Item | Specification |
|---|---|
| Brand | FISHER (now part of Emerson); the DLC3020f belongs to its FIELDVUE digital instrumentation line |
| Model | DLC3020f / DLC3020F digital displacer level controller (Digital Displacer Level Controller), Fieldbus version |
| Positioning | Based on a 249 displacer/torque-tube sensor and electronics, combining transmitter, controller and switch functions in one unit for level, liquid-liquid interface and density measurement; mounts directly on a 249 displacer sensor or, via an adapter, on other displacer-type sensors |
| Difference from DLC3010 | The DLC3010 is an older-generation digital level controller mounted on Fisher 249 displacer cages; it was discontinued in 2022 with the DLC3100 as the recommended replacement. The DLC3020f is an active FOUNDATION Fieldbus digital controller with different output/communication and protocol; the two must not be interchanged |
| Arrival designation | The arrival text marks DLC3020F and also mentions DLC3010; this page treats the photographed DLC3020f as the subject. The ordering configuration (Fieldbus protocol, 249 sensor configuration, certifications, options) is subject to the nameplate / purchase order |
| Source status | The knowledge base contains a Chinese technical compilation based on the original Fisher manual D103434X012; the manual documents only the FOUNDATION Fieldbus version (HART/PROFIBUS are replaced objects, not the native protocol), and the ordering-code table is in Bulletin 11.2 D103433X012; no complete ordering code is assumed here |
III. Technical Data
The specifications below are taken from the original Fisher document "DLC3020f Digital Level Controller Instruction Manual", document no. D103434X012 (English; product-family overview in Product Bulletin D103219X012). Hazardous-area certification categories are from Table 1-2 of that manual; detailed ordering codes and the selection worksheet are in Bulletin 11.2 D103433X012, and the supplied Quick Start Guide is D103470X012. Items not listed in the manual (such as specific Ex marks or SIL classification) are flagged honestly and are subject to the nameplate, purchase order or the official manual, with no values assumed.
| Item | Specification |
|---|---|
| Measurement principle and functions | Displacer buoyancy change -> torque-tube shaft rotation -> electronics digitization; configurable as transmitter, controller or switch (three-in-one); used for level and liquid-liquid interface measurement, with density derived through temperature compensation |
| Measurement / range | Level or interface: displacer length 0-100% (standard displacer 14-120 in, type 249 14/32 in); density: displacement force change 0-100% |
| Output signal / communication | FOUNDATION Fieldbus digital communication (PV output over the fieldbus); no separate 4-20 mA analog output (HART/PROFIBUS are replaced objects, not the native protocol) |
| Input signal and temperature compensation | Torque-tube shaft rotational movement; optional 2/3-wire 100 Ohm platinum RTD process temperature compensation |
| Power supply | 9-32 V DC, 17.7 mA, non-polarized |
| Accuracy | +/-0.15%; independent linearity +/-0.1% of span; repeatability <0.1% FS; hysteresis <0.10% of span; dead band <0.05% of input span |
| Minimum differential specific gravity | 0.1 SGU (with a standard-volume displacer) |
| Process temperature | Depends on the matched 249 sensor material: cast iron -29 to 232 C; steel -29 to 427 C; stainless steel / Monel -198 to 427 C |
| Ambient temperature | Operating -40 to 80 C; transport/storage -40 to 85 C |
| Enclosure and hazardous-area certification | CSA Type 4X; FM NEMA 4X / IP66; ATEX / IECEx IP66. The certification manual Table 1-2 lists intrinsically safe (Ex i), explosion-proof (Ex d), Div 2, non-incendive and dust-ignition-proof categories; specific Ex marks (class / temperature group) are not given in the manual and are in the supplied Quick Start Guide D103470X012. Intrinsically safe and explosion-proof are different certification categories and must not be interchanged; SIL, NEPSI/GB, UKEx, KGS, INMETRO, CUTR and CE are not listed in the manual |
| Wetted materials | Standard displacer 304 stainless steel; options include 316 stainless steel, N10276, N04400, plastic and special alloys (the body does not directly contact the process fluid) |
| Electrical connections | Two 1/2-14 NPT internal conduit connections (M20 adapter available) |
| Weight and EMC | Weight < 2.7 kg (6 lbs); EMC compliant with EN 61326-1:2013 and EN 61326-2-3:2006 |
Sources: the knowledge-base document "FISHER Level Instrument Overview" (entry_id 8d2f32f7d7f34efc9a891f8c2d93d5cb, Product Materials space), based primarily on the original Fisher document "DLC3020f Digital Level Controller Instruction Manual" D103434X012, with reference to Product Bulletin D103219X012 (product-family overview), Bulletin 11.2 D103433X012 (ordering codes) and Quick Start Guide D103470X012 (detailed Ex marks). The DLC3010 discontinuation information is additionally from the knowledge-base document "FISHER Discontinued / Restricted Products Cross-Reference" (entry_id 455429c44759455c90cbe2ff7034557c, based on the discontinued-products PDF, 2025-12): item 194 "DLC3010 Digital level controller for mounting on Fisher 249 displacer cages, discontinued 2022, recommended replacement DLC3100". The two sources corroborate each other; items not listed in the available documents are flagged honestly, with no values assumed.
IV. Related Models
| Item | Specification |
|---|---|
| DLC3010 | An older-generation digital level controller mounted on Fisher 249 displacer cages; discontinued in 2022 with the DLC3100 as the recommended replacement. It was mentioned in the original arrival text and differs from the DLC3020f (Fieldbus) on this page; the two must not be interchanged (per the knowledge-base discontinued-products cross-reference) |
| DLC3100 / DLC3100 SIS | The current digital level transmitter: displacer -> torque tube -> Hall effect -> 4-20 mA + HART (HART 5/7), with temperature compensation; the SIS version carries a safety-instrumented-system classification for safety-related duties. Its HART output differs from the DLC3020f's Fieldbus output (manual D104213X0CN) |
| 249 series displacer sensors | The mounting base for the DLC3020f, available in caged and cageless forms, pressure classes CL125 to CL2500 and multiple materials; accuracy and process-temperature limits depend on the matched 249 sensor (manuals D200099X012 and others) |
| 2500 series pneumatic controllers / transmitters | Pneumatic types paired with a 249 displacer, outputting 3-15 / 6-30 psig, in proportional, proportional-plus-reset, switch and transmitter variants; a different technology path from the digital DLC3020f (manuals D200124X012, D200037X012) |
| L2 series level controllers | The L2/L2e/L2sj/L2t cover pneumatic, electric-contact, low-emission and digital 4-20 mA + HART versions for different energy and emission requirements; in-series alternatives to the Fieldbus type on this page (manual D103032X012 and others) |
| 2390 / 2390B level transmitter | An earlier level transmitter discontinued in 2000 with the DLC3100 as the recommended replacement; a different generation from the DLC3020f (per the knowledge-base discontinued-products cross-reference) |
V. Selection Guide & Common Models
Selection guide:Selection starts with the function and protocol: the DLC3020f is a FOUNDATION Fieldbus digital level controller with no separate 4-20 mA, combining transmitter, controller and switch functions; if 4-20 mA + HART is required, choose the DLC3100 (or the DLC3100 SIS for safety-related duties), and do not confuse the DLC3010 with the DLC3020f. Then check against the vessel conditions: measurement type (level/interface/density), displacer length (standard 14-120 in), process temperature (per the 249 material), ambient temperature, enclosure and hazardous-area certification (specific Ex marks in Quick Start Guide D103470X012; intrinsically safe and explosion-proof must not be interchanged), wetted materials and electrical connections, and verify the ordering code against Bulletin 11.2 D103433X012. A complete selection = DLC3020f body + 249 sensor configuration + options + certification; items not listed in the manual are subject to the nameplate, purchase order or the official manual. Please feel free to inquire for an item-by-item check against your conditions and protocol.
Common models:This arrival: the Fisher FIELDVUE DLC3020f digital displacer level controller (arrival note marks DLC3020F); the original arrival text also mentioned the DLC3010, and this page explains the difference between the two. Parameters come from the Fisher manual D103434X012 and the discontinued-products cross-reference recorded in the knowledge base, for selection and spare-part verification only, not guaranteed values. The specific configuration is subject to the nameplate, purchase order or the official manual, and items not listed are not assumed.
These are some of the configurations we supply regularly. If you are working through a selection, or would like to know about availability of these models, feel free to get in touch — we can look at the right combination together based on your operating conditions.
Disclaimer: The information above is not guaranteed to remain valid and may be modified without separate notice. Please confirm the latest information at the time of inquiry.
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文
ENGLISH
