Flowserve Logix 3820 Digital Valve Positioner - Arrival & Data
Baoman Industrial Technology (Chengdu) Co., Ltd. has recently received a Flowserve Logix 3820-47EA-D43R-0110 digital valve positioner. Flowserve's current digital valve positioner line is the Logix series (1500 / 3200MD / 3400MD / 520MD+ / 3800, etc.); the PMV brand, formerly part of Flowserve, was divested to Amberjack in 2026, so PMV D3/D20/D30 and other PMV models should no longer be recommended when a Flowserve positioner is requested — selection should stay within the Logix series. According to the model numbering rules in the knowledge-base document "Flowserve Smart Valve Positioner — Technical Parameters and Model Coding Rules (Five-Model Edition)", 38 = Logix 3800 series, 2 = HART communication and 0 = aluminum intrinsically safe (IS) housing, so the 3820 corresponds to the HART, aluminum IS version of the Logix 3800 series. The specific configuration codes of this arrival, 3820-47EA-D43R-0110, are subject to the nameplate / purchase order or the latest Flowserve manual. The technical parameters below are organized from the Logix 3800 section of the knowledge base.
I. Arrival Photos

Arrival photo (taken by Baoman Industrial, watermarked, serial information redacted)

Arrival and unboxing detail (taken by Baoman Industrial)

Arrival and unboxing detail (taken by Baoman Industrial)

Arrival and unboxing detail (taken by Baoman Industrial)
II. Brand & Model
| Item | Specification |
|---|---|
| Brand | Flowserve |
| Model | Logix 3820-47EA-D43R-0110 (Logix 3800 series, HART version) |
| Model positioning | Per the manual coding rules: 38 = Logix 3800 series, 2 = HART, 0 = aluminum intrinsically safe (IS) housing; the 3820 corresponds to the HART aluminum IS version of the 3800 series, with the specific configuration subject to the nameplate / purchase order |
| Product type | Digital electro-pneumatic valve positioner for both linear and rotary actuators |
| Communication | HART (manual footnote: HART 6 standard, field-configurable to HART 7); Foundation Fieldbus also available in the 3800 series |
| Action | Single-acting / double-acting; four-way double-acting and three-way single-acting |
| Brand note | Flowserve's current positioners are the Logix series; PMV was divested to Amberjack in 2026, so PMV D3/D20/D30 and other models are not recommended |
III. Technical Data
The Logix 3800 is a modular digital valve positioner compatible with both linear and rotary valves/actuators, directly mountable to VDI/VDE standards without external pneumatic tubing. Most valves complete automatic zero, span and gain calibration in under 60 seconds. Five pressure sensors enable predictive diagnostics of supply pressure, packing friction, air-line leakage, fail-safe position deviation and hysteresis. A knowledge-base business clarification notes that certification codes 14 and 52 have identical certification capability and that this digit only determines the nameplate style (the note appears in the Logix 1500 model rules); the specific certification code of this 3820 is subject to the nameplate / purchase order, and no certification level is assumed.
| Item | Specification |
|---|---|
| Model positioning | Logix 3800 series digital valve positioner; per the coding rules 38 = base series, 2 = HART, 0 = aluminum IS housing, so the 3820 corresponds to the HART aluminum IS version of the 3800 series; specific configuration subject to the nameplate / purchase order |
| Communication | HART (manual footnote: HART 6 standard, field-configurable to HART 7); Foundation Fieldbus also available in the 3800 series |
| Action | Single / double-acting; four-way double-acting and three-way single-acting; compatible with linear and rotary valves/actuators |
| Microprocessor | 32-bit; cold-start recovery 500 ms |
| Electrical | Compliance voltage / current 10 VDC @ 20 mA / 3.6 mA; equivalent resistance 500 Ω @ 20 mA |
| Double-acting performance | Resolution ≤0.25%, linearity ±0.80%, repeatability ≤0.5%, hysteresis ≤1.0%, deadband ≤0.1%, sensitivity ≤0.25%, stability ≤0.4% |
| Single-acting performance | Resolution ≤0.25%, linearity ±0.45%, repeatability ≤0.5%, hysteresis ≤0.35%, deadband ≤0.3%, sensitivity ≤0.25%, stability ≤0.2% |
| Air delivery | Double-acting 18 SCFM@60psi (Cv 0.47); double-acting low-bleed 18 SCFM (Cv 0.47); single-acting 12 SCFM (Cv 0.32) |
| Air consumption | Double-acting 0.3, double-acting low-bleed 0.075, single-acting 0.15 SCFM @60psi |
| Operating temperature | -55 to +85 °C; single-acting relay -40 to +85 °C |
| Protection and housing | IP66; housing in aluminum (intrinsically safe IS / explosion-proof Ex d) or stainless steel (Ex d, marine grade optional) |
| Diagnostics | Five pressure sensors for predictive diagnostics: supply pressure, packing friction, air-line leakage, fail-safe position deviation and hysteresis; standard and Pro diagnostic levels |
| Safety and certifications | ATEX, IECEx, FM/CSA explosion-proof / intrinsically safe / non-incendive; SIL 3 (double-acting HART version only); Ex d IIC |
| Mounting and calibration | Direct mounting to VDI/VDE 3845/3847 standards with no external pneumatic tubing; most valves complete zero, span and gain auto-calibration in <60 seconds |
Source: the knowledge base (Baoman Industrial) document "Flowserve Smart Valve Positioner — Technical Parameters and Model Coding Rules (Five-Model Edition)", Logix 3800 section; the original manufacturer document "Logix™ 3800 Digital Positioner" AIBR000110-05 (EN/A4, 2026-04) and the archived official LOGIX3800 PDF in the knowledge base (including the Logix 3800 positioner configurations selection table). The business clarifications (14/52 differing only in nameplate style; the PMV divestiture) come from knowledge-base business notices rather than the original manual; please reconfirm with Flowserve before quoting or bidding. The specific configuration of this arrival, 3820-47EA-D43R-0110, is subject to the nameplate / purchase order, and no values are assumed.
IV. Related Models
| Item | Specification |
|---|---|
| Logix 3800 series, HART version (this 3820) | This arrival is the 3820-47EA-D43R-0110; parameters follow the Logix 3800 section, with the specific configuration subject to the nameplate / purchase order |
| Logix 3800 series, FF version (ordering code 4) | Code 2 at digit 2 = Foundation Fieldbus version, different communication protocol from the 3820 (digit 2 = 2, HART) |
| Logix 3200MD | Two-wire 4-20 mA + HART, single/double-acting, linear/rotary universal, rich multi-brand retrofit kits; the discontinued 3200IQ is replaced by the 3200MD |
| Logix 520MD+ (incl. 510+) | HART (520MD+) / pure analog (510+), multifunction card AO/DO/DI expansion; the discontinued 520MD is replaced by the 520MD+ |
| Logix 1500 | Single-acting economy model, 4-20 mA / HART 7, one-touch Quick-Cal; certification codes 14 and 52 at digit 4 have identical capability and differ only in nameplate style |
| Logix 3400MD | Foundation Fieldbus loop-powered, two-stage positioning, standard/advanced/Pro diagnostic levels |
| PMV (not recommended) | PMV was divested to Amberjack in 2026; when a Flowserve positioner is requested, always switch to the Logix series and do not recommend PMV D3/D20/D30 |
V. Selection Guide & Common Models
Selection guide:Selection starts with communication and protocol: for HART choose the 3820 (digit 2 = 2); for Foundation Fieldbus choose the 3800 FF version (digit 2 = 4). Then confirm action (four-way double-acting / three-way single-acting), medium (air / natural gas, with low-bleed relay L for natural gas), housing and certification (general purpose 14, ATEX/IECEx 28/37, FM 34/45, etc., subject to the nameplate / purchase order), diagnostic level (standard / Pro) and mounting (standard / direct block / VDI/VDE 3847 manifold / remote mount). SIL 3 applies only to the double-acting HART version. Flowserve positioners should always be selected within the Logix series and PMV is not recommended. If further comparison of the specific configuration codes, certification level or alternative models for the 3820-47EA-D43R-0110 is needed, it can be confirmed against the site conditions and nameplate information.
Common models:This arrival: Flowserve Logix 3820-47EA-D43R-0110 digital valve positioner (Logix 3800 series, HART version). Parameters are extracted from Flowserve original materials summarized in the knowledge base; the specific configuration, certification level and ordering codes are subject to the nameplate / purchase order and the latest Flowserve manual. Different certification / material combinations may be restricted to specific options, and no unlisted values are assumed.
These are some of the configurations we supply regularly. If you are working through a selection, or would like to know about availability of these models, feel free to get in touch — we can look at the right combination together based on your operating conditions.
Disclaimer: The information above is not guaranteed to remain valid and may be modified without separate notice. Please confirm the latest information at the time of inquiry.
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文