Fisher 1098-EGR Pressure Regulator - Arrival & Technical Data
In-stock arrival photos: Emerson Fisher 1098-EGR pressure reducing regulator, a pilot-operated design built around a main valve plus pilot, commonly used for natural-gas transmission and industrial fuel-gas pressure reduction. The specifications below were verified against the official manual and internal technical compilation recorded in the knowledge base, for selection and spare-part reference.
I. Arrival Photos

Arrival photo (taken by Baoman Industrial, watermarked, serial information redacted)

Arrival and unboxing detail (taken by Baoman Industrial)
II. Brand & Model
| Item | Specification |
|---|---|
| Brand | Emerson / Fisher |
| Model | 1098-EGR (high-pressure actuator version: 1098H-EGR) |
| Product type | Economical, precise pilot-operated pressure reducing regulator |
| Construction | Type EGR main valve + standard P590 series filter + Type 6350 regulator / Series 61 pilot / Type Y600AM pilot (Series 61 pilot with Type 1806 check valve) |
| Typical applications | Natural-gas transmission; fuel gas to industrial boilers, furnaces, ovens and mixers; large commercial/institutional buildings; plant air; liquid service requiring slow main-valve travel (approx. 30–90 seconds) |
| Manual reference | D100339X012, Form 5084 (February 2016) |
III. Technical Data
The specifications below are extracted from the Fisher official Instruction Manual for Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators (D100339X012, Form 5084, February 2016) and the knowledge-base technical compilation. The 1098-EGR is a pilot-operated design and belongs to a different product line from direct-operated instrument-supply regulators such as the 67C/67CFR/67D, and from the C/EZR and 912 series. Items not listed in the manual or for which no authoritative official source was found are explicitly marked as not listed in the available materials and are subject to the nameplate / purchase order or the official manual; no values are assumed.
| Item | Specification |
|---|---|
| Product type | Pilot-operated pressure reducing regulator; the 1098H-EGR is the high-pressure actuator version |
| Construction | Type EGR main valve + P590 series filter + Type 6350 regulator / Series 61 pilot / Type Y600AM pilot (Series 61 pilot with Type 1806 check valve) |
| Main valve body sizes | NPS 1, 2 (DN 25, 50); NPS 3, 4, 6 (DN 80, 100, 150); 8×6, 12×6 (DN 200×150, 300×150) |
| End connections | Depending on body / material: NPT, CL125 FF, CL250 RF, CL150/300/600 RF, BWE, SWE, PN 16/25/40 |
| Maximum inlet pressure | Main valve 400 psig (27.6 bar) or the body rating, whichever is lower |
| Maximum pilot supply pressure | 600 psig (41.4 bar) |
| Outlet pressure ranges | Multiple spring ranges, see manual Table 2: e.g. 4–8 in w.c., 7 in w.c.–2 psig, 3–20 psig, 5–35 psig, 35–100 psig, 85–200 psig, 200–300 psig |
| Actuator | Type 1098 sizes 30/40/70 (maximum control pressure 100/75/115 psig); Type 1098H size 30 (maximum control pressure 350 psig / 24.1 bar, emergency case 400 psig) |
| Main valve flow characteristic | Linear (standard), Whisper Trim, quick opening |
| Pressure registration | External (downstream control line) |
| Applicable media | Natural gas, fuel gas, plant air, liquids (slow-travel service) |
| Temperature and elastomers | No single temperature limit given in the manual (depends on construction/elastomer); elastomers NBR −20 to 180 °F, FKM 0 to 300 °F, EPR −20 to 275 °F (FFKM also available) |
| Body and trim materials | Body cast iron / steel / WCC (NACE); trim 316/416 stainless steel, CF8M; spring pressure classes 20/60/125/400 psi (colour-coded yellow/green/blue/red) |
| Cv / weight / certifications | Cv not published separately by Emerson (main-valve + pilot construction; capacity varies with cage/seat combination, see Fisher Catalog 12); weight and specific PED/CE, UL, ATEX, SIL declarations are not listed in the available materials and are subject to the nameplate / purchase order or the official manual |
Knowledge-base document Technical Parameter Supplement 01 — Regulators / Pressure Reducers (General and Gas), item 119 Fisher Types 1098- and 1098H-EGR Pressure Reducers, plus the parts and in-depth parameter sections. Original basis: official Instruction Manual Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators, D100339X012, Form 5084 (February 2016); manual mirrors at manualmachine.com / manualslib.com. Items not in the manual or noted in the internal compilation as lacking authoritative official sources are flagged accordingly, with no assumptions made.
IV. Related Models
| Item | Specification |
|---|---|
| 1098H-EGR | High-pressure actuator version of the 1098-EGR, size 30, maximum control pressure 350 psig / 24.1 bar, emergency case 400 psig |
| Series 61 pilot | Used with pilot-operated regulators such as the 1098-EGR and EZL; loads the actuator diaphragm by reducing inlet pressure to drive the main valve |
| Type EGR main valve | The main valve body of the 1098-EGR, combined with a P590 series filter and a Type 6350 regulator / Series 61 / Y600AM pilot |
| P590 series filter | Filter series included in the standard 1098-EGR configuration |
| Type 6350 regulator / Type Y600AM pilot | Optional 1098-EGR components that combine with the EGR main valve to form a complete pressure-reducing station |
V. Selection Guide & Common Models
Selection guide:When selecting a 1098-EGR, first confirm the medium (natural gas / fuel gas / plant air / liquid), maximum inlet pressure and required outlet pressure range, body size and end connection, and whether a working-monitor or wide-open-monitor configuration is needed. Spare trim should be verified with Emerson using the nameplate FS number and the complete 11-digit part number. If you need a line-by-line comparison of the outlet ranges and differential pressures in manual Tables 2 and 4, or advice on matching pilots and filters, please continue browsing our technical materials and arrival photos for this series; we will help organise the selection points for your operating conditions.
Common models:The specifications on this page are compiled from Fisher official manuals and knowledge-base technical materials and are for selection reference only. Items not listed in the manual or marked as not listed in the available materials are subject to the equipment nameplate, purchase order or the original official manual. The actual supplied model, configuration and certifications are subject to the delivered unit and Emerson factory documents; this page does not constitute a purchase commitment or technical warranty.
These are some of the configurations we supply regularly. If you are working through a selection, or would like to know about availability of these models, feel free to get in touch — we can look at the right combination together based on your operating conditions.
Disclaimer: The information above is not guaranteed to remain valid and may be modified without separate notice. Please confirm the latest information at the time of inquiry.
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文