ASCO 141 Series Redundant Control System 8141A6108G127H1 - Arrival
Baoman Industrial Technology (Chengdu) Co., Ltd. has recently received an ASCO Series 141 Advanced Redundant Control System (ARCS) 8141A6108G127H1; the arrival information identifies its constituents as WSJE-M12L 24DC and X55150616600300 solenoid valves. The ARCS is a redundant pneumatic tripping device designed as a component in safety instrumented systems (SIS), using 1oo2 / 2oo2 / 2oo3 voting solenoids with a fault-tolerant architecture, high diagnostic coverage and automated online testing to greatly reduce spurious trip rates; it is suitable for SIL 3 applications. No dedicated technical document exists in the knowledge base, so the parameters below are taken from the official Emerson / ASCO product page and the ARCS Series 141 Installation & Maintenance Instructions, for technical documentation and reference.
I. Arrival Photos

Arrival photo (taken by Baoman Industrial, watermarked, serial information redacted)

Arrival and unboxing detail (taken by Baoman Industrial)

Arrival and unboxing detail (taken by Baoman Industrial)
II. Brand & Model
| Item | Specification |
|---|---|
| Brand | ASCO (a brand of Emerson) |
| Model | 8141A6108G127H1 (Series 141 ARCS advanced redundant control system) |
| Arrival-identified constituents | WSJE-M12L 24DC and X55150616600300 solenoid valves; this constituent note comes from the arrival information and is not corroborated item by item by the official manual — subject to the nameplate / purchase order |
| Product positioning | A redundant pneumatic tripping device used as a component in safety instrumented systems (SIS), controlling the pilot air signal to a process valve actuator; no single point of failure can cause an unwanted closure of the process valve |
| Redundancy architecture | 1oo2 / 2oo2 / 2oo3 voting solenoids (two or four electrically actuated solenoid valves, V1–V4) |
| Safety level | Suitable for SIL 3 applications; the ASCO Series 327 3/2-way direct-acting solenoid valves on the ARCS manifold are exida-certified SIL 3 capable |
| Construction features | Integrated manifold module with single inlet / single outlet and direct valve-to-valve design eliminating pipework and fittings; factory pre-tested under a single part number; optional individual isolation valves / common bypass allow online maintenance without process interruption |
| Materials | SS316L valve body and manifold, SS316L and aluminium solenoid operators; all-stainless-steel or aluminium constructions also available |
III. Technical Data
The parameters below are taken verbatim from the official Emerson / ASCO "ASCO Series RCS / 141 Redundant Control System" product page and the "Advanced Redundant Control System (ARCS) Direct Acting Platform Series 141 Installation & Maintenance Instructions" (IM-IND-536985-RevAA-sec1, E290699-01/2019). The knowledge base contains only a purchasing record (purchased at 15,500 CNY, in stock) and no technical materials. Items not listed in the official materials are marked "not listed in the available materials; subject to the nameplate / purchase order or the official manual", and no values are assumed.
| Item | Specification |
|---|---|
| Arrived model / voltage | 8141A6108G127H1; the purchasing record notes 24 VDC (subject to the nameplate / purchase order) |
| Product type | Solenoid-operated pneumatic redundant tripping system (Solenoid - Air Pilot actuation) |
| Voting architecture | 1oo2 / 2oo2 / 2oo3 voting solenoids; redundant valves in 2oo2 or 2oo3 configuration (Normally Closed or Normally Open) |
| System composition | Two or four electrically actuated solenoid valves (V1–V4) plus a pneumatically operated (manually controlled) bypass or isolation valve, visual indicators and pressure switches (providing solenoid state feedback for online testing) |
| Operating principle | When energized, air is supplied to the actuator through the Process port. On a trip, the incoming pneumatic signal is blocked and the Process port is connected to the Exhaust port, venting the actuator so its return spring moves the process valve to its fail-safe position |
| Manifold architecture / mode | Normally Closed manifold; de-energized to trip |
| System voltage | 12 VDC, 24 VDC, 48 VDC, 120 VDC, 120/60-110/60 VAC or 230/50-240/50 VAC (24 VDC for this batch) |
| Differential pressure / maximum viscosity | 0/1 - 10 bar (1 bar = 100 kPa); maximum viscosity 65 cSt (mm²/s) |
| Response time | 75 - 100 ms |
| Fluid / air requirement | Dry, non-lubricated air; filtered (5 micron) instrument air recommended; media: air and inert gas |
| Temperature range / seal material | -20°C to +60°C; seal material FPM |
| Valve configuration | Pneumatic valve: 3/2 solenoid-operated valve; bypass valve: 5/2 manually operated valve; isolation valve: 3/2 manually operated valve |
| Ports / flow / maximum pressure | Ports 1/4″ and 1/2″ NPT; flow 2.0–3.0 Cv (typical Process-to-Exhaust Cv in Normally Closed constructions); maximum operating pressure vacuum to 150 PSIG |
| Indication / feedback / protection | Visual indicators: red = air not available, green = air available; pressure switches: SPDT, steel, galvanised; optional pressure gauge; IP65 and ATEX ratings; suitable for corrosive, hazardous, indoor and outdoor environments |
The data were obtained via online search. Sources: (1) the official Emerson product page "ASCO Series RCS Redundant Control System", https://www.emerson.com/en-hu/catalog/asco-rcs-en-gb (voting architecture, flow, voltage, pressure, materials, IP65/ATEX); (2) the official Emerson "Advanced Redundant Control System (ARCS) Direct Acting Platform Series 141 Installation & Maintenance Instructions", document No. IM-IND-536985-RevAA-sec1 / E290699-01/2019 (system composition, mode of operation, voltages, differential pressure, viscosity, response time, temperature, seals, valve configuration, indication and pressure switches); (3) the Chinese brochure "Series 141 Advanced Redundant Control System (ARCS)", document No. FL000108ZHCN-02_11-22. The model 8141A6108G127H1 and the constituent-valve note appear only in the knowledge-base purchasing record and are not listed item by item in the official manual; they are subject to the nameplate / purchase order. Items not listed in the available materials are not assumed.
IV. Related Models
| Item | Specification |
|---|---|
| ASCO Series 327 | The 3/2-way direct-acting solenoid valves mounted on the ARCS manifold, exida-certified SIL 3 capable with advanced diagnostic capability |
| Other ASCO Series RCS configurations | Same redundant control system platform, with body materials available in aluminium, engineered plastics and stainless steel; media air / inert gas, NPT ports |
| Voting architecture comparison | 1oo2 favours availability, 2oo2 favours safety, and 2oo3 balances both; selection must follow SIS safety requirements and tolerance to spurious trips |
| Constituent note | The arrival-identified WSJE-M12L 24DC and X55150616600300 must be checked against the official ordering code of 8141A6108G127H1 before being used as a spare-part basis |
V. Selection Guide & Common Models
Selection guide:Selection starts with defining the voting architecture (1oo2 / 2oo2 / 2oo3) and normally closed / normally open form according to the SIS integrity requirement, then determining the ordering code from actuator supply pressure, port size (1/4″ or 1/2″ NPT), response time and site voltage (24 VDC for this batch). Whether individual isolation valves / common bypass, visual indicators, pressure switches or GO Switch feedback are required should be confirmed item by item against online maintenance and diagnostic needs. Constituents and the specific configuration are subject to the nameplate / purchase order or the official manual. Please feel free to inquire for an item-by-item check against your safety loop and operating conditions.
Common models:This arrival: ASCO Series 141 Advanced Redundant Control System (ARCS) 8141A6108G127H1 (24 VDC). Parameters are taken from the official Emerson / ASCO product page and the ARCS Series 141 Installation & Maintenance Instructions, for technical documentation and spare-part verification only and not as guaranteed values. The arrival-identified constituents and items not listed in the available materials are subject to the nameplate / purchase order or the official manual; no values are assumed.
These are some of the configurations we supply regularly. If you are working through a selection, or would like to know about availability of these models, feel free to get in touch — we can look at the right combination together based on your operating conditions.
Disclaimer: The information above is not guaranteed to remain valid and may be modified without separate notice. Please confirm the latest information at the time of inquiry.
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China