Home » Products » Samson
SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data

SAMSON 3731-5 Ex d FOUNDATION Fieldbus Positioner - Technical Data

Details

1. Product Overview

The SAMSON 3731-5 is an Ex d flameproof FF intelligent electro-pneumatic valve positioner in the 3731 family. It shares a hybrid technology platform with the 3730 series but uses a flameproof (Ex d / Flameproof) cast-aluminum or stainless-steel enclosure, allowing local operation via a single-knob menu in hazardous areas. It uses FOUNDATION™ Fieldbus communication, is bus-powered, and features LCD display, autotune and EXPERTplus diagnostics. The complete ordering code is 15 digits, based on the separate data sheet T 8387-5 EN.

SAMSON 3731-5 Ex d flameproof FF positioner official product image
SAMSON 3731-5 positioner official product image (official image, for selection reference only)

Arrival Photos (taken by Baoman Industrial)

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

2. Technical Description

Flameproof construction: Uses an Ex d flameproof enclosure (cast aluminum or stainless steel), which may include Ex ia intrinsically safe options; degree of protection IP66 / NEMA 4X, weight approximately 2.5 kg. Suitable for Zone 1 hazardous area applications requiring a flameproof enclosure and using FF fieldbus.

Bus communication: Complies with FOUNDATION Fieldbus (IEC 61158-2), bus-powered. Intrinsically safe Ex ia (IIC) bus electrical parameters: Ui=24 V, Ii=380 mA, Pi=1.04 W (Pi=2.58 W for IIB), Ci=5 nF, Li=10 µH. Integrates 1×PID, 1×AO, 1×DI (or floating), 2×DI function blocks, with a 180°-rotatable alphanumeric LCD and EXPERTplus diagnostics.

Ordering code structure: Complete ordering number = 3731-5 + 15 digits, with the 1st digit being the "version/communication digit" (5 = FF). Compared with the 3731-3, the 3731-5 is bus-powered and therefore has no "fail-action" digit, uses 3 digits for explosion protection, and offers a more streamlined option set (no position transmitter 01, no binary output 06). See Section 4 digit by digit.

Explosion-protection positioning: The 3731 series is mainly flameproof Ex d (the 3731-5 on this page = Ex d FF), not an intrinsically safe type. If the application only requires an intrinsically safe Ex ia FF positioner, consider the 3730-5.

3. Key Technical Data

ItemDescription
Communication protocolFOUNDATION™ Fieldbus (IEC 61158-2), bus-powered
Integrated function blocks1×PID, 1×AO, 1×DI (or floating), 2×DI
Bus electrical (Ex ia IIC)Ui=24 V, Ii=380 mA, Pi=1.04 W; Ci=5 nF, Li=10 µH
Supply air pressure1.4-7 bar (depending on version)
Travel rangeDirect 3277: 3.6-30 mm; IEC 60534-6-1 bracket: 3.6-300 mm; rotary: 24°-100°
AccuracyHysteresis ≤0.3%; sensitivity ≤0.1%; flow characteristic deviation ≤1%
Degree of protectionIP66 / NEMA 4X
Type of explosion protectionEx d flameproof (cast aluminum or stainless steel enclosure), may include Ex ia intrinsically safe options
Electrical connection2×1/2 NPT or optional 2×M20×1.5; terminals 2.5 mm²
Self-diagnosticsEXPERT / EXPERTplus (including PST), NE107 status
Ambient temperature-40 ~ +80 °C (certificate limits apply separately)
Ordering code length15 digits (separate data sheet T 8387-5 EN)
Functional safetyIEC 61508: SIL 2 (single) / SIL 3 (redundant)
Source: SAMSON official data sheets T 8387-5 EN, NA 0122; explosion-protection parameters subject to the certificate.

4. Selection Guide (Complete Ordering Code)

Complete ordering number = 3731-5 + 15 digits, with the version digit fixed at 5. The table below lists the available codes and meanings digit by digit:

PositionFieldAvailable codes / Meaning
1Communication/version digit5 = FOUNDATION™ Fieldbus version (with LCD, autotune)
2-4Explosion protection (3 digits)210 = ATEX II 2G Ex db IIC T6 Gb (incl. Ex db eb / Ex db[ia] / Ex ia; II 2D Ex tb IIIC T80°C Db IP66); 230 = CSA/FM; 270 = JIS Ex d IIC T6 (other certifications such as EAC per data sheet)
5-6Options (2 digits)00 = none; 03 = binary input; 05 = forced venting. Note: no option 01 position transmitter, no 06 binary output
7Diagnostics4 = EXPERTplus (control valve expert diagnostics, including partial stroke test PST)
8Electrical connection thread1 = 2×M20×1.5; 2 = 2×1/2 NPT
9-11Explosion certification (3 digits)211 = CCC Ex / NEPSI; 212 = IECEx; 213 = EAC Ex; 215 = KCS; 216 = INMETRO; 217 = TR CMU 1055
12Special application0 = none; 1 = paint-compatible version
13-15Special version000 = none
Source: SAMSON official data sheet T 8387-5 EN, Article code table. Final codes are subject to confirmation by the official selection/ordering tool.

5. Complete Model Enumeration

The following are verified examples of complete 15-digit ordering codes for the 3731-5 with digit-by-digit breakdown:

Complete ordering codeDigit-by-digit breakdown / Meaning
3731-521000412110000Version 5 (FF) · explosion protection 210 (ATEX Ex db flameproof) · options 00 (no additions) · diagnostics 4 (EXPERTplus) · electrical interface 1 (M20×1.5) · certification 211 (CCC / NEPSI) · special application 0 (none) · special version 000 (none)
3731-521003412110000Version 5 (FF) · explosion protection 210 (ATEX Ex db) · options 03 (binary input) · diagnostics 4 · interface 1 (M20×1.5) · certification 211 · application 0 · version 000
3731-521000422110000Version 5 (FF) · explosion protection 210 (ATEX Ex db) · options 00 · diagnostics 4 · interface 2 (2×1/2 NPT) · certification 211 · application 0 · version 000

Note: The initial item has been verified against official T 8387-5 EN; the other two are combination illustrations based on the digit table in Section 4 (only the "options" and "electrical interface" digits are replaced); please consult us for confirmation for formal orders. Note that the 3731-5 has no fail-action digit, which differs from the code structure of the 3731-3.

6. Related Models

Related modelType / Application
3731-3Ex d flameproof HART type (15-digit code, T 8387-3 EN)
3730-5FF intrinsically safe type (non-flameproof), 16-digit code, T 8384-5 EN
3730-6HART + pressure monitoring type, separate data sheet T 8384-6 EN (14 digits)
3730-4PROFIBUS PA fieldbus type (16 digits, T 8384-4 EN)
3725Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia

7. Common Spare Parts

ComponentDescription / Part number
Position sensor assemblyPart number: please consult us for confirmation
i/p converterPart number: please consult us for confirmation
Pneumatic amplifierPart number: please consult us for confirmation
Display and operating unit (LCD and buttons)Part number: please consult us for confirmation
Flameproof housing and cover assemblyPart number: please consult us for confirmation
Cable gland (M20 / 1/2 NPT)Part number: please consult us for confirmation
Source: SAMSON official data sheet NA 0122. Before ordering, please verify the complete model and configuration with us for part numbers.

8. Matching Accessories

AccessoryModel / SpecificationApplication
Filter pressure-reducing valvePlease consult us for confirmationFilters and stabilizes the instrument air supply pressure
Inductive limit switchSJ2-SN (normally closed contact)Limit position feedback
Solenoid valve / forced venting assembly24 V DCEmergency action / forced venting
Binary input modulePlease consult us for confirmationSwitching signal input
Reversing amplifier3710For use with double-acting actuators
Commissioning softwareTROVIS-VIEW (SSP interface) / DTMParameter setting, commissioning and diagnostics
Source: SAMSON official data sheets T 8387-5 EN, NA 0122.

9. Disclaimer

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.

10. Sources & Contact

Source: SAMSON official data sheets T 8387-5 EN, NA 0122.

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

Application area