Home » Products » Samson
SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection
SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection
SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection
SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection
SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection
SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection

SAMSON 3731-3 Ex d HART Smart Positioner - Technical Data & Selection

Details

1. Product Overview

The SAMSON 3731-3 is an Ex d flameproof HART intelligent electro-pneumatic valve positioner in the 3731 family. It shares a hybrid technology platform with the 3730 series (analog PD control + microprocessor) but uses a flameproof (Ex d / Flameproof) cast-aluminum or stainless-steel enclosure, allowing local operation via a single-knob menu in hazardous areas. It features a 4-20 mA two-wire loop with HART communication, LCD, autotune and EXPERTplus diagnostics. The complete ordering code is 15 digits, based on the separate data sheet T 8387-3 EN, and must not be confused with the 16-digit code of the 3730-3.

SAMSON 3731-3 Ex d flameproof HART positioner official product image
SAMSON 3731-3 positioner official product image (official image, for selection reference only)

Arrival Photos (taken by Baoman Industrial)

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3731 Smart Electropneumatic Positioner arrival photo
SAMSON 3731 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

2. Technical Description

Flameproof construction: Uses an Ex d flameproof enclosure (cast aluminum EN AC-43400 chromated + powder coated, or stainless steel), which may include Ex ia intrinsically safe options; degree of protection IP66 / NEMA 4X, weight approximately 2.5 kg. Suitable for industrial applications in Zone 1 hazardous areas requiring flameproof devices.

Control and communication: Wear-free calibrated position sensor + analog i/p + pneumatic amplifier + microprocessor closed-loop control; 4-20 mA two-wire setpoint (reverse polarity protected, minimum span 4 mA, static destruction limit 40 V, internal current limiting 60 mA), HART-band impedance approximately 455 Ω for reception and about 185 Ω for transmission. Features a 180°-rotatable alphanumeric LCD, single-knob autotune and EXPERTplus diagnostics (including PST partial stroke test).

Ordering code structure: Complete ordering number = 3731-3 + 15 digits, with the 1st digit being the "version/communication digit" (3 = HART). Compared with the 3731-5, the 3731-3 has a 4-20 mA loop and therefore has an additional "fail-action" digit, uses 2 digits for explosion protection, and offers a more complete option set. See Section 4 digit by digit.

Explosion-protection positioning: The 3731 series is mainly flameproof Ex d (the 3731-3 on this page = Ex d HART), not an intrinsically safe type. If the application only requires intrinsically safe Ex ia, consider the 3730 series or the 3725.

3. Key Technical Data

ItemDescription
Communication protocolHART field communication protocol (4-20 mA two-wire)
Setpoint signal4-20 mA, reverse polarity protected, minimum span 4 mA; static destruction limit 40 V, internal current limiting 60 mA
Load impedance≤450 Ω at 20 mA
Supply air pressure3731-321/327: 1.4-7 bar; 3731-323: 1.4-6 bar
Travel rangeDirect 3277: 3.6-30 mm; IEC 60534-6-1 bracket: 3.6-300 mm; rotary: 24°-100°
AccuracyHysteresis ≤0.3%; sensitivity ≤0.1%; flow characteristic deviation ≤1%
Degree of protectionIP66 / NEMA 4X
Type of explosion protectionEx d flameproof (cast aluminum or stainless steel enclosure), may include Ex ia intrinsically safe options
Electrical connection2×1/2 NPT or optional 2×M20×1.5; terminals 2.5 mm²
Self-diagnosticsEXPERT / EXPERTplus (including PST), NE107 status
Ambient temperature-40 ~ +80 °C (certificate limits apply separately)
Ordering code length15 digits (separate data sheet T 8387-3 EN)
Functional safetyIEC 61508: SIL 2 (single) / SIL 3 (redundant)
Source: SAMSON official data sheets T 8387-3 EN, NA 0122; explosion-protection parameters subject to the certificate.

4. Selection Guide (Complete Ordering Code)

Complete ordering number = 3731-3 + 15 digits, with the version digit fixed at 3. The table below lists the available codes and meanings digit by digit:

PositionFieldAvailable codes / Meaning
1Communication/version digit3 = HART version (with LCD, autotune, HART communication)
2-3Explosion protection (2 digits)21 = ATEX II 2G Ex db IIC T6 Gb (incl. Ex db eb / Ex db[ia] / Ex ia; II 2D Ex tb IIIC T80°C Db IP66); 23 = FM; 24 = EAC Ex; 27 = JIS Ex d IIC T6
4-5Options (2 digits)00 = none; 01 = position transmitter; 03 = binary input; 05 = forced venting; 06 = binary output (NAMUR/PLC)
6Diagnostics4 = EXPERTplus (control valve expert diagnostics, including partial stroke test PST)
7Electrical connection thread1 = 2×M20×1.5; 2 = 2×1/2 NPT
8Fail action / emergency action0 = emergency shut-off when setpoint = 0 mA (marked "no longer available" in T 8387-3 EN, no longer offered); 1 = emergency shut-off when setpoint falls below 3.85 mA, currently usually ordered as 1
9-11Explosion certification (3 digits)211 = CCC Ex / NEPSI; 212 = IECEx; 213 = EAC Ex; 215 = KCS; 216 = INMETRO; 217 = TR CMU 1055
12Special application0 = none
13-15Special version000 = none
Source: SAMSON official data sheet T 8387-3 EN, Article code table. Final codes are subject to confirmation by the official selection/ordering tool.

5. Complete Model Enumeration

The following are verified examples of complete 15-digit ordering codes for the 3731-3 with digit-by-digit breakdown:

Complete ordering codeDigit-by-digit breakdown / Meaning
3731-321004112110000Version 3 (HART) · explosion protection 21 (ATEX Ex db flameproof) · options 00 (no additions) · diagnostics 4 (EXPERTplus) · electrical interface 1 (M20×1.5) · fail action 1 (emergency shut-off at setpoint <3.85 mA) · certification 211 (CCC / NEPSI) · special application 0 (none) · special version 000 (none)
3731-321004122110000Version 3 (HART) · explosion protection 21 (ATEX Ex db) · options 00 · diagnostics 4 · electrical interface 2 (2×1/2 NPT) · fail action 1 · certification 211 (CCC / NEPSI) · application 0 · version 000
3731-321014112110000Version 3 (HART) · explosion protection 21 (ATEX Ex db) · options 01 (position transmitter) · diagnostics 4 · interface 1 (M20×1.5) · fail action 1 · certification 211 · application 0 · version 000

Note: The initial item has been verified against official T 8387-3 EN; the other two are combination illustrations based on the digit table in Section 4 (only the "electrical interface" and "options" digits are replaced); please consult us for confirmation for formal orders.

6. Related Models

Related modelType / Application
3731-5Ex d flameproof FF type (15-digit code, T 8387-5 EN)
3730-3HART intrinsically safe type (non-flameproof), 16-digit code, T 8384-3 EN
3730-6HART + pressure monitoring type, separate data sheet T 8384-6 EN (14 digits)
3725Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia
3277 actuatorPneumatic diaphragm actuator directly integrated with the positioner (linear)

7. Common Spare Parts

ComponentDescription / Part number
Position sensor assemblyPart number: please consult us for confirmation
i/p converterPart number: please consult us for confirmation
Pneumatic amplifierPart number: please consult us for confirmation
Display and operating unit (LCD and buttons)Part number: please consult us for confirmation
Flameproof housing and cover assemblyPart number: please consult us for confirmation
Cable gland (M20 / 1/2 NPT)Part number: please consult us for confirmation
Source: SAMSON official data sheet NA 0122. Before ordering, please verify the complete model and configuration with us for part numbers.

8. Matching Accessories

AccessoryModel / SpecificationApplication
Filter pressure-reducing valvePlease consult us for confirmationFilters and stabilizes the instrument air supply pressure
Position transmitterPlease consult us for confirmationOutputs 4-20 mA valve position feedback signal
Inductive limit switchSJ2-SN (normally closed contact)Limit position feedback
Solenoid valve / forced venting assembly24 V DCEmergency action / forced venting
Binary input / output modulePlease consult us for confirmationSwitching signal input and output
Reversing amplifier3710For use with double-acting actuators
Commissioning softwareTROVIS-VIEW (SSP interface) / DTMParameter setting, commissioning and diagnostics
Source: SAMSON official data sheets T 8387-3 EN, NA 0122.

9. Disclaimer

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.

10. Sources & Contact

Source: SAMSON official data sheets T 8387-3 EN, NA 0122.

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China