Home » Products » Samson
SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data
SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data

SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data

Details

1. Product Overview

The SAMSON 3730-5 is a FOUNDATION Fieldbus (FF) fieldbus intelligent electro-pneumatic valve positioner in the 3730 family. It complies with IEC 61158-2 transmission technology and is bus-powered; it compares the setpoint sent by the control system with the valve travel/opening and outputs a signal pressure. The device features LCD display, single-knob autotune and EXPERTplus diagnostics, and can integrate function blocks such as PID/AO/DI. The complete ordering code is 16 digits, with the 4th digit fixed at 0 as the FF identifier and explosion protection occupying 4 digits (P1 + P14-P16), which differs from the coding of the 3730-3/4.

SAMSON 3730-5 FOUNDATION Fieldbus positioner official product image
SAMSON 3730-5 positioner official product image (official image, for selection reference only)

Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

2. Technical Description

Bus communication: Complies with the FOUNDATION Fieldbus specification (IEC 61158-2), bus-powered; supports function blocks 1×PID, 1×AO, 1×DI (or floating), 2×DI, allowing the control strategy to be configured on the control-room side. An SSP interface is provided locally for TROVIS-VIEW commissioning.

Control and diagnostics: A closed loop formed by a wear-free calibrated position sensor, an analog i/p module and a pneumatic amplifier, with microprocessor autotune; integrated EXPERTplus control valve diagnostics, including dedicated options such as a leak sensor, with status output according to NE107.

Ordering code structure: Complete ordering number = 3730-5 + 16 digits, mask example ×××0××××0×00×0××, in which the 4th digit is fixed at 0 (FF identifier) and explosion protection occupies 4 digits (P1 + P14-P16). See Section 4 digit by digit.

Explosion-protection boundary: The 3730-5 belongs to the 3730-0~5 basic series, mainly intrinsically safe Ex ia, including IECEx, CCC Ex, CSA, EAC, KCS, Ex nA and other options; it does not include flameproof Ex d.

3. Key Technical Data

ItemDescription
CommunicationFOUNDATION Fieldbus, IEC 61158-2, bus-powered
Integrated function blocks1×PID, 1×AO, 1×DI (or floating), 2×DI
Supply air pressure1.4-7.0 bar
Travel range3.6-300 mm (linear, depending on mounting)
Rotation angle range24°-100° (rotary)
AccuracyHysteresis ≤0.3%; sensitivity ≤0.1%; characteristic deviation ≤1%
Degree of protectionIP66 / NEMA 4X
Type of explosion protectionMainly intrinsically safe Ex ia, including IECEx / CCC Ex / CSA / EAC / KCS / Ex nA; no flameproof Ex d
Self-diagnosticsEXPERTplus, NE107 status indication; optional leak sensor
Ambient temperature-20 ~ +80 °C (metal cable gland -45 ~ +80 °C)
MountingDirect integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847
Functional safetyComplies with IEC 61508, can be used in SIL 2 (single) / SIL 3 (redundant)
Source: SAMSON official data sheets T 8384-5 EN, NA 0122; explosion-protection parameters subject to the certificate.

4. Selection Guide (Complete Ordering Code)

Complete ordering number = 3730-5 + 16 digits, mask example ×××0××××0×00×0×× (4th digit fixed at 0, explosion protection occupies 4 digits). The table below lists the available codes and meanings digit by digit (positions marked "※" are inferred from the official table; final confirmation with the official selection/ordering tool is recommended):

PositionItemAvailable codes / Meaning
P1/P14-P16Explosion protection (4 digits)0000 = none; 1000 = ATEX Ex ia / II 2D Ex ia IIIC; 5000 = ATEX dust Ex tb; 8000 = ATEX Ex nA / Ex tc; 1012 = IECEx Ex ia; 8013 = IECEx Ex nA; 1009 = CCC Ex Ex ia; 8010 = CCC Ex Ex ic/nA; 3000 = CSA Ex ia; 1014 = EAC Ex ia; 1029 = KCS Ex ia
P2Inductive limit switch0 = none; 1 = SJ2-SN (NC contact)
P3Solenoid valve0 = none; 4 = with, 24 V DC
P4Bus identifier (fixed)0 = FF fixed position
P5Separate position sensor0 = none; 0100 = with
P6Leak sensor0 = none; 1 = with
P7Digital input0 = none; 01 = floating contact
P8Self-diagnostics4 = EXPERTplus
P10Housing material0 = aluminum (standard); 01 = stainless steel 1.4408
P13Special application0 = none; 1 = same paint color as the device; 2 = vent port with 1/4-18 NPT thread, rear sealed; 6 = connection per VDI/VDE 3847; 7 = port prepared per VDI/VDE 3847
P?※Special version000 = none
Source: SAMSON official data sheet T 8384-5 EN, Article code table. Positions marked "※" are subject to confirmation by the official selection/ordering tool.

5. Complete Model Enumeration

The following are examples of complete 16-digit ordering codes for the 3730-5 (deduced by combining the digit table in Section 4; for formal orders, the code generated by the official selection tool shall prevail — please consult us for confirmation):

Complete ordering codeDigit-by-digit breakdown / Meaning
3730-5 1000000400000000P1=1, P14-P16=000 (ATEX Ex ia intrinsically safe, explosion-protection 4-digit code 1000) · P2=0 (no limit switch) · P3=0 · P4=0 (FF fixed position) · P8=4 (EXPERTplus) · P10=0 (aluminum housing) · P13=0 (no special application)
3730-5 8000000400000000P1=8, P14-P16=000 (ATEX Ex nA non-sparking, explosion-protection 4-digit code 8000) · P4=0 · P8=4 (EXPERTplus) · remaining digits standard configuration
3730-5 1000000400000009P1=1, P14-P16=009 (CCC Ex Ex ia, explosion-protection 4-digit code 1009) · P4=0 · P8=4 (EXPERTplus) · remaining digits standard configuration

Note: The above are combination illustrations deduced from the digit table, to show that "3730-5 must be followed by a full 16 digits, the 4th digit must be 0, and explosion protection occupies 4 digits". With many fields and complex additional certifications, do not assemble codes by yourself; please consult us for confirmation.

6. Related Models

Related modelType / Application
3731-5Ex d flameproof FF version corresponding to the 3730-5 (15-digit code, T 8387-5 EN)
3730-4PROFIBUS PA fieldbus type (16-digit code, T 8384-4 EN)
3730-3HART full-featured type, a widely used communication version in this family
3730-6HART + supply/output pressure monitoring type, separate data sheet T 8384-6 EN (14-digit code)
3725Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia

7. Common Spare Parts

ComponentDescription / Part number
Position sensor assemblyPart number: please consult us for confirmation
i/p converterPart number: please consult us for confirmation
Pneumatic amplifierPart number: please consult us for confirmation
Display and operating unit (LCD and buttons)Part number: please consult us for confirmation
Housing and cover assemblyPart number: please consult us for confirmation
Cable glandPart number: please consult us for confirmation
Source: SAMSON official data sheet NA 0122. Before ordering, please verify the complete model and configuration with us for part numbers.

8. Matching Accessories

AccessoryModel / SpecificationApplication
Filter pressure-reducing valvePlease consult us for confirmationFilters and stabilizes the instrument air supply pressure
Inductive limit switchSJ2-SN (normally closed contact)Limit position feedback
Solenoid valve24 V DCForced venting / emergency action
Separate position sensorPlease consult us for confirmationPosition detection for separate actuator mounting
Leak sensorPlease consult us for confirmationValve seat leakage monitoring
Reversing amplifier3710For use with double-acting actuators
Commissioning softwareTROVIS-VIEW (SSP interface) / DTMParameter setting, commissioning and diagnostics

9. Disclaimer

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.

10. Sources & Contact

Source: SAMSON official data sheets T 8384-5 EN, NA 0122.

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China