SAMSON 3730-5 FOUNDATION Fieldbus Positioner - Technical Data
1. Product Overview
The SAMSON 3730-5 is a FOUNDATION Fieldbus (FF) fieldbus intelligent electro-pneumatic valve positioner in the 3730 family. It complies with IEC 61158-2 transmission technology and is bus-powered; it compares the setpoint sent by the control system with the valve travel/opening and outputs a signal pressure. The device features LCD display, single-knob autotune and EXPERTplus diagnostics, and can integrate function blocks such as PID/AO/DI. The complete ordering code is 16 digits, with the 4th digit fixed at 0 as the FF identifier and explosion protection occupying 4 digits (P1 + P14-P16), which differs from the coding of the 3730-3/4.

SAMSON 3730-5 positioner official product image (official image, for selection reference only)
Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked
2. Technical Description
Bus communication: Complies with the FOUNDATION Fieldbus specification (IEC 61158-2), bus-powered; supports function blocks 1×PID, 1×AO, 1×DI (or floating), 2×DI, allowing the control strategy to be configured on the control-room side. An SSP interface is provided locally for TROVIS-VIEW commissioning.
Control and diagnostics: A closed loop formed by a wear-free calibrated position sensor, an analog i/p module and a pneumatic amplifier, with microprocessor autotune; integrated EXPERTplus control valve diagnostics, including dedicated options such as a leak sensor, with status output according to NE107.
Ordering code structure: Complete ordering number = 3730-5 + 16 digits, mask example ×××0××××0×00×0××, in which the 4th digit is fixed at 0 (FF identifier) and explosion protection occupies 4 digits (P1 + P14-P16). See Section 4 digit by digit.
3. Key Technical Data
| Item | Description |
|---|---|
| Communication | FOUNDATION Fieldbus, IEC 61158-2, bus-powered |
| Integrated function blocks | 1×PID, 1×AO, 1×DI (or floating), 2×DI |
| Supply air pressure | 1.4-7.0 bar |
| Travel range | 3.6-300 mm (linear, depending on mounting) |
| Rotation angle range | 24°-100° (rotary) |
| Accuracy | Hysteresis ≤0.3%; sensitivity ≤0.1%; characteristic deviation ≤1% |
| Degree of protection | IP66 / NEMA 4X |
| Type of explosion protection | Mainly intrinsically safe Ex ia, including IECEx / CCC Ex / CSA / EAC / KCS / Ex nA; no flameproof Ex d |
| Self-diagnostics | EXPERTplus, NE107 status indication; optional leak sensor |
| Ambient temperature | -20 ~ +80 °C (metal cable gland -45 ~ +80 °C) |
| Mounting | Direct integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847 |
| Functional safety | Complies with IEC 61508, can be used in SIL 2 (single) / SIL 3 (redundant) |
4. Selection Guide (Complete Ordering Code)
Complete ordering number = 3730-5 + 16 digits, mask example ×××0××××0×00×0×× (4th digit fixed at 0, explosion protection occupies 4 digits). The table below lists the available codes and meanings digit by digit (positions marked "※" are inferred from the official table; final confirmation with the official selection/ordering tool is recommended):
| Position | Item | Available codes / Meaning |
|---|---|---|
| P1/P14-P16 | Explosion protection (4 digits) | 0000 = none; 1000 = ATEX Ex ia / II 2D Ex ia IIIC; 5000 = ATEX dust Ex tb; 8000 = ATEX Ex nA / Ex tc; 1012 = IECEx Ex ia; 8013 = IECEx Ex nA; 1009 = CCC Ex Ex ia; 8010 = CCC Ex Ex ic/nA; 3000 = CSA Ex ia; 1014 = EAC Ex ia; 1029 = KCS Ex ia |
| P2 | Inductive limit switch | 0 = none; 1 = SJ2-SN (NC contact) |
| P3 | Solenoid valve | 0 = none; 4 = with, 24 V DC |
| P4 | Bus identifier (fixed) | 0 = FF fixed position |
| P5 | Separate position sensor | 0 = none; 0100 = with |
| P6 | Leak sensor | 0 = none; 1 = with |
| P7 | Digital input | 0 = none; 01 = floating contact |
| P8 | Self-diagnostics | 4 = EXPERTplus |
| P10 | Housing material | 0 = aluminum (standard); 01 = stainless steel 1.4408 |
| P13 | Special application | 0 = none; 1 = same paint color as the device; 2 = vent port with 1/4-18 NPT thread, rear sealed; 6 = connection per VDI/VDE 3847; 7 = port prepared per VDI/VDE 3847 |
| P?※ | Special version | 000 = none |
5. Complete Model Enumeration
The following are examples of complete 16-digit ordering codes for the 3730-5 (deduced by combining the digit table in Section 4; for formal orders, the code generated by the official selection tool shall prevail — please consult us for confirmation):
| Complete ordering code | Digit-by-digit breakdown / Meaning |
|---|---|
3730-5 1000000400000000 | P1=1, P14-P16=000 (ATEX Ex ia intrinsically safe, explosion-protection 4-digit code 1000) · P2=0 (no limit switch) · P3=0 · P4=0 (FF fixed position) · P8=4 (EXPERTplus) · P10=0 (aluminum housing) · P13=0 (no special application) |
3730-5 8000000400000000 | P1=8, P14-P16=000 (ATEX Ex nA non-sparking, explosion-protection 4-digit code 8000) · P4=0 · P8=4 (EXPERTplus) · remaining digits standard configuration |
3730-5 1000000400000009 | P1=1, P14-P16=009 (CCC Ex Ex ia, explosion-protection 4-digit code 1009) · P4=0 · P8=4 (EXPERTplus) · remaining digits standard configuration |
Note: The above are combination illustrations deduced from the digit table, to show that "3730-5 must be followed by a full 16 digits, the 4th digit must be 0, and explosion protection occupies 4 digits". With many fields and complex additional certifications, do not assemble codes by yourself; please consult us for confirmation.
6. Related Models
| Related model | Type / Application |
|---|---|
| 3731-5 | Ex d flameproof FF version corresponding to the 3730-5 (15-digit code, T 8387-5 EN) |
| 3730-4 | PROFIBUS PA fieldbus type (16-digit code, T 8384-4 EN) |
| 3730-3 | HART full-featured type, a widely used communication version in this family |
| 3730-6 | HART + supply/output pressure monitoring type, separate data sheet T 8384-6 EN (14-digit code) |
| 3725 | Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia |
7. Common Spare Parts
| Component | Description / Part number |
|---|---|
| Position sensor assembly | Part number: please consult us for confirmation |
| i/p converter | Part number: please consult us for confirmation |
| Pneumatic amplifier | Part number: please consult us for confirmation |
| Display and operating unit (LCD and buttons) | Part number: please consult us for confirmation |
| Housing and cover assembly | Part number: please consult us for confirmation |
| Cable gland | Part number: please consult us for confirmation |
8. Matching Accessories
| Accessory | Model / Specification | Application |
|---|---|---|
| Filter pressure-reducing valve | Please consult us for confirmation | Filters and stabilizes the instrument air supply pressure |
| Inductive limit switch | SJ2-SN (normally closed contact) | Limit position feedback |
| Solenoid valve | 24 V DC | Forced venting / emergency action |
| Separate position sensor | Please consult us for confirmation | Position detection for separate actuator mounting |
| Leak sensor | Please consult us for confirmation | Valve seat leakage monitoring |
| Reversing amplifier | 3710 | For use with double-acting actuators |
| Commissioning software | TROVIS-VIEW (SSP interface) / DTM | Parameter setting, commissioning and diagnostics |
9. Disclaimer
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.
10. Sources & Contact
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文