SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data
1. Product Overview
The SAMSON 3730-4 is a PROFIBUS PA fieldbus intelligent electro-pneumatic valve positioner in the 3730 family. It complies with the PROFIBUS-PA specification (based on IEC 61158-2 transmission technology) and is bus-powered; it compares the setpoint periodically sent by the control system with the valve travel/opening and outputs the corresponding signal pressure. The device is certified to PROFIBUS-PA Profile 3.01/3.02, supports automatic ID adaptation (facilitating replacement of older models such as the 3785), and features LCD display, single-knob autotune and EXPERTplus diagnostics. The complete ordering code is 16 digits, with the 4th digit fixed at 0 as the PROFIBUS identifier.

SAMSON 3730-4 positioner official product image (official image, for selection reference only)
Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked
2. Technical Description
Bus communication: The fieldbus interface complies with IEC 61158-2 and is bus-powered according to FISCO (Fieldbus Intrinsically Safe Concept); permissible supply voltage 9-32 V DC, maximum operating current 15 mA. Supports integration via DTM (FDT 1.2), EDD/AMS/PDM, etc.; an SSP interface is additionally provided locally for TROVIS-VIEW configuration.
Control and diagnostics: Composed of a wear-free calibrated position sensor, an analog i/p module and a pneumatic amplifier, with a microprocessor performing closed-loop control and autotune; integrated EXPERTplus control valve diagnostics (T 8389), with status alarms graded according to NAMUR NE107. Standard configuration includes one binary input for a DC voltage signal.
Ordering code structure: Complete ordering number = 3730-4 + 16 digits, mask example ×××0×0××0×00×0××, in which the 4th digit is fixed at 0 (PROFIBUS identifier). See Section 4 digit by digit.
3. Key Technical Data
| Item | Description |
|---|---|
| Communication | PROFIBUS PA, IEC 61158-2 / IEC 61784, Profile 3.01/3.02 |
| Power supply | Bus-powered, 9-32 V DC, maximum operating current 15 mA, compliant with FISCO |
| Supply air pressure | 1.4-7.0 bar |
| Travel range | 3.6-300 mm (linear, depending on mounting) |
| Rotation angle range | 24°-100° (rotary) |
| Accuracy | Hysteresis ≤0.3%; sensitivity ≤0.1%; characteristic deviation ≤1% |
| Degree of protection | IP66 / NEMA 4X |
| Type of explosion protection | Mainly intrinsically safe Ex ia, including CSA/FM, Ex nA, etc.; no flameproof Ex d |
| Self-diagnostics | EXPERTplus, NE107 status alarm |
| Ambient temperature | -20 ~ +80 °C (metal cable gland -45 ~ +80 °C) |
| Mounting | Direct integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847 |
| Functional safety | Complies with IEC 61508, can be used in SIL 2 (single) / SIL 3 (redundant) |
4. Selection Guide (Complete Ordering Code)
Complete ordering number = 3730-4 + 16 digits, mask example ×××0×0××0×00×0×× (4th digit forced to 0). The table below lists the available codes and meanings digit by digit (positions marked "※" are inferred from the official table; final confirmation with the official selection/ordering tool is recommended):
| Position | Item | Available codes / Meaning |
|---|---|---|
| P1 | Explosion protection | 0 = none; 1 = ATEX II 2G Ex ia IIC T6 Gb / II 2D Ex ia IIIC T80°C Db; 3 = CSA/FM intrinsically safe/non-sparking; 5 = FM or ATEX dust; 8 = ATEX II 3G Ex nA IIC T6 Gc |
| P2 | Inductive limit switch | 0 = not included; 1 = 1×SJ2-SN (NC contact) |
| P3 | Solenoid valve | 0 = not included; 4 = with, 24 V DC |
| P4 | Bus identifier (fixed) | 0 = PROFIBUS PA fixed position |
| P4-P8※ | Separate position sensor | 0 = not included; 00100 = with (10 m connecting cable, IP67) |
| P5-P6※ | Digital input | 00 = not included; 01 = floating contact |
| P7 | Self-diagnostics | 1 = EXPERT (standard version); 2 = EXPERT+ (enhanced version) |
| P9-P10※ | Housing material | 0 = aluminum (standard); 01 = stainless steel 1.4408 |
| P12 | Special application | 0 = none; 1 = coating in specified paint color; 2 = vent connection with 1/4-18 NPT thread |
| P?※ | Special version | 000 = none; 1000099 = NEPSI Ex ia; 8001100 = NEPSI Ex nL/nA; 1001122 = IECEx |
5. Complete Model Enumeration
The following are examples of complete 16-digit ordering codes for the 3730-4 (deduced by combining the digit table in Section 4; for formal orders, the code generated by the official selection tool shall prevail — please consult us for confirmation):
| Complete ordering code | Digit-by-digit breakdown / Meaning |
|---|---|
3730-4 1000001000000000 | P1=1 (ATEX Ex ia intrinsically safe) · P2=0 (no limit switch) · P3=0 (no solenoid valve) · P4=0 (PROFIBUS fixed position) · P7=1 (EXPERT standard diagnostics) · P9-P10=00 (aluminum housing) · P12=0 (no special application) |
3730-4 1000002000000000 | P1=1 (ATEX Ex ia) · P4=0 · P7=2 (EXPERT+ enhanced diagnostics) · remaining digits standard configuration |
3730-4 8000001000000000 | P1=8 (ATEX Ex nA non-sparking) · P4=0 · P7=1 (EXPERT standard diagnostics) · remaining digits standard configuration |
Note: The above are combination illustrations deduced from the digit table, to show that "3730-4 must be followed by a full 16 digits and the 4th digit must be 0". With many fields and complex additional certifications, do not assemble codes by yourself; please consult us for confirmation.
6. Related Models
| Related model | Type / Application |
|---|---|
| 3730-5 | FOUNDATION Fieldbus fieldbus type (16-digit code, T 8384-5 EN) |
| 3730-3 | HART full-featured type, a widely used communication version in this family |
| 3730-6 | HART + supply/output pressure monitoring type, separate data sheet T 8384-6 EN (14-digit code) |
| 3725 | Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia |
| 3277 actuator | Pneumatic diaphragm actuator directly integrated with the positioner (linear) |
7. Common Spare Parts
| Component | Description / Part number |
|---|---|
| Position sensor assembly | Part number: please consult us for confirmation |
| i/p converter | Part number: please consult us for confirmation |
| Pneumatic amplifier | Part number: please consult us for confirmation |
| Display and operating unit (LCD and buttons) | Part number: please consult us for confirmation |
| Housing and cover assembly | Part number: please consult us for confirmation |
| Cable gland | Part number: please consult us for confirmation |
8. Matching Accessories
| Accessory | Model / Specification | Application |
|---|---|---|
| Filter pressure-reducing valve | Please consult us for confirmation | Filters and stabilizes the instrument air supply pressure |
| Inductive limit switch | SJ2-SN (normally closed contact) | Limit position feedback |
| Solenoid valve | 24 V DC | Forced venting / emergency action |
| Separate position sensor | Please consult us for confirmation | Position detection for separate actuator mounting |
| Reversing amplifier | 3710 | For use with double-acting actuators |
| Commissioning software | TROVIS-VIEW (SSP interface) / DTM | Parameter setting, commissioning and diagnostics |
9. Disclaimer
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.
10. Sources & Contact
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文