Home » Products » Samson
SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data
SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data
SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data
SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data
SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data
SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data

SAMSON 3730-4 PROFIBUS PA Positioner - Technical Data

Details

1. Product Overview

The SAMSON 3730-4 is a PROFIBUS PA fieldbus intelligent electro-pneumatic valve positioner in the 3730 family. It complies with the PROFIBUS-PA specification (based on IEC 61158-2 transmission technology) and is bus-powered; it compares the setpoint periodically sent by the control system with the valve travel/opening and outputs the corresponding signal pressure. The device is certified to PROFIBUS-PA Profile 3.01/3.02, supports automatic ID adaptation (facilitating replacement of older models such as the 3785), and features LCD display, single-knob autotune and EXPERTplus diagnostics. The complete ordering code is 16 digits, with the 4th digit fixed at 0 as the PROFIBUS identifier.

SAMSON 3730-4 PROFIBUS PA positioner official product image
SAMSON 3730-4 positioner official product image (official image, for selection reference only)

Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 Smart Electropneumatic Positioner arrival photo
SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

2. Technical Description

Bus communication: The fieldbus interface complies with IEC 61158-2 and is bus-powered according to FISCO (Fieldbus Intrinsically Safe Concept); permissible supply voltage 9-32 V DC, maximum operating current 15 mA. Supports integration via DTM (FDT 1.2), EDD/AMS/PDM, etc.; an SSP interface is additionally provided locally for TROVIS-VIEW configuration.

Control and diagnostics: Composed of a wear-free calibrated position sensor, an analog i/p module and a pneumatic amplifier, with a microprocessor performing closed-loop control and autotune; integrated EXPERTplus control valve diagnostics (T 8389), with status alarms graded according to NAMUR NE107. Standard configuration includes one binary input for a DC voltage signal.

Ordering code structure: Complete ordering number = 3730-4 + 16 digits, mask example ×××0×0××0×00×0××, in which the 4th digit is fixed at 0 (PROFIBUS identifier). See Section 4 digit by digit.

Explosion-protection boundary: The 3730-4 belongs to the 3730-0~5 basic series, mainly intrinsically safe Ex ia, including CSA/FM intrinsically safe, Ex nA non-sparking and other options; it does not include flameproof Ex d. For a bus type requiring a flameproof enclosure, please consult us for confirmation.

3. Key Technical Data

ItemDescription
CommunicationPROFIBUS PA, IEC 61158-2 / IEC 61784, Profile 3.01/3.02
Power supplyBus-powered, 9-32 V DC, maximum operating current 15 mA, compliant with FISCO
Supply air pressure1.4-7.0 bar
Travel range3.6-300 mm (linear, depending on mounting)
Rotation angle range24°-100° (rotary)
AccuracyHysteresis ≤0.3%; sensitivity ≤0.1%; characteristic deviation ≤1%
Degree of protectionIP66 / NEMA 4X
Type of explosion protectionMainly intrinsically safe Ex ia, including CSA/FM, Ex nA, etc.; no flameproof Ex d
Self-diagnosticsEXPERTplus, NE107 status alarm
Ambient temperature-20 ~ +80 °C (metal cable gland -45 ~ +80 °C)
MountingDirect integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847
Functional safetyComplies with IEC 61508, can be used in SIL 2 (single) / SIL 3 (redundant)
Source: SAMSON official data sheets T 8384-4 EN, NA 0122; explosion-protection parameters subject to the certificate.

4. Selection Guide (Complete Ordering Code)

Complete ordering number = 3730-4 + 16 digits, mask example ×××0×0××0×00×0×× (4th digit forced to 0). The table below lists the available codes and meanings digit by digit (positions marked "※" are inferred from the official table; final confirmation with the official selection/ordering tool is recommended):

PositionItemAvailable codes / Meaning
P1Explosion protection0 = none; 1 = ATEX II 2G Ex ia IIC T6 Gb / II 2D Ex ia IIIC T80°C Db; 3 = CSA/FM intrinsically safe/non-sparking; 5 = FM or ATEX dust; 8 = ATEX II 3G Ex nA IIC T6 Gc
P2Inductive limit switch0 = not included; 1 = 1×SJ2-SN (NC contact)
P3Solenoid valve0 = not included; 4 = with, 24 V DC
P4Bus identifier (fixed)0 = PROFIBUS PA fixed position
P4-P8※Separate position sensor0 = not included; 00100 = with (10 m connecting cable, IP67)
P5-P6※Digital input00 = not included; 01 = floating contact
P7Self-diagnostics1 = EXPERT (standard version); 2 = EXPERT+ (enhanced version)
P9-P10※Housing material0 = aluminum (standard); 01 = stainless steel 1.4408
P12Special application0 = none; 1 = coating in specified paint color; 2 = vent connection with 1/4-18 NPT thread
P?※Special version000 = none; 1000099 = NEPSI Ex ia; 8001100 = NEPSI Ex nL/nA; 1001122 = IECEx
Source: SAMSON official data sheet T 8384-4 EN, Article code table. Positions marked "※" are subject to confirmation by the official selection/ordering tool.

5. Complete Model Enumeration

The following are examples of complete 16-digit ordering codes for the 3730-4 (deduced by combining the digit table in Section 4; for formal orders, the code generated by the official selection tool shall prevail — please consult us for confirmation):

Complete ordering codeDigit-by-digit breakdown / Meaning
3730-4 1000001000000000P1=1 (ATEX Ex ia intrinsically safe) · P2=0 (no limit switch) · P3=0 (no solenoid valve) · P4=0 (PROFIBUS fixed position) · P7=1 (EXPERT standard diagnostics) · P9-P10=00 (aluminum housing) · P12=0 (no special application)
3730-4 1000002000000000P1=1 (ATEX Ex ia) · P4=0 · P7=2 (EXPERT+ enhanced diagnostics) · remaining digits standard configuration
3730-4 8000001000000000P1=8 (ATEX Ex nA non-sparking) · P4=0 · P7=1 (EXPERT standard diagnostics) · remaining digits standard configuration

Note: The above are combination illustrations deduced from the digit table, to show that "3730-4 must be followed by a full 16 digits and the 4th digit must be 0". With many fields and complex additional certifications, do not assemble codes by yourself; please consult us for confirmation.

6. Related Models

Related modelType / Application
3730-5FOUNDATION Fieldbus fieldbus type (16-digit code, T 8384-5 EN)
3730-3HART full-featured type, a widely used communication version in this family
3730-6HART + supply/output pressure monitoring type, separate data sheet T 8384-6 EN (14-digit code)
3725Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia
3277 actuatorPneumatic diaphragm actuator directly integrated with the positioner (linear)

7. Common Spare Parts

ComponentDescription / Part number
Position sensor assemblyPart number: please consult us for confirmation
i/p converterPart number: please consult us for confirmation
Pneumatic amplifierPart number: please consult us for confirmation
Display and operating unit (LCD and buttons)Part number: please consult us for confirmation
Housing and cover assemblyPart number: please consult us for confirmation
Cable glandPart number: please consult us for confirmation
Source: SAMSON official data sheet NA 0122. Before ordering, please verify the complete model and configuration with us for part numbers.

8. Matching Accessories

AccessoryModel / SpecificationApplication
Filter pressure-reducing valvePlease consult us for confirmationFilters and stabilizes the instrument air supply pressure
Inductive limit switchSJ2-SN (normally closed contact)Limit position feedback
Solenoid valve24 V DCForced venting / emergency action
Separate position sensorPlease consult us for confirmationPosition detection for separate actuator mounting
Reversing amplifier3710For use with double-acting actuators
Commissioning softwareTROVIS-VIEW (SSP interface) / DTMParameter setting, commissioning and diagnostics

9. Disclaimer

The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.

10. Sources & Contact

Source: SAMSON official data sheets T 8384-4 EN, NA 0122.

Ordering & Inquiry

If you need help confirming model numbers, configurations or availability, please feel free to contact us. We can assist with selection and technical confirmation based on your operating conditions and signal requirements.
Tel: +86 028-60220547  |  Email: info@bit-cd.com
Baoman Industrial Technology (Chengdu) Co., Ltd   Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

Application area