SAMSON 3730-3 HART Smart Positioner - Technical Data & Selection
1. Product Overview
The SAMSON 3730-3 is a HART full-featured intelligent electro-pneumatic valve positioner in the 3730 family and a widely used version in this family. It superimposes HART communication on a 4-20 mA two-wire loop, receives the setpoint from the control system, drives a pneumatic linear or rotary actuator for closed-loop valve position control, and integrates LCD display, single-knob autotune and EXPERTplus expert diagnostics (NE107 status indication). Its complete ordering code uses a 16-digit grouped, digit-by-digit structure; please order using the complete ordering code rather than the abbreviated "3730-3".

SAMSON 3730-3 HART positioner official product image (official image, for selection reference only)
Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked
2. Technical Description
Control principle: A closed loop formed by a wear-free calibrated position sensor, an analog i/p module with downstream pneumatic amplifier, and a microprocessor electronic unit. The microprocessor compares the setpoint with the valve position and outputs a signal pressure; four initialization modes and sub-initialization (sub) modes are supported, parameters are stored in EEPROM, with continuous zero-point monitoring and tight shut-off function.
HART communication: Uses the HART field communication protocol; the HART-band impedance is approximately 350-450 Ω for reception and about 115 Ω for transmission; the two-wire load is ≤8.2 V (410 Ω at 20 mA). Configuration, parameter read/write and diagnostics can be performed via a handheld communicator or TROVIS-VIEW / DTM.
Diagnostics and status: Integrated EXPERTplus expert diagnostics for control valves; two programmable position switches and one fault alarm contact; status output according to NAMUR NE107, transmittable via the fault contact or an optional analog position transmitter.
Ordering code structure: Complete ordering number = 3730-3 + 16 digits, mask example ×××××××0×0×0××, digit by digit in Section 4. The digit positions and example codes below are taken from the official data sheet T 8384-3 EN and have been verified.
3. Key Technical Data
| Item | Description |
|---|---|
| Input signal | 4-20 mA two-wire, reverse polarity protected, minimum span 4 mA; HART superimposed |
| Load impedance | ≤8.2 V (410 Ω at 20 mA) |
| Supply air pressure | 1.4-7.0 bar (20-105 psi) |
| Travel range | 3.6-300 mm (linear, depending on mounting) |
| Rotation angle range | 24°-100° (rotary) |
| Accuracy | Hysteresis ≤0.3%; sensitivity ≤0.1%; characteristic deviation ≤1% |
| Degree of protection | IP66 / NEMA 4X |
| Type of explosion protection | Mainly intrinsically safe Ex ia, including CSA, dust, Ex nA, etc.; no flameproof Ex d |
| Self-diagnostics | EXPERTplus, NE107 status indication |
| Ambient temperature | -20 ~ +80 °C (metal cable gland -45 ~ +80 °C; explosion protection subject to the certificate) |
| Mounting | Direct integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847 |
| Functional safety | Complies with IEC 61508; can be used in SIL 2 (single) / SIL 3 (redundant) safety instrumented systems |
4. Selection Guide (Complete Ordering Code)
Complete ordering number = 3730-3 + 16 digits, mask example ×××××××0×0×0××. The table below lists the available codes and meanings digit by digit (positions marked "※" are inferred from the official table; final confirmation with the official selection/ordering tool is recommended):
| Position | Item | Available codes / Meaning |
|---|---|---|
| P1 | Explosion protection | 0 = no explosion protection; 1 = ATEX II 2G Ex ia IIC Gb / II 2D Ex ia IIIC T80°C Db; 3 = CSA Ex ia IIC T6; 5 = ATEX dust Ex tb IIIC T80°C Db; 8 = ATEX Ex nA IIC T6 Gc / Ex tc IIIC T80°C Dc |
| P2 | Inductive limit switch | 0 = none; 1 = SJ2-SN (normally closed contact) |
| P3 | Solenoid valve | 0 = none; 4 = with, 24 V DC |
| P4-P7 | Additional equipment (mutually exclusive group) | 1000 = position transmitter (4-20 mA position feedback, i.e. "with feedback"); 0100 / 0200 = separate position sensor (when P2=0, P10=0); P5=3 = analog input x; P6=1 = leak sensor; P7=2 = digital input; 0000 = no additional equipment |
| P8 | Self-diagnostics | 0 = standard EXPERT (default); 4 = EXPERTplus enhanced self-diagnostics |
| P9 | Fixed position | 0 |
| P10 | Housing material | 0 = aluminum (standard); 1 = stainless steel |
| P11-P12 | Fixed positions | 0 / 0 |
| P13 | Special application | 0 = none; 1 = free of substances affecting painting; 2 = 1/4 NPT vent port (rear of housing); 6 = with additional vent hole + VDI/VDE 3847 adapter; 7 = with additional vent hole |
| P14 | Fixed position | 0 |
| P15-P16 | Special version (combined with P1) | 00 = standard; 12 = IECEx Ex ia; 34 = Ex tb IIIC; 13 = Ex nA / Ex tc; 14 = EAC Ex ia; 20 = 2Ex ic / 2Ex nA |
5. Complete Model Enumeration
The following are verified examples of complete 16-digit ordering codes for the 3730-3 with digit-by-digit breakdown:
| Complete ordering code | Digit-by-digit breakdown / Meaning |
|---|---|
3730-3 1001000400000000 | P1=1 (ATEX Ex ia intrinsically safe) · P2=0 · P3=0 · P4-P7=1,0,0,0 (with position transmitter = position feedback) · P8=4 (EXPERTplus) · P9=0 (fixed) · P10=0 (aluminum housing) · P11/P12=0 (fixed) · P13=0 · P14=0 (fixed) · P15-P16=00 (standard version) |
3730-3 1100000400000000 | P1=1 (ATEX Ex ia) · P2=1 (SJ2-SN inductive limit switch, i.e. "feedback" via discrete limit switch) · P3=0 · P4-P7=0000 · P8=4 (EXPERTplus) · P10=0 (aluminum housing) · P15-P16=00 (standard version) |
3730-3 1001000401000012 | P1=1 (ATEX Ex ia) · P2=0 · P3=0 · P4-P7=1000 (position transmitter feedback) · P8=4 (EXPERTplus) · P9=0 (fixed) · P10=1 (stainless steel housing) · P11/P12=0 (fixed) · P13=0 · P14=0 (fixed) · P15-P16=12 (IECEx Ex ia additional certification) — combination illustration; please consult us for confirmation for formal orders |
Note: The initial two items have been verified against official T 8384-3 EN; the third is a combination illustration based on the digit table in Section 4. The combination of additional certification and material is subject to confirmation by the official selection tool (please consult us for confirmation).
6. Related Models
| Related model | Type / Application |
|---|---|
| 3731-3 | Ex d flameproof HART version corresponding to the 3730-3 (15-digit code, T 8387-3 EN) |
| 3730-6 | HART + supply/output pressure monitoring type, separate data sheet T 8384-6 EN (14-digit code) |
| 3730-2 | Non-communication full-featured type, with parameterization and EXPERTplus diagnostics |
| 3730-4 / 3730-5 | PROFIBUS PA / FOUNDATION Fieldbus fieldbus types |
| 3725 | Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia |
7. Common Spare Parts
| Component | Description / Part number |
|---|---|
| Position sensor assembly | Part number: please consult us for confirmation |
| i/p converter | Part number: please consult us for confirmation |
| Pneumatic amplifier | Part number: please consult us for confirmation |
| Display and operating unit (LCD and buttons) | Part number: please consult us for confirmation |
| Housing and cover assembly | Part number: please consult us for confirmation |
| Cable gland | Part number: please consult us for confirmation |
8. Matching Accessories
| Accessory | Model / Specification | Application |
|---|---|---|
| Filter pressure-reducing valve | Please consult us for confirmation | Filters and stabilizes the instrument air supply pressure |
| Position transmitter | Please consult us for confirmation | Outputs 4-20 mA valve position feedback signal |
| Inductive limit switch | SJ2-SN (normally closed contact) | Limit position feedback |
| Solenoid valve | 24 V DC | Forced venting / emergency action |
| Separate position sensor | Please consult us for confirmation | Position detection for separate actuator mounting |
| Leak sensor | Please consult us for confirmation | Valve seat leakage monitoring |
| Reversing amplifier | 3710 | For use with double-acting actuators |
| Commissioning software | TROVIS-VIEW (SSP interface) / DTM | Parameter setting, commissioning and diagnostics |
9. Disclaimer
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.
10. Sources & Contact
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文