SAMSON 3730-2 Full-Feature Digital Positioner - Technical Data
1. Product Overview
The SAMSON 3730-2 is a non-communication full-featured electro-pneumatic valve positioner in the 3730 family. It features microprocessor control, LCD display with a single rotary knob, autotune, and supports parameterization and EXPERTplus diagnostics (NE107 status indication); it is the configuration for applications that do not use a fieldbus but require complete commissioning/diagnostic capability. The difference from the 3730-3 is that the 3730-2 has no HART communication and the signal remains a pure 4-20 mA setpoint.

SAMSON 3730-2 positioner official product image (official image, for selection reference only)
Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked
2. Technical Description
Control principle: A closed loop formed by valve position detection, analog i/p conversion, pneumatic amplification and a microprocessor electronic unit, driving the actuator according to the control algorithm; initialization/autotune is supported, with parameters stored in non-volatile memory; the tight shut-off function can be activated and continuous zero-point monitoring performed.
Diagnostics: Integrated EXPERT / EXPERTplus expert diagnostics for control valves; status is output as a condensed state according to NAMUR NE107 (via a fault alarm contact or an optional analog position transmitter), facilitating preventive maintenance. This is the main increment of the 3730-2 over the 3730-1.
Communication boundaries: No HART, PROFIBUS PA or FOUNDATION Fieldbus communication. If HART is required, select the 3730-3; if bus-powered PROFIBUS PA is required, select the 3730-4; if FF is required, select the 3730-5.
Ordering code structure: Complete ordering number = "3730-2" + 16 digits, using a grouped, digit-by-digit structure; its explosion-protection and additional-equipment positions are essentially similar to those of the 3730-3, but there is no fixed bus-identification position (the 4th digit is not required to be 0). For detailed positions refer to T 8384-2 EN; please consult us for confirmation of the final code.
3. Key Technical Data
| Item | Description |
|---|---|
| Input signal | 4-20 mA two-wire (no communication superimposed) |
| Supply air pressure | 1.4-7.0 bar (limitable by software to 1.4 / 2.4 / 3.7 bar) |
| Travel range | 3.6-300 mm (linear, depending on mounting) |
| Rotation angle range | 24°-100° (rotary) |
| Control type | Microprocessor control + autotune + parameterization |
| Self-diagnostics | EXPERT / EXPERTplus, NE107 status indication |
| Degree of protection | IP66 |
| Type of explosion protection | Mainly intrinsically safe Ex ia, including Ex nA non-sparking and dust explosion-protection options; no flameproof Ex d |
| Ambient temperature | -40 ~ +80 °C (depending on enclosure and explosion-protection options) |
| Mounting | Direct integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847 |
4. Selection Guide (Complete Ordering Code)
Complete ordering number = 3730-2 + 16 digits. The table below is a quick reference of the grouped, digit-by-digit structure (positions essentially similar to the 3730-3, but without a fixed bus position); for detailed positions refer to T 8384-2 EN:
| Position | Item | Available codes / Meaning |
|---|---|---|
| P1 | Explosion protection | 0 = no explosion protection; 1 = ATEX Ex ia intrinsically safe; 3 = CSA intrinsically safe; 5 = dust explosion protection; 8 = Ex nA non-sparking |
| P2 | Inductive limit switch | 0 = none; 1 = SJ2-SN (normally closed contact) |
| P3 | Solenoid valve | 0 = none; 4 = with, 24 V DC |
| P4-P7 | Additional equipment (mutually exclusive group) | 0000 = none; 1000 = position transmitter (4-20 mA feedback); 0100 = separate position sensor; other combinations per data sheet |
| P8 | Self-diagnostics | 0 = standard EXPERT; 4 = EXPERTplus (enhanced self-diagnostics) |
| P9-P14 | Fixed / reserved positions | Fill in according to the data sheet; usually 0 for standard orders |
| P15-P16 | Special version | 00 = standard; other additional certifications per data sheet |
5. Complete Model Enumeration
The following lists the complete ordering code formats for the 3730-2 (16 digits). The complete codes shown here are illustrations constructed according to the grouped, digit-by-digit structure; for the meaning of each digit refer to Section 4. For formal orders, the code generated by the SAMSON official selection tool shall prevail (please consult us for confirmation).
| Complete ordering code | Digit-by-digit breakdown / Meaning |
|---|---|
3730-2 1000000400000000 | P1=1 (ATEX Ex ia intrinsically safe); P2=0 no limit switch; P3=0 no solenoid valve; P4-P7=0000 no additional equipment; P8=4 (EXPERTplus); P15-P16=00 standard version |
3730-2 1100000400000000 | P1=1 (ATEX Ex ia); P2=1 (SJ2-SN limit switch); P8=4 (EXPERTplus); remaining digits standard |
3730-2 1001000400000000 | P1=1 (ATEX Ex ia); P4-P7=1000 (with 4-20 mA position transmitter feedback); P8=4 (EXPERTplus); remaining digits standard |
Note: The above is for structural illustration only, to show that "3730-2 must be followed by a full 16-digit code"; it does not represent a confirmed model ready for direct ordering. For any uncertain position, always state "Please consult us for confirmation".
6. Related Models
| Related model | Type / Application |
|---|---|
| 3730-1 | Non-communication digital type, with LCD and autotune, no EXPERTplus diagnostics |
| 3730-3 | HART full-featured type, a widely used communication version in this family |
| 3730-6 | HART + supply/output pressure monitoring type, separate data sheet T 8384-6 EN (14-digit code) |
| 3725 | Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia |
| 3277 actuator | Pneumatic diaphragm actuator directly integrated with the positioner (linear) |
7. Common Spare Parts
| Component | Description / Part number |
|---|---|
| Position sensor assembly | Part number: please consult us for confirmation |
| i/p converter | Part number: please consult us for confirmation |
| Pneumatic amplifier | Part number: please consult us for confirmation |
| Display and operating unit (LCD and buttons) | Part number: please consult us for confirmation |
| Housing and cover assembly | Part number: please consult us for confirmation |
8. Matching Accessories
| Accessory | Model / Specification | Application |
|---|---|---|
| Filter pressure-reducing valve | Please consult us for confirmation | Filters and stabilizes the instrument air supply pressure |
| Position transmitter | Please consult us for confirmation | Outputs 4-20 mA valve position feedback signal |
| Inductive limit switch | SJ2-SN (normally closed contact) | Limit position feedback |
| Solenoid valve | 24 V DC | Forced venting / emergency action |
| Separate position sensor | Please consult us for confirmation | Position detection for separate actuator mounting |
| Reversing amplifier | 3710 | For use with double-acting actuators |
| Commissioning software | TROVIS-VIEW (SSP interface) | Parameter setting, commissioning and diagnostics |
9. Disclaimer
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.
10. Sources & Contact
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China