SAMSON 3730-1 Digital Positioner (No Communication) - Technical Data
1. Product Overview
The SAMSON 3730-1 is a non-communication digital electro-pneumatic valve positioner in the 3730 family. It adds a microprocessor in addition to the basic control platform, receives the 4-20 mA setpoint, drives a pneumatic linear or rotary actuator to form a valve position closed loop, and is equipped with an LCD display and a single rotary knob supporting autotune. Compared with the purely mechanical 3730-0, the 3730-1 is more convenient for local commissioning and for adapting valve/actuator characteristics; however, it has no fieldbus or HART communication and does not provide the EXPERTplus diagnostics of the 3730-2/3.

SAMSON 3730-1 positioner official product image (official image, for selection reference only)
Arrival Photos (taken by Baoman Industrial)

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked

SAMSON 3730 arrival photo, taken by Baoman Industrial, watermarked, identification details masked
2. Technical Description
Control principle: A closed loop formed by a valve position sensing element, an analog i/p converter, a pneumatic amplifier and a microprocessor electronic unit. The microprocessor compares the actual valve position with the setpoint and outputs a pneumatic control signal according to the control algorithm; initialization/autotune is supported, automatically adapting to valve and actuator characteristics, with parameters stored in non-volatile memory.
Display and operation: A rotatable LCD and a single rotary knob; parameters are listed in a single-level menu, allowing local viewing and setting without entering submenus. This is the main increment of the 3730-1 over the 3730-0.
Functional boundaries: No HART / PROFIBUS PA / FOUNDATION Fieldbus communication; no EXPERTplus diagnostics (for these diagnostics, select the 3730-2 or 3730-3). Optional additional functions include inductive limit switch, solenoid valve, position transmitter, separate position sensor, etc.
Ordering code structure: Complete ordering number = "3730-1" + 16 digits, using a grouped, digit-by-digit structure; its explosion-protection and additional-equipment positions are essentially similar to those of the 3730-3, but there is no fixed bus-identification position (the 4th digit is not required to be 0). For detailed positions refer to T 8384-2 EN; please consult us for confirmation of the final code.
3. Key Technical Data
| Item | Description |
|---|---|
| Input signal | 4-20 mA two-wire (no communication superimposed) |
| Supply air pressure | 1.4-7.0 bar (limitable by software) |
| Travel range | 3.6-300 mm (linear, depending on mounting) |
| Rotation angle range | 24°-100° (rotary) |
| Control type | Microprocessor control + autotune |
| Display and operation | LCD + single rotary knob, rotatable reading |
| Degree of protection | IP66 |
| Type of explosion protection | Mainly intrinsically safe Ex ia, including Ex nA non-sparking and dust explosion-protection options; no flameproof Ex d |
| Ambient temperature | -40 ~ +80 °C (depending on enclosure and explosion-protection options) |
| Mounting | Direct integration / NAMUR / IEC 60534-6-1 / VDI-VDE 3845 / 3847 |
4. Selection Guide (Complete Ordering Code)
Complete ordering number = 3730-1 + 16 digits. The table below is a quick reference of the grouped, digit-by-digit structure (positions essentially similar to the 3730-3, but without a fixed bus position); for detailed positions refer to T 8384-2 EN:
| Position | Item | Available codes / Meaning |
|---|---|---|
| P1 | Explosion protection | 0 = no explosion protection; 1 = ATEX Ex ia intrinsically safe; 3 = CSA intrinsically safe; 5 = dust explosion protection; 8 = Ex nA non-sparking |
| P2 | Inductive limit switch | 0 = none; 1 = SJ2-SN (normally closed contact) |
| P3 | Solenoid valve | 0 = none; 4 = with, 24 V DC |
| P4-P7 | Additional equipment (mutually exclusive group) | 0000 = none; 1000 = position transmitter (4-20 mA feedback); 0100 = separate position sensor; other combinations per data sheet |
| P8 | Self-diagnostics | 0 = standard (3730-1 does not include EXPERTplus) |
| P9-P14 | Fixed / reserved positions | Fill in according to the data sheet; usually 0 for standard orders |
| P15-P16 | Special version | 00 = standard; other additional certifications per data sheet |
5. Complete Model Enumeration
The following lists the complete ordering code formats for the 3730-1 (16 digits). The complete codes shown here are illustrations constructed according to the grouped, digit-by-digit structure; for the meaning of each digit refer to Section 4. For formal orders, the code generated by the SAMSON official selection tool shall prevail (please consult us for confirmation).
| Complete ordering code | Digit-by-digit breakdown / Meaning |
|---|---|
3730-1 1000000000000000 | P1=1 (ATEX Ex ia intrinsically safe); P2=0 no limit switch; P3=0 no solenoid valve; P4-P7=0000 no additional equipment; P8=0 standard; P15-P16=00 standard version |
3730-1 1100000000000000 | P1=1 (ATEX Ex ia); P2=1 (SJ2-SN inductive limit switch); remaining digits standard configuration |
3730-1 1001000000000000 | P1=1 (ATEX Ex ia); P4-P7=1000 (with 4-20 mA position transmitter feedback); remaining digits standard configuration |
Note: The above is for structural illustration only, to show that "3730-1 must be followed by a full 16-digit code"; it does not represent a confirmed model ready for direct ordering. For any uncertain position, always state "Please consult us for confirmation".
6. Related Models
| Related model | Type / Application |
|---|---|
| 3730-0 | Non-communication basic control type, no microprocessor, purely mechanical |
| 3730-2 | Non-communication full-featured type, with parameterization and EXPERTplus diagnostics |
| 3730-3 | HART full-featured type, a widely used communication version in this family |
| 3725 | Digital basic positioner, 10-digit ordering code, intrinsically safe Ex ia |
| 3277 actuator | Pneumatic diaphragm actuator directly integrated with the positioner (linear) |
7. Common Spare Parts
| Component | Description / Part number |
|---|---|
| Position sensor assembly | Part number: please consult us for confirmation |
| i/p converter | Part number: please consult us for confirmation |
| Pneumatic amplifier | Part number: please consult us for confirmation |
| Display and operating unit (LCD and buttons) | Part number: please consult us for confirmation |
| Housing and cover assembly | Part number: please consult us for confirmation |
8. Matching Accessories
| Accessory | Model / Specification | Application |
|---|---|---|
| Filter pressure-reducing valve | Please consult us for confirmation | Filters and stabilizes the instrument air supply pressure |
| Position transmitter | Please consult us for confirmation | Outputs 4-20 mA valve position feedback signal |
| Inductive limit switch | SJ2-SN (normally closed contact) | Limit position feedback |
| Solenoid valve | 24 V DC | Forced venting / emergency action |
| Reversing amplifier | 3710 | For use with double-acting actuators |
| Commissioning software | TROVIS-VIEW (SSP interface) | Parameter setting and commissioning |
9. Disclaimer
The information above is not guaranteed to remain valid at all times. Subsequent changes will not be notified separately. Please confirm the latest information at the time of inquiry.
10. Sources & Contact
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文
ENGLISH