Fisher DVC6205 Remote-Mount Digital Valve Controller
1. Product Overview
The Fisher FIELDVUE DVC6205 is the remote-mount body of the DVC6200 family, paired with a separate DVC6215 remote travel sensor. When the valve/actuator sees high temperature, strong vibration or limited space, the DVC6205 electronics can be mounted away from the valve and connected by cable to the valve-mounted DVC6215 sensor, for an ambient rating up to 125 °C.
DVC6205 retains the non-contact Hall feedback and full digital diagnostics (HART/FF/PROFIBUS PA), is available in aluminum only (option RM), and suits high-temperature, high-vibration service.





2. Technical Description
Remote-mount principle — focus of this page: select RM (remote mount) in segment ⑩: DVC6205 body + DVC6215 remote travel sensor. DVC6215 mounts on the valve for position sensing; DVC6205 body is remotely mounted, rated 125 °C, aluminum only.
Communication: HART 5 (HART 7 optional), FOUNDATION fieldbus or PROFIBUS PA, per basic model.
High-temperature capability: remote feedback unit -52 to +125 °C; body ambient -40 to +85 °C (fluorosilicone -52 to +85 °C).
Feedback and diagnostics: Hall-effect non-contact; diagnostics per protocol (HART HC/AD/PD/ODV, FF FD/AD/PD/PS).
3. Main Technical Specifications
| Parameter | Specification / Description |
|---|---|
| Basic model | DVC6205 (remote body) + DVC6215 (remote travel sensor), option RM |
| Input signal | 4-20 mA DC (HART) / FF / PROFIBUS PA, per protocol |
| Supply pressure | Max 10.0 bar (145 psig), or actuator rating whichever lower |
| Output signal | Pneumatic, up to full supply; travel span 0.4-9.5 bar; single/double acting |
| Independent linearity | Typical ±0.50% of output span |
| Ambient temperature | Body -40 to +85 °C (fluorosilicone -52 to +85 °C); remote feedback unit -52 to +125 °C |
| Enclosure rating | CSA/FM Type 4X, IP66; ATEX/IECEx IP66 |
| Connections | Supply/output 1/4 NPT internal; electrical 1/2 NPT (M20 optional) |
| Actuator compatibility | Linear stroke 6.5-606 mm; rotary 45-90° |
| Weight | DVC6205 ~4.1 kg; DVC6215 ~1.4 kg |
| Construction | A03600 low-copper aluminum (remote mount aluminum only); polyester cover |
| Hazardous-area approvals | CSA, FM, ATEX, IECEx, NEPSI etc. (per code 1A-1N) |
4. Selection Guide (ordering code by segment)
Complete code: DVC6205 ①_②_③_④_⑤_⑥_⑦_⑧_⑨_RM_…, segment ⑩ fixed at RM (remote mount), paired with DVC6215 remote travel sensor.
| Seg | Field | Remote-mount notes |
|---|---|---|
| Base | Model | DVC6205 body + DVC6215 sensor (this page) |
| ① | Hazardous area | 1A CSA / 1B FM / 1C ATEX Ex ia / 1D ATEX Ex d / 1F IECEx / 1I NEPSI etc. |
| ② | Housing material | 2A aluminum (remote mount aluminum only) |
| ③ | Housing type | 3A housing B (standard) |
| ④ | FF blocks | 4A n/a (H/P); 4B/4C/4D for FF |
| ⑤ | Pneumatic action | 5A single forward; 5B single reverse; 5C double acting |
| ⑥ | Feedback I/O | 6B none; 6C 4-20 mA transmitter; 6D single limit switch; 6A n/a (F/P) |
| ⑦ | Gauges | 7A/7B none; 7C 0-60 psig/0-4 bar; 7F 0-160 psig/0-11 bar |
| ⑧ | Connections | 8A 1/2 NPT+1/4 NPT; 8B/8C M20 adapter; 8D M20+1/4 NPT (ATEX) |
| ⑨ | Diagnostics | HC/AD/PD (HART); FD/AD/PD/PS (FF); ODV HART only |
| ⑩ | Other options | RM remote mount (fixed, DVC6205+6215, 125 °C, aluminum only); also LB low-bleed, H7 HART 7, SF filter, LL marine, PP plugs, CC custom |
Example: DVC6205 1D_2A_3A_4A_5A_6C_7C_8A_PD_RM_H7 (HART, ATEX Ex d, aluminum, housing B, single forward, 4-20 mA feedback, 0-60 psig dual gauge, 1/2+1/4 NPT, PD online diagnostics, remote mount 125 °C, HART 7). Consult for any unclear segment.
5. Complete Model Enumeration
| Series | Model / Description |
|---|---|
| Remote mount | DVC6205 (body) + DVC6215 (remote travel sensor, 125 °C, this page) |
| Integral aluminum | DVC6200H / F / P (standard mount) |
| Stainless housing | DVC6200S (2B stainless) |
| Safety | DVC6200-SIS (SIL3, RM optional) |
Historic / supply models (original information retained):
| Model / Configuration |
|---|
| DVC6200HC | DVC6200H | DVC6200F | DVC2000 | |
| DVC2000AC | DVC2000HC | DVC2000AD | DVC2000PD | |
| DVC6000 | DVC6010 | DVC6020 | DVC6030 | |
| DVC6010AC | DVC6010HC | DVC6010AD | DVC6010PD | |
| DVC6020AC | DVC6020HC | DVC6020AD | DVC6020PD | |
| DVC6030AC | DVC6030HC | DVC6030AD | DVC6030PD | |
| DVC6010FCFD | DVC6010LCFD | DVC6010SCFD | DVC6020FCFD | |
| DVC6020LCFD | DVC6020SCFD | DVC6030SCFD | DVC6010F | |
| DVC6020F | DVC6030F | DVC6005/6025PD | DVC6200S | |
| DVC6200SIS | DVC6205 | DVC6215 | DVC6205/DVC6215/HC/AD/PD | |
| Home > Products > Fisher > DVC6205 Remote Mount Digital Valve Controller |
6. Related Models
Related: DVC6200H/F/P (integral), DVC6200S (stainless), DVC6200-SIS (SIL3). Remote mount is only for high-temperature / high-vibration / confined-space service; body and sensor must be ordered together via the RM option.
7. Common Spare Parts
| Spare | Part number / Description |
|---|---|
| Remote travel sensor | DVC6215 (for DVC6205, rated 125 °C) |
| Repair kit | Consult Emerson by nameplate serial number |
| Supply/output gauge | Per segment 7 |
8. Accessories
Accessories: DVC6215 remote travel sensor and cable, filter regulator (e.g. Fisher 67CFR), high-temperature brackets and magnet, HART/FF configuration tools, intrinsic safety barriers.
9. Disclaimer
The above information is not guaranteed to remain valid and is subject to change without notice. Please confirm the latest information at the time of inquiry; certification status, production status and specific ordering codes should be verified with the manufacturer.
10. Sources & Contact
We supply the above models and the listed spare parts and accessories. For selection or supply inquiries, please consult +86 028-60220547 / info@bit-cd.com
Ordering & Inquiry
Baoman Industrial Technology (Chengdu) Co., Ltd Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

简体中文