Home » Service & Support » Technical Documentation
Fisher 67C/67D Filter Regulators - Complete Technical Data
Release time:2026-11-19 20:35:23 | Views:

The Fisher 67C / 67D series are direct-acting instrument filter regulators that supply stable, reduced-pressure air to positioners, electro-pneumatic converters and other field instruments. This article systematically covers product positioning, model comparison, technical parameters and selection points for engineering reference.

I. Overview & Series Positioning

The 67C and 67D are two port-size platforms of Fisher direct-acting instrument regulators. The core difference lies in connection size and flow capacity; other functional features (filtration, internal relief valve) are the same. All four series include a filter and internal relief valve, with a maximum inlet pressure of 250 psig (17.2 bar).

Aspect67C Series (67CFR / 67CFSR)67D Series (67DFR / 67DFSR)
Body connection1/4″ NPT1/2″ NPT
Main valve Cv0.361.33
Max inlet pressure (with filter)250 psig (17.2 bar)250 psig (17.2 bar)
Typical applicationSingle instrument / small-flow pneumatic supplyLarger actuators / multi-instrument manifold supply

Source: Fisher official "67C Series Instrument Regulators" technical manual (document 5469), "67D Series Regulators" technical manual (document 5858).

Fisher 67CFR filter regulator
Fisher 67CFR filter regulator (photographed by BAUMAN, with anti-theft watermark)

II. Four-Series Comparison

SeriesBody materialConnectionFilterInternal reliefPositioning
67CFRAluminum1/4″ NPTYes (5 µm)Yes (soft seat)Most common, economy
67CFSRStainless CF3M/CF8M1/4″ NPTYes (5 µm)Yes (soft seat)Corrosive / hygienic service
67DFRAluminum1/2″ NPTYes (5 µm)Yes (soft seat)Large port, economy
67DFSRStainless CF8M1/2″ NPTYes (5 µm)Yes (soft seat)Large port, corrosion resistant

III. Technical Data

3.1 67C Series (67CFR / 67CFSR)

Parameter67CFR (Aluminum)67CFSR (Stainless)
Body connection1/4″ NPS NPT (second outlet for gauge or plug)1/4″ NPS NPT (second outlet for gauge or plug)
Max inlet pressure250 psig (17.2 bar)250 psig (17.2 bar)
Outlet pressure range0-20 / 0-35 / 0-60 / 0-125 psig0-20 / 0-35 / 0-60 / 0-125 / 0-150 psig
Main valve Cv0.36 (Cq 11.7)0.36 (Cq 11.7)
Internal relief Cv0.0450.045
FilterStd 5 µm polyethylene; opt. 5 µm cellulose / 40 µm PVDF or stainlessStd 5 µm polyethylene; opt. 5 µm cellulose / 40 µm PVDF or stainless
Temperature (NBR std)-29 to 82 ℃ (-40 to 82 ℃ with SS bolts)-29 to 82 ℃ (-40 to 82 ℃ with SS bolts)
Weight1 lb (0.5 kg)4 lb (2 kg)
Smart Bleed™ setting6 psig (0.41 bar) differential6 psig (0.41 bar) differential

3.2 67D Series (67DFR / 67DFSR)

Parameter67DFR (Aluminum)67DFSR (Stainless)
Body connection1/2″ NPT (plus two 1/4″ NPT outlets)1/2″ NPT (plus two 1/4″ NPT outlets)
Max inlet pressure250 psig (17.2 bar)250 psig (17.2 bar)
Outlet pressure range0-20 / 0-35 / 0-60 / 0-125 psig0-20 / 0-35 / 0-60 / 0-125 / 0-150 psig
Main valve Cv1.33 (Cq 45.24)1.33 (Cq 45.24)
Weight1 kg (2.0 lb)2 kg (4.6 lb)

Source: Fisher official technical manuals (documents 5469 / 5858).

IV. Outlet Pressure & Spring Chart (Key to Selection)

Outlet pressureSpring colorApplicable series
0-20 psig (0-1.4 bar)Green / green stripeAll four series
0-35 psig (0-2.4 bar)Silver / silver stripeAll four series
0-60 psig (0-4.1 bar)Blue / blue stripeAll four series
0-125 psig (0-8.6 bar)Red / red stripeAll four series
0-150 psig (0-10.3 bar)BlackStainless 67CFSR / 67DFSR only

Elastomer & Temperature Range

ElastomerTemperature rangeApplication
NBR (standard)-29 to 82 ℃ (-40 to 82 ℃ with SS bolts)Standard air / instrument air
FKM (Viton)-18 to 82 ℃ (up to -18 to 149 ℃ with PVDF/SS element)High temperature, corrosive chemicals
VMQ (silicone, low temp)-51 to 82 ℃Low temperature (incompatible with hydrocarbon gas)

V. Selection Points & Precautions

① Determine port size first: 1/4″ → 67C platform; 1/2″ → 67D platform. ② Then material and service: aluminum for standard air/economy-priority; stainless for corrosive gas, food/pharma, coastal/high-humidity. ③ Choose spring range per outlet pressure. ④ Choose with/without gauge per local indication needs. ⑤ Select Smart Bleed™ internal check valve when downstream venting on air failure is required.

Note: The internal relief valve is for very small seat leakage only, not full overpressure protection; if inlet pressure may exceed the downstream equipment rating, add a separate relief/limiting device. Do not confuse port sizes (67C = 1/4″, 67D = 1/2″). Silicone elastomer is incompatible with hydrocarbon gas.

Source: Fisher official technical manuals (documents 5469 / 5858); final selection subject to Emerson official confirmation.

Fisher 67CFR regulator body
67CFR regulator body (batch information obscured, with anti-theft watermark)

VI. Selection Guide & Common Models

Selection guide: When selecting from the 67C/67D family, first decide the duty — instrument air regulation typically uses the 67C/67CFR, while larger flow calls for the 67D series. Next, choose materials based on media and installation environment (aluminium for general service, stainless for corrosive or hygienic applications). The outlet-pressure range and spring range should be checked together, as this is the key to correct selection. Models with internal relief or Smart Bleed™ suit applications needing small seat-leakage relief.

Common models: 67C, 67CFR (with filtration and internal relief), 67CFSR (stainless), 67D, 67DFR, 67DFSR, with common outlet ranges of 0–20 / 0–35 / 0–60 / 0–125 psig.

If you are specifying instrument air or a regulation application, or would like to know about availability of these models and spare parts, please feel free to contact us. We can help check the right model and spring range against your media, inlet pressure and required outlet setting.

BAUMAN Industrial Technology (Chengdu) Co., Ltd.

We supply imported brands including Fisher, Masoneilan, SAMSON, ABB and Siemens — valve positioners, actuators, filter regulators and spare parts. Common models kept in stock; selection consulting, technical support and field service available.
Tel: +86 028-60220547 | Email: info@bit-cd.com
Address: Room 1108, Building A, Tingbiao Central Plaza, No. 158 Erxianqiao East Road, Chenghua District, Chengdu, Sichuan Province, China

Disclaimer: The information above is not guaranteed to remain valid and may be modified without separate notice. Please confirm the latest information at the time of inquiry.